Plan Review Details - Permit 05070366
Plan Review Stops For Permit 05070366
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2007-10-04 Cont ID  
Sent By shill Date 2007-10-04 Time 16:05 Rev Time 0.00
Received By shill Date 2007-10-04 Time 16:05 Sent To  
Notes
2007-10-04 16:06:35****CORRECTIONS - RESTAMP****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER ARE TO BE
 ORIGINALS, FAC61G15-23.THE ARCHITECTURAL SHEETS HAVE
 BEEN STAMPED.HAVE THE ENGINEERING SHEETS SIGNED,
 SEALED AND DATED AND SUBMIT FOR RESTAMP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-07-10 Cont ID  
Sent By shill Date 2007-07-10 Time 12:56 Rev Time 0.00
Received By shill Date 2007-07-10 Time 12:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-06-12 Cont ID  
Sent By shill Date 2007-06-12 Time 12:09 Rev Time 0.00
Received By shill Date 2007-06-12 Time 12:09 Sent To  
Notes
2007-06-12 12:11:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ONE NOA HAS BEEN STAMPED (03-1021.02, US DOOR).
 THE OTHER TWO WERE NOT A PART OF THE ISSUED PERMIT.
 SUBMIT THEM AS A REVISION FOR REVIEW.
  
 2.)PROVIDE THE ELEVATION CERTIFICATE AS THIS PROPERTY
 IS LOCATED IN A HIGH HAZARD FLOOD ZONE.CONTRACTOR HAD
 BEEN INFORMED THAT A CO HOLD WAS PLACED ON THIS JOB
 PENDING RECEIPT OF THE ELEVATION CERTIFICATE.PLEASE
 SUBMIT AT THIS TIME.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-04-29 Cont ID  
Sent By shill Date 2007-04-29 Time 15:09 Rev Time 0.00
Received By shill Date 2007-04-29 Time 15:09 Sent To  
Notes
2007-04-29 15:16:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THIS WAS ISSUED WITH A PROVISO THAT AN ELEVATION
 CERTIFICATE BE PROVIDED AT TIME OF CONCRETE POUR.THIS
 WAS NOT PROVIDED.A CO HOLD HAS BEEN PLACED AND WILL
 BE REMOVED WHEN THIS ITEM IS ADDRESSED.
  
 2.)THE ENERGY CALCS DID NOT PASS ELECTRIC REVIEW.
 ENERGY CALCS UNDER THIS PERMIT TO BE FBC2001, NOT
 FBC2004.
  
 3.)THE ORIGINAL DESIGNER WAS JEFFREY GASPAR, THIS
 PLAN IS BY MB DESIGN.ONLY ONE DESIGNER OF RECORD CAN
 BE ON THIS PROJECT.ADDRESS.
  
 4.)DECLARE OCCUPANT LOAD, OCCUPANCY CLASSIFICATION. S
 WAS DECLARED, APPEARS THAT IT IS MIXED, B AND S. WHAT
 WILL BE STORED IN THE AIR CONDITIONED WAREHOUSE AREA?
 PROVIDE MORE INFORMATION IN REGARDS TO THE USE OF THIS
 SPACE.
  
 5.)WALL LEGEND A DOES NOT MATCH WALL A ON THE FLOOR
 PLAN.
  
 6.)SHOW WALL FINISHES FOR THE BATHROOMS, FBC1204.2.
  
 7.)THERE ARE REFERENCES TO FBC2004.THIS PERMIT WAS
 ISSUED UNDER FBC2001.
  
 8.)SEE FBC TABLE 704.1, OCCUPANCY SEPARATION
 REQUIREMENTS.SHOW OCCUPANCY OF EACH AREA, AND
 SEPARATION, FBC704.1.IF EXEMPT, SHOW HOW THIS WILL BE
 EXEMPT FBC704.1.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-01-23 Cont ID  
Sent By shill Date 2007-01-23 Time 16:43 Rev Time 0.00
Received By shill Date 2007-01-23 Time 16:43 Sent To  
Notes
2007-01-23 16:44:09REVISION S1 AND S2

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-18 Cont ID  
Sent By shill Date 2006-04-18 Time 17:06 Rev Time 0.00
Received By shill Date 2006-04-18 Time 16:56 Sent To  
Notes
2006-07-21 00:00:00PA FOR ROOF RETURNED TO CONTRACTOR (DID
 NOT SELECT APPROVED ASSEMBLY), NEEDS
 PRODUCT APPROVALS WITH ROOF PERMIT
 APPLICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-23 Cont ID  
Sent By shill Date 2006-03-23 Time 14:16 Rev Time 4.00
Received By shill Date 2006-03-23 Time 08:30 Sent To  
Notes
2006-03-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS TWO REVIEWS,
 NUMBERING REMAINING THE SAME FOR
 CONSISTENCY
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 PLEASE KEEP THE NOC PROVIDED IN THE
 PACKAGE.
  
 5.)THIS PARCEL IS IN A FLOOD ZONE.A
 FORM BOARD ELEVATION CERTIFICATE WILL BE
 REQUIRED.THE FINISHED FLOOR IS TO BE
 SIX INCHES ABOVE BASE FLOOD ELEVATION,
 CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(2). NOTE MINIMUM ELEVATION ON THE
 PLAN.
  
 THIS HAS BEEN ADDRESSED.THE PERMIT
 WILL BE ISSUED WITH A PROVISO THAT AN
 ELEVATION CERTIFICATE BE PROVIDED AT
 FORM BOARD INSPECTION.
  
 6-7.)ADDRESSED.
  
  
 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1.
 SHOW ALL DISTANCES FROM THE PROPERTY
 LINE SO THAT TABLE 500 AND TABLE 600
 COMPLIANCE CAN BE DETERMINED.SHOW
 ACCESSIBLE PARKING, ACCESSIBLE ROUTE
 FROM THE PUBLIC WAY FBC CHAPTER 11.
  
 THIRD REVIEW - THE ACCESSIBLE PARKING IS
 TO COMPLY WITH FBC11-4.1.2(5)(A),
 ACCESSIBLE PARKING SHALL BE PROVIDED IN
 EACH SUCH PARKING AREA.NO ACCESSIBLE
 PARKING SHOWN IN THE REAR PARKING LOT.
 ACCESSIBLE ROUTE AT THE REAR OF THE
 BUILDING IS NOT CLEAR.
  
 THE PARKING IS TO COMPLY WITH THE CITY
 OF WEST PALM BEACH STANDARDS, SEE
 ATTACHED DETAIL.
  
 NOTE THAT THE CIVILS ARE TO BE
 CONSISTENT WITH THE ARCHITECTURALS.
  
 9-13.)ADDRESSED.
  
 16.)THE FOLLOWING NOAS WERE REVIEWED
 AND APPEAR CODE COMPLIANT EXCEPT AS
 NOTED BUT REQUIRE FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 ARCH ALUMINUM IMPACT WALL 3000
 ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR
 MODEL 651 ROLLING DOOR ? EXPIRED NOA
  
 ARCH ALUMINUM IMPACT WALL 3000 OK.
 THE ARCH ALUMINUM MAGNUM STILE ENTRANCE
 DOOR NOT IN THE PACKAGE.ANY ITEMS NOT
 PROPERLY SUBMITTED AND REVIEWED PRIOR TO
 PERMIT ISSUANCE WILL REQUIRE SEPARATE
 PERMITS.
 ROLLING DOOR OK.
  
 17.)PROVIDE PRODUCT APPROVALS FOR THE
 REAR METAL DOOR, FLAT ROOF, STANDING
 SEAM, ROLLING DOOR.ANY PRODUCT
 APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  
 PRODUCT APPROVALS FOR THE REAR METAL
 DOOR, STANDING SEAM ROOF, ROLLUP DOOR
 OK.
  
 CHOOSE THE APPROVED ASSEMBLY YOU ARE
 USING FROM THE CHOICES PROVIDED IN THE
 NOA.IF THIS IS NOT ADDRESSED PRIOR TO
 PERMIT ISSUANCE,
  
 18.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT ADDRESSED IN THE NEXT
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-10 Cont ID  
Sent By shill Date 2005-11-10 Time 19:17 Rev Time 2.00
Received By shill Date 2005-11-10 Time 18:36 Sent To  
Notes
2005-11-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS REVIEW, NUMBERING
 REMAINING THE SAME FOR CONSISTENCY
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 FS713.13 REQUIRES THE CONTRACTOR?S NAME
 AND ADDRESS SO THAT NOTICES CAN BE
 SERVED AS REQUIRED BY THE FLORIDA LEIN
 LAW.CONTRACTOR ADDRESS IS NOT ON THE
 NOC.
  
 5.)THIS PARCEL IS IN A FLOOD ZONE.A
 FORM BOARD ELEVATION CERTIFICATE WILL BE
 REQUIRED.THE FINISHED FLOOR IS TO BE
 SIX INCHES ABOVE BASE FLOOD ELEVATION,
 CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(2). NOTE MINIMUM ELEVATION ON THE
 PLAN.
  
 NOT ADDRESSED.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 7.)A WAREHOUSE SHOULD BE S OCCUPANCY,
 THE OFFICE AREA IS B.PLEASE SEE FBC312
 AND FBC305.BUSINESS OCCUPANCY WAS
 DECLARED ON SHEET A2.
  
 NOT ADDRESSED; STILL SHOWS A WAREHOUSE
 AND DECLARES B OCCUPANCY.BASED ON THE
 FLOOR PLAN WHICH SHOWS A WAREHOUSE, THE
 OFFICES ARE ACCESSORY TO THE PRIMARY
 OCCUPANCY OF STORAGE, SEE FBC704.1.2.1.
  
  
 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1.
 SHOW ALL DISTANCES FROM THE PROPERTY
 LINE SO THAT TABLE 500 AND TABLE 600
 COMPLIANCE CAN BE DETERMINED.SHOW
 ACCESSIBLE PARKING, ACCESSIBLE ROUTE
 FROM THE PUBLIC WAY FBC CHAPTER 11.
  
 9.)THE AREA INCREASE CALCULATIONS ON
 A2 STATES THAT THE ALLOWABLE AREA FOR
 BUSINESS TYPE V IS 9000 SF.PLEASE NOTE
 THAT IT IS 14000 SF PER FBC TABLE 500
 AND 16000 FOR STORAGE.
  
 YOU HAVE CHANGED THE BUILDING TYPE TO
 VI.AREA ALLOWED FOR TYPE VI, STORAGE
 OCCUPANCY, UNPROTECTED UNSPRINKLED IS
 6000.THE BUILDING IS NOT COMPLIANT FBC
 TABLE 500.
  
 12.)CLARIFY THE ROOF AREA ON A3.
  
 13.)DOOR HARDWARE TO COMPLY WITH
 FBC11-4.13.9.
  
 THIS WAS ADDRESSED BY PROVIDING THE CODE
 SECTION.PLANS ARE TO BE PROVIDE DESIGN
 CRITERIA, FBC*104.2.1.
  
 16.)THE FOLLOWING NOAS WERE REVIEWED
 AND APPEAR CODE COMPLIANT EXCEPT AS
 NOTED BUT REQUIRE FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 ARCH ALUMINUM IMPACT WALL 3000
 ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR
 MODEL 651 ROLLING DOOR ? EXPIRED NOA
  
 FLORIDA PRODUCT APPROVALS REQUIRED IN
 ADDITION TO THE NOAS PROVIDED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 17.)PROVIDE PRODUCT APPROVALS FOR THE
 REAR METAL DOOR, FLAT ROOF, STANDING
 SEAM, ROLLING DOOR.ANY PRODUCT
 APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  
 FLORIDA PRODUCT APPROVALS REQUIRED
 FAC9B72, WWW.FLORIDABUILDNIG.ORG
  
 18.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT ADDRESSED IN THE NEXT
 REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By shill Date 2005-08-13 Time 22:51 Rev Time 3.00
Received By shill Date 2005-08-13 Time 20:18 Sent To  
Notes
2005-08-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY (CHANGE OF USE).THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION. 233-5025
  
 3.)PLEASE CONTACT JOHN HIGGINS IN
 REGARDS TO ADDRESSING FOR THIS PARCEL.
 OUR RECORDS CONFLICT WITH THE ADDRESS ON
 YOUR APPLICATION.HE CAN BE REACHED AT
 805-1239.***NOTE 8/16 - J.HIGGINS
 CHANGED OUR RECORDS TO REFLECT 5760
 CORPORATE WAY AS CORRECT ADDRESS FOR
 THIS PARCEL***
  
 4.)GENERAL NOTES, ITEM 12 ON THE
 SURVEY PREPARED BY TARGET SURVEYING,
 INC. STATES THAT THE SURVEY WILL NOT BE
 USED FOR CONSTRUCTION OR PERMITTING.
 SUBMIT A SURVEY FOR PERMITTING.
  
 5.)THE SURVEYOR IS REQUIRED TO DATE
 THE SEAL, FS472.025, SEE ATTACHED.THE
 SEAL IS TO BE LEGIBLE.
  
 5.)THIS PARCEL IS IN A FLOOD ZONE.A
 FORM BOARD ELEVATION CERTIFICATE WILL BE
 REQUIRED.THE FINISHED FLOOR IS TO BE
 SIX INCHES ABOVE BASE FLOOD ELEVATION,
 CITY OF WEST PALM BEACH MUNICIPAL CODE
 94-546(2). NOTE MINIMUM ELEVATION ON THE
 PLAN.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 7.)A WAREHOUSE SHOULD BE S OCCUPANCY,
 THE OFFICE AREA IS B.PLEASE SEE FBC312
 AND FBC305.BUSINESS OCCUPANCY WAS
 DECLARED ON SHEET A2.
  
 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1.
 SHOW ALL DISTANCES FROM THE PROPERTY
 LINE SO THAT TABLE 500 AND TABLE 600
 COMPLIANCE CAN BE DETERMINED.SHOW
 ACCESSIBLE PARKING, ACCESSIBLE ROUTE
 FROM THE PUBLIC WAY FBC CHAPTER 11.
  
 9.)THE AREA INCREASE CALCULATIONS ON
 A2 STATES THAT THE ALLOWABLE AREA FOR
 BUSINESS TYPE V IS 9000 SF.PLEASE NOTE
 THAT IT IS 14000 SF PER FBC TABLE 500
 AND 16000 FOR STORAGE.
  
 10.)TYPE V CONSTRUCTION IS TO HAVE
 NONCOMBUSTIBLE WALLS.THE PARAPET AND
 THE WALL BELOW THE HIP ROOF SHOWS WOOD
 SHEATHING.SEVERAL DETAILS ARE
 AFFECTED; 2-A3, D-A4.CHECK ALL
 DETAILS.
  
 11.)DOOR 3 APPEARS TO BLOCK OVER HALF
 THE WIDTH OF THE HALLWAY, FBC1012.1.4.
  
 12.)CLARIFY THE ROOF AREA ON A3.
  
 13.)DOOR HARDWARE TO COMPLY WITH
 FBC11-4.13.9.
  
 14.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 15.)PROVIDE LEGIBLE NOAS.THEY ARE
 AVAILABLE EITHER AT WWW.MIAMIDADE.GOV
 (FIND A DEPT, BUILDING CODE COMPLIANCE,
 PRODUCT CONTROL) OR AT
 WWW.FLORIDABUILDING.ORG (PRODUCT
 APPROVAL).
  
 16.)THE FOLLOWING NOAS WERE REVIEWED
 AND APPEAR CODE COMPLIANT EXCEPT AS
 NOTED BUT REQUIRE FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.
  
 ARCH ALUMINUM IMPACT WALL 3000
 ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR
 MODEL 651 ROLLING DOOR ? EXPIRED NOA
  
 17.)PROVIDE PRODUCT APPROVALS FOR THE
 REAR METAL DOOR, FLAT ROOF, STANDING
 SEAM, ROLLING DOOR.ANY PRODUCT
 APPROVALS NOT REVIEWED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 13:28 Sent To  
Notes
2007-04-08 13:54:36 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THIS PROJECT WAS PERMITTED UNDER
 THE 2001 FBC .
 PLEASE SEE THIS WAS UNDER THE PREVIOUS VERSION. PLEASE
 SEE THAT THE ENERGY CALCULATIONS DO NOT COORDINATE WITH
 THE PLANS FOR THE FIXTURES, TYPES, WATTAGES, ETC.
 PLEASE SEE THE FIXTURE LEGEND. PLEASE SEE THE LIGHTING
 DENSITIES PROVIDED ON PLANS DO NOT CORRELATE WITH THE
 ACTUAL FIXTURES ON PLANS OR WHAT IS IN ENERGY
 CALCULATIONS.
 PLEASE REVISE ALL OF THE ENERGY CALCULATIONS AND
 DENSITIES ALONG WITH REVISED PLANS AS NEEDED TO
 COORDINATE ALL.
 FBC 13-415.1.AB.1.1, 13-415.2
 FBC 106.1.2 ADMIN SECTION.
  
 2) NOTE: PLEASE SEE REVISED RISER WHICH SHOWS A 200AMP
 DISCONNECT FEEDING A 100AMP RATED PANEL. PLEASE ALSO
 SEE PLANS WHICH INDICATE THE SAME.
 PLEASE SEE THE LOAD SHOWN AT 161AMPS EXCEEDS THAT OF
 THE RATING OF PANEL ALSO.
 PLEASE SEE PANEL SCHEDULE WHICH INDICATES A 200A RATED
 BREAKER IN THIS 100AMP PANEL.
 PLEASE SEE 240.4, 310.16 ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE MISSING CIRCUITING ON PLANS FOR
 EM/EXT LTS.PLEASE SEE 700.12E FOR CIRCUITING.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-07 Cont ID  
Sent By dpalmer Date 2006-03-07 Time 19:46 Rev Time 0.00
Received By dpalmer Date 2006-03-07 Time 19:28 Sent To  
Notes
2006-03-07 00:00:00ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-17 Cont ID  
Sent By dpalmer Date 2005-11-17 Time 22:06 Rev Time 0.50
Received By dpalmer Date 2005-11-17 Time 21:37 Sent To  
Notes
2005-11-17 00:00:00**** UNSAT ****
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 OTHER COMMENTS , PLEASE ADDRES BELOW AT
 THIS TIME.
  
 1)NOTE: PLEASE SEE NOTE # 4 FROM
 PREVIOUS REVIEW WHICH REQUESTED TO
 CLARIFY ONE UNIT SHOWN ON PLANS WHICH
 SEEMS TO GETTING BUILT OUT HOWEVER RISER
 DIAGRAM AND RISER NOTES DO NOT TEND TO
 CORRELATE WITH THIS.
 PLEASE SEE CIRCUTING FOR PANEL T-1
 CORRLELATES WITH THIS BLD OUT.
 PLEASE PROVIDE INFORMATION FOR
 DISCONNECT METER ETC.
 215.5
  
 2)NOTE: THIS IS ONLY A NOTE: RECEPT
 CIRCUITED TO #9, SEEMS TO BE INDICATED
 TO BE ABOVE CEILING.
 RECEPTS ARE NOT PERMITTED ABOVE.
  
 3)NOTE: PLEASE SEE A RE-RECORDED NOC
 WILL BE REQUIRED AS THE ONE PRESENTLY
 SUBMITTED HAS EXPIRED.
 PLEASE SEE FS 713.13(2).
 PLEASE KNOW, IF WORK HAS NOT COMMENCED
 WITH IN 90 DAYS OF RECORDING, THE NOC
 SHALL BECOME VOID.
 THIS NOTE ID NOT FOR THE ELECTRICAL
 ENGINEER.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By dpalmer Date 2005-07-27 Time 21:22 Rev Time 1.75
Received By dpalmer Date 2005-07-26 Time 21:03 Sent To  
Notes
2005-07-27 00:00:00*********** UNSAT ******************
  
 PLEASE SEE ADDRESS IN OUR SYSTEM FOR PCN
 USED SHOWS "5660" CORP WAY. PLEASE SEE
 PERMIT APPLICATION AND PLANS SHOWS
 "5760". PLEASE SEE ADDRESSING WILL NEED
 TO BE CORRELATED.
  
 1)NOTE: PLEASE LABEL EACH
 WAREHOUSE/OFFICE SPACE. IE: UNIT
 A,B,C,,,,1,2,3,, ETC
 PLEASE CORRELATE THIS AND LABEL RISER
 ACCORD.
 215.5
  
 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED
 TYPPICAL PANEL SCHEDULE.
 PLEASE ALSO SHOW CIRCUITING FOR HOUSE
 LOADS.
 215.5
  
 3)NOTE: PLEASE CLARIFY, PLANS APPEAR TO
 SHOW EM/EXT LTS CIRCUITED TO HOUSE
 PANEL? YET, NOTE ON ON LIGHTING LEGEND
 MENTIONS AHEAD OF LOCAL LIGHTING.
 PLEASE SEE 700.12E, WHICH REQUIRES
 FIXTURES TO BE CONNECTED TOBRANCH
 CIRCUIT FOR LOCAL AREA LIGHTING.
 PLEASE ALSO SEE THIS WOULD INDICATEA
 CROSS OVER IN ELECTRICAL CIRCUITS INTO
 EACH TENANT SPACE?
  
 4)NOTE: PLEASE CLARIFY PLANS WHICH
 APPEARS TO SHOW ONE UNIT, OFFICE
 WAREHOUSE BEING BUILT OUT. HOWEVER,
 RISER DIAGRAM DOES NOT CORREALTE WITH
 THIS?
 RISER SHOWS ALL DISCONNECTS AND PANELS
 AS FUTURE?
  
 5)NOTE: PLEASE SEE 600.5 WHICH REQUIRES
 THE TENANT SIGN CIRCUIT TO BE LOCATED AT
 ENTRANCE INTO UNIT.
 PLEASE SEE J-BOX SEEMS TO BE ABOVE
 WINDOW AS FOR A WINDOW SIGN? PLEASE SEE
 NEXT COMMENT.
  
 6)NOTE: PLEASE SEE IF ANY OF THESE UNITS
 ARE INTENDED FOR RETAIL SPACE, A WINDOW
 RECEPT WILL BE REQUIRED ABOVE WINDOW.
 PLEASE SEE THIS IS ONLY A COMMENT AT
 THIS TIME OF NOW UNITS ARE GOING TO
 BUILT OUT. IF ANY UNIT IS BUILT OUT AT
 THIS TIME, A RECEPT WILL BE REQUIRED.
 210.62,220.12
  
 7)NOTE: PLEASE INCLUDE CONDUCTORS FROM
 MAIN TO GUTTER . 215.5,240.4,310.16
 PLEASE ALSO SEE NEXT COMMENT FOR
 EQUIPMENT GROUNDING CONDUCTOR.
  
 8)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST
 MEANS OF DISCONNECT.250.24,250.6,
 250.110 ETC.
 PLEASE SEE NOTE #8 ON RISER NOTES DOES
 NOT SEEM TO INCLUDE THIS.?
  
 9)NOTE: PLEASE ALSO SEE NOTE #8 ON RISER
 APPEARS TO SHOW CONDUITS/FEEDERS ETC ON
 LOAD SIDE OF TENANT DISCONNECTS ALSO
 BEING CONNECTED TO FPL TRANSFORMER?
 PLEASE SEE RISER DIAGRAM.
  
 10)NOTE: PLEASE SEE NOTES #4&5 ON RISER
 NOTES PERTAINING TO GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE 250.50, WHICH ALSO
 REQUIRES FOOTER STEEL. PLEASE INCLUDE
 THIS IN A DETAIL TO BE PROVIDED FOR
 GROUNDING ELECTRODE SYSTEM.
  
 11)NOTE: PLEASE CLARIFY NOTE #15 ON
 RISER AND NOTES WHICH MENTIONS TO
 INSTALL, 2-2" CONDUITS FROM "GUTTER" TO
 EACH TEANT SPACE? PLEASE SEE RISER SHOWS
 THESE CONDUITS BEING INSTALLED TO EACH
 DISCONNECT? PLEASE ALSO CLARIFY (TWO)
 CONDUITS FOR EACH FEEDER?
 215.5
  
 12)NOTE: PLEASE INCLUDE SIZING FOR
 GUTTER AT THIS TIME. PLEASE SEE 366.
  
 13)NOTE: PLEASE CLARIFY PANEL "HP"
 SHOWING A BACK-FED 60A BRKR FOR MAIN,
 YET RISER AND PLANS BOTH INDICATE A
 FUSIBLE MAIN DISCONNECT RIGHT NEXT TO
 PANEL??
 PLEASE SEE THE ADDITIONAL "MAIN" WITH A
 RETENTION CLIP MAY BE INSTALLED, HOWEVER
 THIS IS NOT REQUIRED. THIS IS ONLY A
 NOTE. IF SHOWN ON PLANS THEN IT WILL BE
 REQUIRED TO BE INSTALLED.
 215.5
  
 14)NOTE: PLEASE CLARIFY FIXTURE "A"
 SHOWN ON PLANS; LIGHT FIXTURE ON PLAN
 AND ON "LIGHTING LEGEND" APPEARS TO SHOW
 THIS FIXTURE AS A SURFACE MOUNBTED
 SCONCE TYOE OF FIXTURE, HOWEVER PLEASE
 SEE " LIGHTING FIXTURE SCHEDULE" WHICH
 DOES NOT CORRELATE WITH THIS FOR FIX
 "A".?
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE WHICH SHOULD BE
 SEPARATE AND MRKED VOID/OLD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-26 00:00:00IN ELECTRICAL FOR REVIEW.
 PLAN REVIEW NOTES FOR ELECTRICAL WILL
 FOLLOW ONCE REVIEW IS COMPLETE.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-07-21 Cont ID  
Sent By rchokshi Date 2006-07-21 Time 14:17 Rev Time 0.00
Received By rchokshi Date 2006-07-21 Time 14:15 Sent To  
Notes
2006-07-21 00:00:00PASSED
 ALL PREVIOUS COMMENTS TAKEN CARE OF.
 RASIK

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-11-10 Cont ID  
Sent By mamini Date 2005-11-10 Time 14:27 Rev Time 1.00
Received By mamini Date 2005-11-10 Time 14:27 Sent To  
Notes
2005-11-10 00:00:00PASSED WITH PROVISOS:
  
 1. PARKING STALLS MUST BE PAINTED WITH
 DOUBLE 4" WIDE STRIPES, PER CITY'
 REQUIREMENT.
 2. POLLUTION PREVENTION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO ANY
 CONSTRUCTION ACTIVITIES.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By mamini Date 2005-07-20 Time 14:07 Rev Time 1.00
Received By mamini Date 2005-07-20 Time 14:07 Sent To  
Notes
2005-07-20 00:00:00FAILED:
  
 1. PLEASE NOTE THAT CONNECTIONS TO THE
 CITY' SERVICES AND THE LOCATION OF THE
 PROPOSED F.HYD AND THE 12' U.E. MUST BE
 APPROVED BY THE PUBLIC UTILITIES AND
 ENGINEERING.
 2. DUMPSTER ENCLOSURE MUST BE SIZED PER
 CITY OF WPB REQUIREMENT, IF GARBAGE IS
 TO BE PICKED UP BY THE CITY.
 3. ALL OFF STREET REGULAR PARKING STALLS
 MUST BE PAINTED WITH DOUBLE 4" WIDE
 STRIPES, PER CITY REQUIREMENT.
 4. PLEASE PROVIDE CALCULATIONS FOR TOTAL
 SITE AREA, BUILDING AREA, AND PERVIOUS &
 IMPERVIOUS AREA.
 5. PLEASE NOTE THAT, IN ADDITION TO THE
 ABOVE REVIEW COMMENTS, THE REVIEW
 COMMENTS FROM THE PUBLIC UTILITIES AND
 ENGINEERINGMUST BE ADDRESSSED/OR
 IMPLEMENTED INTO THE CIVIL PLANS PRIOR
 TO GETTING APPROVAL FROM BUILDING
 DEPARTMENT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-05-18 Cont ID  
Sent By mwennerg Date 2007-05-18 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2007-05-18 Time 14:30 Sent To  
Notes
2007-05-18 14:34:55***DENIED***
  
 1) PLANS INDICATE STORAGE OCCUPANCY UNDER BUILDING
 DATA. PLEASE CLARIFY OCCUPANCY CLASSIFICATION AS
 STORAGE WOULD SEEM TO APPLY TO PART OF THIS PROJECT.
  
 2) PLEASE SEE OTHER REVIEW COMMENTS REGARDING DESIGNER
 OF RECORD REQUIREMENTS.
  
 3) WHEN APPLYING CODE REFERENCE, THE APPLICABLE EDITION
 SHALL BE USED.
  
 4) PLEASE INDICATE WHAT WILL BE STORED IN THE
 WAREHOUSE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-11-16 Cont ID  
Sent By nmccray Date 2005-11-16 Time 11:44 Rev Time 0.00
Received By nmccray Date 2005-11-16 Time 11:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By mwennerg Date 2005-08-11 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2005-08-11 Time 15:03 Sent To  
Notes
2005-08-11 00:00:00******DENIED******
  
 1) PLANS INDICATE THAT INTERIOR FINISH
 ON WALLS AND CEILINGS TO BE CLASS A, B,
 OR C. PLEASE INDICATE THE CLASSIFICATION
 OF WALLS AND CEILINGS APPLICABLE TO THIS
 OCCUPANCY.
  
 2) IT IS UNDERSTOOD THAT MONUMENT SIGNS
 ARE PLANNED TO BE INSTALLED UPON
 APPROVAL. IF A DELAY SHOULD OCCUR PRIOR
 TO OCCUPANCY, ADDRESSES ON THE BUILDING
 WILL BE REQUIRED THAT ARE AT LEAST 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 3) NOTE #4 REFERS TO A KEY LOCKING
 DEVICE ON THE EGRESS SIDE OF EACH MAIN
 EXIT DOOR. THIS ARRANGEMENT IS ONLY
 ACCEPTABLE IF ALL THE CRITERIA IN
 ACCORDANCE WITH NFPA 101, SECTION
 7.2.1.5.4 IS MET.
  
 4) SOME EXIT SIGNS APPEAR TO BE MISSING
 ON THE WAREHOUSE DOORS LEADING TO THE
 OFFICE AREAS.
  
 5) PLEASE SHOW ALL THE EMERGENCY
 LIGHTING FACILITIES. THERE APPEARS TO BE
 SOME MISSING IN WAREHOUSE AREAS.
  
 6) 2A-10B,C RATED FIRE EXTINGUISHERS
 SHALL BE MOUNTED AT DISTANCES TO SATISFY
 THE 75' TRAVEL DISTANCE REQUIREMENT.
  
 7) PLEASE ILLUSTRATE REQUIRED FIRE
 SEPARATION REQUIREMENT FOR SEPARATE
 TENANT SPACES.
  
 8) PLEASE SHOW LOCATION AND DISTANCE OF
 CLOSEST FIRE HYDRANT IN RELATION TO
 BUILDING.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-10-12 Cont ID  
Sent By bpowell Date 2007-10-17 Time 09:27 Rev Time 0.00
Received By shill Date 2007-10-12 Time 15:13 Sent To Z
Notes
2007-10-12 15:13:59TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-10-01 Cont ID  
Sent By adarroug Date 2007-10-01 Time 09:02 Rev Time 0.00
Received By adarroug Date 2007-10-01 Time 08:26 Sent To Z
Notes
2007-10-01 09:02:39TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 15:01 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 15:01 Sent To Z
Notes
2007-09-28 15:01:53TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 11:07 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 11:07 Sent To B
Notes
2007-06-18 11:07:58TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 11:37 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 11:37 Sent To B
Notes
2007-05-29 11:38:13TO "SHILL" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 17:41 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:41 Sent To  
Notes
2007-04-03 17:52:40TO COMM BOARD # 29
2007-04-02 17:40:40WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 15:28 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 15:28 Sent To  
Notes
2007-01-17 15:28:47TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-15 Cont ID  
Sent By adarroug Date 2006-04-15 Time 13:00 Rev Time 0.00
Received By adarroug Date 2006-04-15 Time 13:00 Sent To  
Notes
2006-05-10 00:00:00TO "COMM" BD#45
2006-04-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 09:31 Sent To  
Notes
2006-03-06 00:00:00TO "COMM" BD#48
2006-02-13 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 17:18 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 17:18 Sent To  
Notes
2005-11-09 00:00:00TO "COMM" BD#32
2005-10-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-13 Cont ID  
Sent By shill Date 2005-08-13 Time 22:53 Rev Time 0.00
Received By shill Date 2005-07-12 Time 08:12 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#15
2005-07-14 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-05-02 Cont ID  
Sent By rregueir Date 2007-05-02 Time 15:01 Rev Time 0.00
Received By rregueir Date 2007-05-02 Time 09:45 Sent To  
Notes
2007-05-02 15:01:06---------------DENIED-----------------
  
 1. REVISION TO AN APPROVED PLAN SHALL BE DONE/APPROVED
 BY THE DESIGNER OF RECORD PER FAC 61G15-30.
  
 2. IF THIS PLAN IS TO BE A REVISION UNDER MASTER PERMIT
 #05070366, IT NEEDS TO BE UNDER THE 2001 FBC WHICH WAS
 IN EFFECT AT THE TIME OF PERMIT ISSUANCE.
  
 3. PREVIOUS PLAN WAS PASSED WITH A PROVISO. THE PROVISO
 RELATES TO FBC,M 306.5 (2001) WHICH REQUIRES PERMANENT
 ACCESS TO EQUIPMENT ON ROOFS AND ELEVATED STRUCTURES.
 IT NEEDS TO BE ADDRRESSED DURING THE REVISION PROCESS.
  
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-03 Cont ID  
Sent By hmoser Date 2005-12-03 Time 09:16 Rev Time 0.00
Received By hmoser Date 2005-12-03 Time 09:15 Sent To  
Notes
2005-12-03 00:00:00PASS PRIVISO
 PLEASE REFER TO SECTION 306.5 EQUIPMENT
 AND APPLIANCES ON ROORS.2001 FBC(M)
 PLAN REVIEW BY HAROLD MOSER.561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By pkrauss Date 2005-07-27 Time 20:13 Rev Time 1.00
Received By pkrauss Date 2005-07-27 Time 19:42 Sent To  
Notes
2005-07-27 00:00:00DENIED:
 1. PLAN SHEET A-3-ROOF EQUIPMENT DETAIL
 CLEARENCE ABOVE FINISHED ROOF SHALL
 COMPLY WITH ZOOL FBC 1511.7.
  
 2. PROUIDE DETAIL FOR HANGING OF THE
 AHU.
  
 3. CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE,
 2001 FBC 1503.4.4.
  
 4. PLAN SHEET MP-2 HVAC SPECIFICATIONS
 #19 - EMERGENCY DRAIN PAN SHALL HAVE
 OVERFLOW PROTECTION IN ACCORDANCE WITH
 2001 FBC(M)307.2.3.
  
 5.PLEASE INDICATE VENTILATION FOR THE
 WAREHOUSE AREAS PER 2001 FBC(M) TABLE
 403.3.
  
 6. INDICATE ACCESS TO EQUIPMENT LOCATED
 ON THE ROOF.PERMANENT MEANS OF ACCESS
 IS REQUIRED FOR HEIGHTS GREATER THAN 16
 FEET. 2001 FBC(M)306.5
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-05-16 Cont ID  
Sent By kstevens Date 2007-05-16 Time 08:03 Rev Time 0.00
Received By kstevens Date 2007-05-16 Time 08:03 Sent To  
Notes
2007-05-16 09:14:22DENIED
 REFERENCE: FLORIDA STATUTES
 FLORIDA ADMINISTRATIVE CODE
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
  
 1. THE REVISION SUBMITTED SUPERCEDES THE SHEETS
 SUBMITTED AND APPROVED FOR THE ORIGINAL PERMIT. BY
 SUPERCEDING THESE SHEETS, ALL INFORMATION ORIGINALLY
 SUBMITTED WILL BE DELETED. THIS IS NOT ACCEPTABLE.
  
 2. IF THERE IS REVISIONS FOR THE PLANS, THEY SHALL BE
 DESIGNED BY THE ARCHITECT AND ENGINEER OF RECORD. IF
 THERE WILL BE A NEW ARCHITECT AND ENGINEER OF RECORD,
 THEN A NEW PERMIT WILL BE REQUIRED AND A SHOP DRAWING
 APPROVED BY THE ORIGINAL ARCHITECT AND ENGINEER SHALL
 BE SUBMITTED.
  
 3. A SEPARAGE PERMIT WITH THE NEW DESIGN PROFESSIONALS
 WILL BE ALLOWED AFTER THE CERTIFICATE OF OCCUPANCY
 WITHOUT APPROVAL OF THE ORIGINAL DESIGN TEAM.
  
 4. SHT A-1 THE BUILDING DATA INDICATES THE OCCUPANCY AS
 STORAGE. THE FLOOR PLAN INDICATES A MIXED OCCUPANCY
 WITH BUSINESS AND STORAGE OCCUPANCY. PLEASE INDICATE
 CORRECT OCCUPANCE.
  
 5. PER TABLE 403.1 A SERVICE SINK IS REQUIRED IN THE
 STORAGE OCCUPANCY.
  
 6. SHT A-1 THE BREAK ROOM SINK REQUIRES A FORWARD
 APPROACH MAXIMUM 19" UNDERNEATH THE SINK, AND NOT
 PARALLEL APPROACH AS SHOWN. SECTION 11-4.16.5.
  
 7. SHT A-1 THE ROOM FINISH SCHEDULE INDICATES PAINT ON
 THE WALLS OF THE TOILET ROOMS 106 & 107. PER SECTION
 1210.2 WALLS WITHIN 2 FEET OF THE WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. PAINTED
 WALLS DOES NOT COMPLY WITH THE "HARD" REQUIREMENT.
 PLEASE INDICATE COMPLIANCE.
  
 8. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOW COMPLIANCE
 WITH THE FOLLOWING:
 ___FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ___FOR LAVS
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.16.5 FAUCETS
 THE W/C'S SHALL BE 18" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE & THE LAV SHALL BE A MINIMUM OF 15" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGURE
 29 AND THE LAV SHALL BE CENTERED ON THE 30" DIMENSION
 OF THE CLEAR FLOOR SPACE.
  
 9. SHT A-2 DETAIL #1. SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS.
  
 10. SHT P-1 SANITARY RISER DIAGRAM. ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ADDITIONAL
 FIXTURES, (BREAK ROOM SINK), SHALL DISCHARGE DOWNSTREAM
 OF THE WET VENT. SECTION 909.1.
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE BUILDING/SPACE. SECTION 608.13.2..
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
 .

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-14 Cont ID  
Sent By kstevens Date 2005-12-14 Time 07:42 Rev Time 1.00
Received By kstevens Date 2005-12-13 Time 16:56 Sent To  
Notes
2005-12-14 00:00:00RPZV BACKFLOR REQD. ON WATER SERVICE

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By kstevens Date 2005-08-08 Time 17:50 Rev Time 2.95
Received By kstevens Date 2005-08-08 Time 17:50 Sent To  
Notes
2005-08-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1. SHT A-2 PER TABLE 403.2 SEPARATE
 FACILITIES ARE REQUIRED FOR MEN AND
 WOMEN.
 2. SHT A-2 TABLE 403.1 STORAGE
 FACILITIES REQUIRES A SERVICE SINK.
 3. SHT A-2 INDICATES 13,392SF BUILDING
 AREA, BUT SHT A-3 GUTTER & DOWNSPOUT
 CALCULATIONS SHOW FLAT ROOF AREA AS
 6,128SF. PLEASE CLARIFY. SECTION
 104.2.1.
 4. SHT A-3 GUTTER & DOWNSPOUT
 CALCULATION FOR PARAPETS DO NOT INCLUDE
 THE PARAPET WALL FOR THE FRONT OF THE
 BUILDING. ALSO ALL VERTICAL WALLS FOR
 THE THREE SIDES OF THE CUPOLA, AND 5
 SIDES FOR EACH WALL AT THE A/C EQUIPMENT
 SHALL BE INCLUDED IN THE CALCULATIONS.
 SECTION 1106.4. ALSO NOT INCLUDED IN THE
 CALCULATIONS SHALL BE THE AREA OF THE
 ROOF FROM THE CUPOLA THAT DRAINS ONTO
 THE FLAT ROOF AREA FROM ABOVE. PLEASE
 RECALCULATE SQUARE FOOTAGE FOR ROOF AREA
 TO BE DRAINED.
 5. SUBMIT A DETAIL FOR THE GUTTER
 SHOWING SIZE OF GUTTER COMPLYING WITH
 TABLE 1106.6, SLOPE OF GUTTER WITH HIGH
 POINTS OF GUTTER CALLED OUT ON PLAN,
 WITH THE SIZE AND LOCATION OF EACH
 DOWNSPOUT. INDICATE THE TOTAL AREA
 DRAINING INTO EACH DOWNSPOUT. SECTION
 104.2.1.
 6. SHT A-6 DETAIL #9 CONTROLS FOR
 DRINKING FOUNTAIN DO NOT SEEM TO COMPLY
 WITH SECTION 11-4.27.4. (TWISTING OF THE
 WRIST). PLEASE CLARIFY. - PLEASE SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 7. SHT A-6 DETAIL #2 SHOW THE FOLLOWING:
  
 FOR W/C, 11-4.16.5 FLUSH CONTROLS
 FOR LAV, 11-4.19.5 FAUCETS
 8. SHT ME-2 SANT. RISER DIAGRAM, A 2-WAY
 CLEANOUT IS REQUIRED NEAR THE JUNCTION
 OF THE BUILDING DRAIN AND THE BUILDING
 SEWER. SECTION 708.3.5.
 9. SHT MP-2 SANT. RISER DIAGRAM, ALL
 HORIZONTAL BUILDING DRAINS REQUIRE A
 CLEANOUT. SECTION 708.3.1.
 10. SHT MP-2 WATER RISER DIAGRAM, AN RPZ
 BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUILDING.
 11. A SEPARATE IRRIGATION PERMIT AND
 PLANS ARE REQUIRED. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2007-10-17 Cont ID  
Sent By bpowell Date 2007-10-17 Time 09:27 Rev Time 0.00
Received By bpowell Date 2007-10-17 Time 09:27 Sent To I
Notes
2007-10-17 14:15:27REVISION

Review Stop Z ZONING
Rev No 4 Status F Date 2007-10-03 Cont ID  
Sent By bpowell Date 2007-10-03 Time 15:04 Rev Time 0.00
Received By bpowell Date 2007-10-03 Time 15:04 Sent To B
Notes
2007-10-03 15:05:411. THE PLANS SHALL REFLECT THE ACTUAL CONDITIONS OF THE
 SITE. THE PIGMY DATE PALMS THAT HAVE BEEN RELOCATED
 SHALL SHOW THE NEW LOCATION OF EACH, THE SIDEWALK GOING
 THROUGH THE LANDSCAPE ISLAND SHALL BE SHOWN, AND ANY
 OTHER CONDITION SHOWN ON THE PLAN MUST REFLECT WHAT IS
 ACTUALLY THERE.
  
 2. ALL PLANS WITHIN THE PACKET SHALL BE CONSISTENT.
  
 FOR QUESTIONS OR COMMENTS CONTACT;BOBBY POWELL JR.,
 PLANNER, (561) 822-1435, [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2006-06-30 Cont ID  
Sent By eschneid Date 2006-06-30 Time 17:07 Rev Time 0.00
Received By eschneid Date 2006-06-30 Time 17:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-03-22 Cont ID  
Sent By ebowers Date 2006-03-22 Time 09:55 Rev Time 0.00
Received By ebowers Date 2006-03-22 Time 09:55 Sent To I
Notes
2006-03-07 00:00:00NEW SHEET CONTAINING NEW SITE PLAN.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-03 Cont ID  
Sent By ebowers Date 2005-08-03 Time 12:13 Rev Time 0.00
Received By ebowers Date 2005-08-03 Time 12:12 Sent To I
Notes
***NONE***