| Plan Review Stops For Permit 05070366 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-04 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-04 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2007-10-04 16:06:35 | ****CORRECTIONS - RESTAMP**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER ARE TO BE | | | ORIGINALS, FAC61G15-23.THE ARCHITECTURAL SHEETS HAVE | | | BEEN STAMPED.HAVE THE ENGINEERING SHEETS SIGNED, | | | SEALED AND DATED AND SUBMIT FOR RESTAMP. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2007-07-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-10 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-10 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-06-12 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-06-12 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2007-06-12 12:11:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)ONE NOA HAS BEEN STAMPED (03-1021.02, US DOOR). | | | THE OTHER TWO WERE NOT A PART OF THE ISSUED PERMIT. | | | SUBMIT THEM AS A REVISION FOR REVIEW. | | | | | | 2.)PROVIDE THE ELEVATION CERTIFICATE AS THIS PROPERTY | | | IS LOCATED IN A HIGH HAZARD FLOOD ZONE.CONTRACTOR HAD | | | BEEN INFORMED THAT A CO HOLD WAS PLACED ON THIS JOB | | | PENDING RECEIPT OF THE ELEVATION CERTIFICATE.PLEASE | | | SUBMIT AT THIS TIME. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2007-04-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-04-29 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-04-29 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2007-04-29 15:16:46 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)THIS WAS ISSUED WITH A PROVISO THAT AN ELEVATION | | | CERTIFICATE BE PROVIDED AT TIME OF CONCRETE POUR.THIS | | | WAS NOT PROVIDED.A CO HOLD HAS BEEN PLACED AND WILL | | | BE REMOVED WHEN THIS ITEM IS ADDRESSED. | | | | | | 2.)THE ENERGY CALCS DID NOT PASS ELECTRIC REVIEW. | | | ENERGY CALCS UNDER THIS PERMIT TO BE FBC2001, NOT | | | FBC2004. | | | | | | 3.)THE ORIGINAL DESIGNER WAS JEFFREY GASPAR, THIS | | | PLAN IS BY MB DESIGN.ONLY ONE DESIGNER OF RECORD CAN | | | BE ON THIS PROJECT.ADDRESS. | | | | | | 4.)DECLARE OCCUPANT LOAD, OCCUPANCY CLASSIFICATION. S | | | WAS DECLARED, APPEARS THAT IT IS MIXED, B AND S. WHAT | | | WILL BE STORED IN THE AIR CONDITIONED WAREHOUSE AREA? | | | PROVIDE MORE INFORMATION IN REGARDS TO THE USE OF THIS | | | SPACE. | | | | | | 5.)WALL LEGEND A DOES NOT MATCH WALL A ON THE FLOOR | | | PLAN. | | | | | | 6.)SHOW WALL FINISHES FOR THE BATHROOMS, FBC1204.2. | | | | | | 7.)THERE ARE REFERENCES TO FBC2004.THIS PERMIT WAS | | | ISSUED UNDER FBC2001. | | | | | | 8.)SEE FBC TABLE 704.1, OCCUPANCY SEPARATION | | | REQUIREMENTS.SHOW OCCUPANCY OF EACH AREA, AND | | | SEPARATION, FBC704.1.IF EXEMPT, SHOW HOW THIS WILL BE | | | EXEMPT FBC704.1.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-23 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-23 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2007-01-23 16:44:09 | REVISION S1 AND S2 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-04-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-04-18 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-04-18 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | PA FOR ROOF RETURNED TO CONTRACTOR (DID | | | NOT SELECT APPROVED ASSEMBLY), NEEDS | | | PRODUCT APPROVALS WITH ROOF PERMIT | | | APPLICATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-03-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-23 |
Time |
14:16 |
Rev Time |
4.00 |
| Received By |
shill |
Date |
2006-03-23 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2006-03-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | COMMENTS FROM PREVIOUS TWO REVIEWS, | | | NUMBERING REMAINING THE SAME FOR | | | CONSISTENCY | | | | | | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | PLEASE KEEP THE NOC PROVIDED IN THE | | | PACKAGE. | | | | | | 5.)THIS PARCEL IS IN A FLOOD ZONE.A | | | FORM BOARD ELEVATION CERTIFICATE WILL BE | | | REQUIRED.THE FINISHED FLOOR IS TO BE | | | SIX INCHES ABOVE BASE FLOOD ELEVATION, | | | CITY OF WEST PALM BEACH MUNICIPAL CODE | | | 94-546(2). NOTE MINIMUM ELEVATION ON THE | | | PLAN. | | | | | | THIS HAS BEEN ADDRESSED.THE PERMIT | | | WILL BE ISSUED WITH A PROVISO THAT AN | | | ELEVATION CERTIFICATE BE PROVIDED AT | | | FORM BOARD INSPECTION. | | | | | | 6-7.)ADDRESSED. | | | | | | | | | 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1. | | | SHOW ALL DISTANCES FROM THE PROPERTY | | | LINE SO THAT TABLE 500 AND TABLE 600 | | | COMPLIANCE CAN BE DETERMINED.SHOW | | | ACCESSIBLE PARKING, ACCESSIBLE ROUTE | | | FROM THE PUBLIC WAY FBC CHAPTER 11. | | | | | | THIRD REVIEW - THE ACCESSIBLE PARKING IS | | | TO COMPLY WITH FBC11-4.1.2(5)(A), | | | ACCESSIBLE PARKING SHALL BE PROVIDED IN | | | EACH SUCH PARKING AREA.NO ACCESSIBLE | | | PARKING SHOWN IN THE REAR PARKING LOT. | | | ACCESSIBLE ROUTE AT THE REAR OF THE | | | BUILDING IS NOT CLEAR. | | | | | | THE PARKING IS TO COMPLY WITH THE CITY | | | OF WEST PALM BEACH STANDARDS, SEE | | | ATTACHED DETAIL. | | | | | | NOTE THAT THE CIVILS ARE TO BE | | | CONSISTENT WITH THE ARCHITECTURALS. | | | | | | 9-13.)ADDRESSED. | | | | | | 16.)THE FOLLOWING NOAS WERE REVIEWED | | | AND APPEAR CODE COMPLIANT EXCEPT AS | | | NOTED BUT REQUIRE FLORIDA STATE OR LOCAL | | | PRODUCT APPROVALS, FAC9B72. | | | WWW.FLORIDABUILDING.ORG. | | | | | | ARCH ALUMINUM IMPACT WALL 3000 | | | ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR | | | MODEL 651 ROLLING DOOR ? EXPIRED NOA | | | | | | ARCH ALUMINUM IMPACT WALL 3000 OK. | | | THE ARCH ALUMINUM MAGNUM STILE ENTRANCE | | | DOOR NOT IN THE PACKAGE.ANY ITEMS NOT | | | PROPERLY SUBMITTED AND REVIEWED PRIOR TO | | | PERMIT ISSUANCE WILL REQUIRE SEPARATE | | | PERMITS. | | | ROLLING DOOR OK. | | | | | | 17.)PROVIDE PRODUCT APPROVALS FOR THE | | | REAR METAL DOOR, FLAT ROOF, STANDING | | | SEAM, ROLLING DOOR.ANY PRODUCT | | | APPROVALS NOT REVIEWED PRIOR TO PERMIT | | | ISSUANCE WILL REQUIRE SEPARATE PERMITS. | | | | | | PRODUCT APPROVALS FOR THE REAR METAL | | | DOOR, STANDING SEAM ROOF, ROLLUP DOOR | | | OK. | | | | | | CHOOSE THE APPROVED ASSEMBLY YOU ARE | | | USING FROM THE CHOICES PROVIDED IN THE | | | NOA.IF THIS IS NOT ADDRESSED PRIOR TO | | | PERMIT ISSUANCE, | | | | | | 18.)SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW FEE WILL BE CHARGED IF | | | COMMENTS ARE NOT ADDRESSED IN THE NEXT | | | REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-11-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-10 |
Time |
19:17 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-11-10 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2005-11-10 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | COMMENTS FROM PREVIOUS REVIEW, NUMBERING | | | REMAINING THE SAME FOR CONSISTENCY | | | | | | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | FS713.13 REQUIRES THE CONTRACTOR?S NAME | | | AND ADDRESS SO THAT NOTICES CAN BE | | | SERVED AS REQUIRED BY THE FLORIDA LEIN | | | LAW.CONTRACTOR ADDRESS IS NOT ON THE | | | NOC. | | | | | | 5.)THIS PARCEL IS IN A FLOOD ZONE.A | | | FORM BOARD ELEVATION CERTIFICATE WILL BE | | | REQUIRED.THE FINISHED FLOOR IS TO BE | | | SIX INCHES ABOVE BASE FLOOD ELEVATION, | | | CITY OF WEST PALM BEACH MUNICIPAL CODE | | | 94-546(2). NOTE MINIMUM ELEVATION ON THE | | | PLAN. | | | | | | NOT ADDRESSED. | | | | | | 6.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALCS. | | | | | | 7.)A WAREHOUSE SHOULD BE S OCCUPANCY, | | | THE OFFICE AREA IS B.PLEASE SEE FBC312 | | | AND FBC305.BUSINESS OCCUPANCY WAS | | | DECLARED ON SHEET A2. | | | | | | NOT ADDRESSED; STILL SHOWS A WAREHOUSE | | | AND DECLARES B OCCUPANCY.BASED ON THE | | | FLOOR PLAN WHICH SHOWS A WAREHOUSE, THE | | | OFFICES ARE ACCESSORY TO THE PRIMARY | | | OCCUPANCY OF STORAGE, SEE FBC704.1.2.1. | | | | | | | | | 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1. | | | SHOW ALL DISTANCES FROM THE PROPERTY | | | LINE SO THAT TABLE 500 AND TABLE 600 | | | COMPLIANCE CAN BE DETERMINED.SHOW | | | ACCESSIBLE PARKING, ACCESSIBLE ROUTE | | | FROM THE PUBLIC WAY FBC CHAPTER 11. | | | | | | 9.)THE AREA INCREASE CALCULATIONS ON | | | A2 STATES THAT THE ALLOWABLE AREA FOR | | | BUSINESS TYPE V IS 9000 SF.PLEASE NOTE | | | THAT IT IS 14000 SF PER FBC TABLE 500 | | | AND 16000 FOR STORAGE. | | | | | | YOU HAVE CHANGED THE BUILDING TYPE TO | | | VI.AREA ALLOWED FOR TYPE VI, STORAGE | | | OCCUPANCY, UNPROTECTED UNSPRINKLED IS | | | 6000.THE BUILDING IS NOT COMPLIANT FBC | | | TABLE 500. | | | | | | 12.)CLARIFY THE ROOF AREA ON A3. | | | | | | 13.)DOOR HARDWARE TO COMPLY WITH | | | FBC11-4.13.9. | | | | | | THIS WAS ADDRESSED BY PROVIDING THE CODE | | | SECTION.PLANS ARE TO BE PROVIDE DESIGN | | | CRITERIA, FBC*104.2.1. | | | | | | 16.)THE FOLLOWING NOAS WERE REVIEWED | | | AND APPEAR CODE COMPLIANT EXCEPT AS | | | NOTED BUT REQUIRE FLORIDA STATE OR LOCAL | | | PRODUCT APPROVALS, FAC9B72. | | | WWW.FLORIDABUILDING.ORG. | | | | | | ARCH ALUMINUM IMPACT WALL 3000 | | | ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR | | | MODEL 651 ROLLING DOOR ? EXPIRED NOA | | | | | | FLORIDA PRODUCT APPROVALS REQUIRED IN | | | ADDITION TO THE NOAS PROVIDED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | 17.)PROVIDE PRODUCT APPROVALS FOR THE | | | REAR METAL DOOR, FLAT ROOF, STANDING | | | SEAM, ROLLING DOOR.ANY PRODUCT | | | APPROVALS NOT REVIEWED PRIOR TO PERMIT | | | ISSUANCE WILL REQUIRE SEPARATE PERMITS. | | | | | | FLORIDA PRODUCT APPROVALS REQUIRED | | | FAC9B72, WWW.FLORIDABUILDNIG.ORG | | | | | | 18.)SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW FEE WILL BE CHARGED IF | | | COMMENTS ARE NOT ADDRESSED IN THE NEXT | | | REVIEW. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-13 |
Time |
22:51 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-08-13 |
Time |
20:18 |
Sent To |
|
|
| Notes |
| 2005-08-13 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY (CHANGE OF USE).THE PLANS | | | MUST BE STAMPED AND THE RECEIPT ATTACHED | | | TO THE APPLICATION. 233-5025 | | | | | | 3.)PLEASE CONTACT JOHN HIGGINS IN | | | REGARDS TO ADDRESSING FOR THIS PARCEL. | | | OUR RECORDS CONFLICT WITH THE ADDRESS ON | | | YOUR APPLICATION.HE CAN BE REACHED AT | | | 805-1239.***NOTE 8/16 - J.HIGGINS | | | CHANGED OUR RECORDS TO REFLECT 5760 | | | CORPORATE WAY AS CORRECT ADDRESS FOR | | | THIS PARCEL*** | | | | | | 4.)GENERAL NOTES, ITEM 12 ON THE | | | SURVEY PREPARED BY TARGET SURVEYING, | | | INC. STATES THAT THE SURVEY WILL NOT BE | | | USED FOR CONSTRUCTION OR PERMITTING. | | | SUBMIT A SURVEY FOR PERMITTING. | | | | | | 5.)THE SURVEYOR IS REQUIRED TO DATE | | | THE SEAL, FS472.025, SEE ATTACHED.THE | | | SEAL IS TO BE LEGIBLE. | | | | | | 5.)THIS PARCEL IS IN A FLOOD ZONE.A | | | FORM BOARD ELEVATION CERTIFICATE WILL BE | | | REQUIRED.THE FINISHED FLOOR IS TO BE | | | SIX INCHES ABOVE BASE FLOOD ELEVATION, | | | CITY OF WEST PALM BEACH MUNICIPAL CODE | | | 94-546(2). NOTE MINIMUM ELEVATION ON THE | | | PLAN. | | | | | | 6.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALCS. | | | | | | 7.)A WAREHOUSE SHOULD BE S OCCUPANCY, | | | THE OFFICE AREA IS B.PLEASE SEE FBC312 | | | AND FBC305.BUSINESS OCCUPANCY WAS | | | DECLARED ON SHEET A2. | | | | | | 8.)PROVIDE A SITE PLAN, FBC*104.3.1.1. | | | SHOW ALL DISTANCES FROM THE PROPERTY | | | LINE SO THAT TABLE 500 AND TABLE 600 | | | COMPLIANCE CAN BE DETERMINED.SHOW | | | ACCESSIBLE PARKING, ACCESSIBLE ROUTE | | | FROM THE PUBLIC WAY FBC CHAPTER 11. | | | | | | 9.)THE AREA INCREASE CALCULATIONS ON | | | A2 STATES THAT THE ALLOWABLE AREA FOR | | | BUSINESS TYPE V IS 9000 SF.PLEASE NOTE | | | THAT IT IS 14000 SF PER FBC TABLE 500 | | | AND 16000 FOR STORAGE. | | | | | | 10.)TYPE V CONSTRUCTION IS TO HAVE | | | NONCOMBUSTIBLE WALLS.THE PARAPET AND | | | THE WALL BELOW THE HIP ROOF SHOWS WOOD | | | SHEATHING.SEVERAL DETAILS ARE | | | AFFECTED; 2-A3, D-A4.CHECK ALL | | | DETAILS. | | | | | | 11.)DOOR 3 APPEARS TO BLOCK OVER HALF | | | THE WIDTH OF THE HALLWAY, FBC1012.1.4. | | | | | | 12.)CLARIFY THE ROOF AREA ON A3. | | | | | | 13.)DOOR HARDWARE TO COMPLY WITH | | | FBC11-4.13.9. | | | | | | 14.)PROVIDE A SOILS INVESTIGATION | | | REPORT. | | | | | | 15.)PROVIDE LEGIBLE NOAS.THEY ARE | | | AVAILABLE EITHER AT WWW.MIAMIDADE.GOV | | | (FIND A DEPT, BUILDING CODE COMPLIANCE, | | | PRODUCT CONTROL) OR AT | | | WWW.FLORIDABUILDING.ORG (PRODUCT | | | APPROVAL). | | | | | | 16.)THE FOLLOWING NOAS WERE REVIEWED | | | AND APPEAR CODE COMPLIANT EXCEPT AS | | | NOTED BUT REQUIRE FLORIDA STATE OR LOCAL | | | PRODUCT APPROVALS, FAC9B72. | | | WWW.FLORIDABUILDING.ORG. | | | | | | ARCH ALUMINUM IMPACT WALL 3000 | | | ARCH ALUMINUM MAGNUM STILE ENTRANCE DOOR | | | MODEL 651 ROLLING DOOR ? EXPIRED NOA | | | | | | 17.)PROVIDE PRODUCT APPROVALS FOR THE | | | REAR METAL DOOR, FLAT ROOF, STANDING | | | SEAM, ROLLING DOOR.ANY PRODUCT | | | APPROVALS NOT REVIEWED PRIOR TO PERMIT | | | ISSUANCE WILL REQUIRE SEPARATE PERMITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-04-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-08 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-08 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2007-04-08 13:54:36 | | | | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE THIS PROJECT WAS PERMITTED UNDER | | | THE 2001 FBC . | | | PLEASE SEE THIS WAS UNDER THE PREVIOUS VERSION. PLEASE | | | SEE THAT THE ENERGY CALCULATIONS DO NOT COORDINATE WITH | | | THE PLANS FOR THE FIXTURES, TYPES, WATTAGES, ETC. | | | PLEASE SEE THE FIXTURE LEGEND. PLEASE SEE THE LIGHTING | | | DENSITIES PROVIDED ON PLANS DO NOT CORRELATE WITH THE | | | ACTUAL FIXTURES ON PLANS OR WHAT IS IN ENERGY | | | CALCULATIONS. | | | PLEASE REVISE ALL OF THE ENERGY CALCULATIONS AND | | | DENSITIES ALONG WITH REVISED PLANS AS NEEDED TO | | | COORDINATE ALL. | | | FBC 13-415.1.AB.1.1, 13-415.2 | | | FBC 106.1.2 ADMIN SECTION. | | | | | | 2) NOTE: PLEASE SEE REVISED RISER WHICH SHOWS A 200AMP | | | DISCONNECT FEEDING A 100AMP RATED PANEL. PLEASE ALSO | | | SEE PLANS WHICH INDICATE THE SAME. | | | PLEASE SEE THE LOAD SHOWN AT 161AMPS EXCEEDS THAT OF | | | THE RATING OF PANEL ALSO. | | | PLEASE SEE PANEL SCHEDULE WHICH INDICATES A 200A RATED | | | BREAKER IN THIS 100AMP PANEL. | | | PLEASE SEE 240.4, 310.16 ETC | | | FBC 106.1.2 | | | | | | 3) NOTE: PLEASE SEE MISSING CIRCUITING ON PLANS FOR | | | EM/EXT LTS.PLEASE SEE 700.12E FOR CIRCUITING. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-03-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-07 |
Time |
19:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-07 |
Time |
19:28 |
Sent To |
|
|
| Notes |
| 2006-03-07 00:00:00 | ELECTRICAL PLANS STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-11-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-17 |
Time |
22:06 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-11-17 |
Time |
21:37 |
Sent To |
|
|
| Notes |
| 2005-11-17 00:00:00 | **** UNSAT **** | | | | | | PLEASE SEE PLANS ARE COMING BACK FOR | | | OTHER COMMENTS , PLEASE ADDRES BELOW AT | | | THIS TIME. | | | | | | 1)NOTE: PLEASE SEE NOTE # 4 FROM | | | PREVIOUS REVIEW WHICH REQUESTED TO | | | CLARIFY ONE UNIT SHOWN ON PLANS WHICH | | | SEEMS TO GETTING BUILT OUT HOWEVER RISER | | | DIAGRAM AND RISER NOTES DO NOT TEND TO | | | CORRELATE WITH THIS. | | | PLEASE SEE CIRCUTING FOR PANEL T-1 | | | CORRLELATES WITH THIS BLD OUT. | | | PLEASE PROVIDE INFORMATION FOR | | | DISCONNECT METER ETC. | | | 215.5 | | | | | | 2)NOTE: THIS IS ONLY A NOTE: RECEPT | | | CIRCUITED TO #9, SEEMS TO BE INDICATED | | | TO BE ABOVE CEILING. | | | RECEPTS ARE NOT PERMITTED ABOVE. | | | | | | 3)NOTE: PLEASE SEE A RE-RECORDED NOC | | | WILL BE REQUIRED AS THE ONE PRESENTLY | | | SUBMITTED HAS EXPIRED. | | | PLEASE SEE FS 713.13(2). | | | PLEASE KNOW, IF WORK HAS NOT COMMENCED | | | WITH IN 90 DAYS OF RECORDING, THE NOC | | | SHALL BECOME VOID. | | | THIS NOTE ID NOT FOR THE ELECTRICAL | | | ENGINEER. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-27 |
Time |
21:22 |
Rev Time |
1.75 |
| Received By |
dpalmer |
Date |
2005-07-26 |
Time |
21:03 |
Sent To |
|
|
| Notes |
| 2005-07-27 00:00:00 | *********** UNSAT ****************** | | | | | | PLEASE SEE ADDRESS IN OUR SYSTEM FOR PCN | | | USED SHOWS "5660" CORP WAY. PLEASE SEE | | | PERMIT APPLICATION AND PLANS SHOWS | | | "5760". PLEASE SEE ADDRESSING WILL NEED | | | TO BE CORRELATED. | | | | | | 1)NOTE: PLEASE LABEL EACH | | | WAREHOUSE/OFFICE SPACE. IE: UNIT | | | A,B,C,,,,1,2,3,, ETC | | | PLEASE CORRELATE THIS AND LABEL RISER | | | ACCORD. | | | 215.5 | | | | | | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH THE SUBMITTED | | | TYPPICAL PANEL SCHEDULE. | | | PLEASE ALSO SHOW CIRCUITING FOR HOUSE | | | LOADS. | | | 215.5 | | | | | | 3)NOTE: PLEASE CLARIFY, PLANS APPEAR TO | | | SHOW EM/EXT LTS CIRCUITED TO HOUSE | | | PANEL? YET, NOTE ON ON LIGHTING LEGEND | | | MENTIONS AHEAD OF LOCAL LIGHTING. | | | PLEASE SEE 700.12E, WHICH REQUIRES | | | FIXTURES TO BE CONNECTED TOBRANCH | | | CIRCUIT FOR LOCAL AREA LIGHTING. | | | PLEASE ALSO SEE THIS WOULD INDICATEA | | | CROSS OVER IN ELECTRICAL CIRCUITS INTO | | | EACH TENANT SPACE? | | | | | | 4)NOTE: PLEASE CLARIFY PLANS WHICH | | | APPEARS TO SHOW ONE UNIT, OFFICE | | | WAREHOUSE BEING BUILT OUT. HOWEVER, | | | RISER DIAGRAM DOES NOT CORREALTE WITH | | | THIS? | | | RISER SHOWS ALL DISCONNECTS AND PANELS | | | AS FUTURE? | | | | | | 5)NOTE: PLEASE SEE 600.5 WHICH REQUIRES | | | THE TENANT SIGN CIRCUIT TO BE LOCATED AT | | | ENTRANCE INTO UNIT. | | | PLEASE SEE J-BOX SEEMS TO BE ABOVE | | | WINDOW AS FOR A WINDOW SIGN? PLEASE SEE | | | NEXT COMMENT. | | | | | | 6)NOTE: PLEASE SEE IF ANY OF THESE UNITS | | | ARE INTENDED FOR RETAIL SPACE, A WINDOW | | | RECEPT WILL BE REQUIRED ABOVE WINDOW. | | | PLEASE SEE THIS IS ONLY A COMMENT AT | | | THIS TIME OF NOW UNITS ARE GOING TO | | | BUILT OUT. IF ANY UNIT IS BUILT OUT AT | | | THIS TIME, A RECEPT WILL BE REQUIRED. | | | 210.62,220.12 | | | | | | 7)NOTE: PLEASE INCLUDE CONDUCTORS FROM | | | MAIN TO GUTTER . 215.5,240.4,310.16 | | | PLEASE ALSO SEE NEXT COMMENT FOR | | | EQUIPMENT GROUNDING CONDUCTOR. | | | | | | 8)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS AFTER THE FIRST | | | MEANS OF DISCONNECT.250.24,250.6, | | | 250.110 ETC. | | | PLEASE SEE NOTE #8 ON RISER NOTES DOES | | | NOT SEEM TO INCLUDE THIS.? | | | | | | 9)NOTE: PLEASE ALSO SEE NOTE #8 ON RISER | | | APPEARS TO SHOW CONDUITS/FEEDERS ETC ON | | | LOAD SIDE OF TENANT DISCONNECTS ALSO | | | BEING CONNECTED TO FPL TRANSFORMER? | | | PLEASE SEE RISER DIAGRAM. | | | | | | 10)NOTE: PLEASE SEE NOTES #4&5 ON RISER | | | NOTES PERTAINING TO GROUNDING ELECTRODE | | | SYSTEM. PLEASE SEE 250.50, WHICH ALSO | | | REQUIRES FOOTER STEEL. PLEASE INCLUDE | | | THIS IN A DETAIL TO BE PROVIDED FOR | | | GROUNDING ELECTRODE SYSTEM. | | | | | | 11)NOTE: PLEASE CLARIFY NOTE #15 ON | | | RISER AND NOTES WHICH MENTIONS TO | | | INSTALL, 2-2" CONDUITS FROM "GUTTER" TO | | | EACH TEANT SPACE? PLEASE SEE RISER SHOWS | | | THESE CONDUITS BEING INSTALLED TO EACH | | | DISCONNECT? PLEASE ALSO CLARIFY (TWO) | | | CONDUITS FOR EACH FEEDER? | | | 215.5 | | | | | | 12)NOTE: PLEASE INCLUDE SIZING FOR | | | GUTTER AT THIS TIME. PLEASE SEE 366. | | | | | | 13)NOTE: PLEASE CLARIFY PANEL "HP" | | | SHOWING A BACK-FED 60A BRKR FOR MAIN, | | | YET RISER AND PLANS BOTH INDICATE A | | | FUSIBLE MAIN DISCONNECT RIGHT NEXT TO | | | PANEL?? | | | PLEASE SEE THE ADDITIONAL "MAIN" WITH A | | | RETENTION CLIP MAY BE INSTALLED, HOWEVER | | | THIS IS NOT REQUIRED. THIS IS ONLY A | | | NOTE. IF SHOWN ON PLANS THEN IT WILL BE | | | REQUIRED TO BE INSTALLED. | | | 215.5 | | | | | | 14)NOTE: PLEASE CLARIFY FIXTURE "A" | | | SHOWN ON PLANS; LIGHT FIXTURE ON PLAN | | | AND ON "LIGHTING LEGEND" APPEARS TO SHOW | | | THIS FIXTURE AS A SURFACE MOUNBTED | | | SCONCE TYOE OF FIXTURE, HOWEVER PLEASE | | | SEE " LIGHTING FIXTURE SCHEDULE" WHICH | | | DOES NOT CORRELATE WITH THIS FOR FIX | | | "A".? | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE COPY OF OLD/VOIDED | | | SHEETS FOR REFERENCE WHICH SHOULD BE | | | SEPARATE AND MRKED VOID/OLD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-07-26 00:00:00 | IN ELECTRICAL FOR REVIEW. | | | PLAN REVIEW NOTES FOR ELECTRICAL WILL | | | FOLLOW ONCE REVIEW IS COMPLETE. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-07-21 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-07-21 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | PASSED | | | ALL PREVIOUS COMMENTS TAKEN CARE OF. | | | RASIK |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2005-11-10 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-11-10 |
Time |
14:27 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2005-11-10 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2005-11-10 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. PARKING STALLS MUST BE PAINTED WITH | | | DOUBLE 4" WIDE STRIPES, PER CITY' | | | REQUIREMENT. | | | 2. POLLUTION PREVENTION PLANS MUST BE | | | INSTALLED IN FIELD PRIOR TO ANY | | | CONSTRUCTION ACTIVITIES. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-07-20 |
Time |
14:07 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2005-07-20 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | FAILED: | | | | | | 1. PLEASE NOTE THAT CONNECTIONS TO THE | | | CITY' SERVICES AND THE LOCATION OF THE | | | PROPOSED F.HYD AND THE 12' U.E. MUST BE | | | APPROVED BY THE PUBLIC UTILITIES AND | | | ENGINEERING. | | | 2. DUMPSTER ENCLOSURE MUST BE SIZED PER | | | CITY OF WPB REQUIREMENT, IF GARBAGE IS | | | TO BE PICKED UP BY THE CITY. | | | 3. ALL OFF STREET REGULAR PARKING STALLS | | | MUST BE PAINTED WITH DOUBLE 4" WIDE | | | STRIPES, PER CITY REQUIREMENT. | | | 4. PLEASE PROVIDE CALCULATIONS FOR TOTAL | | | SITE AREA, BUILDING AREA, AND PERVIOUS & | | | IMPERVIOUS AREA. | | | 5. PLEASE NOTE THAT, IN ADDITION TO THE | | | ABOVE REVIEW COMMENTS, THE REVIEW | | | COMMENTS FROM THE PUBLIC UTILITIES AND | | | ENGINEERINGMUST BE ADDRESSSED/OR | | | IMPLEMENTED INTO THE CIVIL PLANS PRIOR | | | TO GETTING APPROVAL FROM BUILDING | | | DEPARTMENT. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-05-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-05-18 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-05-18 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2007-05-18 14:34:55 | ***DENIED*** | | | | | | 1) PLANS INDICATE STORAGE OCCUPANCY UNDER BUILDING | | | DATA. PLEASE CLARIFY OCCUPANCY CLASSIFICATION AS | | | STORAGE WOULD SEEM TO APPLY TO PART OF THIS PROJECT. | | | | | | 2) PLEASE SEE OTHER REVIEW COMMENTS REGARDING DESIGNER | | | OF RECORD REQUIREMENTS. | | | | | | 3) WHEN APPLYING CODE REFERENCE, THE APPLICABLE EDITION | | | SHALL BE USED. | | | | | | 4) PLEASE INDICATE WHAT WILL BE STORED IN THE | | | WAREHOUSE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-11-16 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-11-16 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-11 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-11 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2005-08-11 00:00:00 | ******DENIED****** | | | | | | 1) PLANS INDICATE THAT INTERIOR FINISH | | | ON WALLS AND CEILINGS TO BE CLASS A, B, | | | OR C. PLEASE INDICATE THE CLASSIFICATION | | | OF WALLS AND CEILINGS APPLICABLE TO THIS | | | OCCUPANCY. | | | | | | 2) IT IS UNDERSTOOD THAT MONUMENT SIGNS | | | ARE PLANNED TO BE INSTALLED UPON | | | APPROVAL. IF A DELAY SHOULD OCCUR PRIOR | | | TO OCCUPANCY, ADDRESSES ON THE BUILDING | | | WILL BE REQUIRED THAT ARE AT LEAST 6" IN | | | HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. | | | | | | 3) NOTE #4 REFERS TO A KEY LOCKING | | | DEVICE ON THE EGRESS SIDE OF EACH MAIN | | | EXIT DOOR. THIS ARRANGEMENT IS ONLY | | | ACCEPTABLE IF ALL THE CRITERIA IN | | | ACCORDANCE WITH NFPA 101, SECTION | | | 7.2.1.5.4 IS MET. | | | | | | 4) SOME EXIT SIGNS APPEAR TO BE MISSING | | | ON THE WAREHOUSE DOORS LEADING TO THE | | | OFFICE AREAS. | | | | | | 5) PLEASE SHOW ALL THE EMERGENCY | | | LIGHTING FACILITIES. THERE APPEARS TO BE | | | SOME MISSING IN WAREHOUSE AREAS. | | | | | | 6) 2A-10B,C RATED FIRE EXTINGUISHERS | | | SHALL BE MOUNTED AT DISTANCES TO SATISFY | | | THE 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | 7) PLEASE ILLUSTRATE REQUIRED FIRE | | | SEPARATION REQUIREMENT FOR SEPARATE | | | TENANT SPACES. | | | | | | 8) PLEASE SHOW LOCATION AND DISTANCE OF | | | CLOSEST FIRE HYDRANT IN RELATION TO | | | BUILDING. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-10-17 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-12 |
Time |
15:13 |
Sent To |
Z |
|
| Notes |
| 2007-10-12 15:13:59 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2007-10-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-01 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-01 |
Time |
08:26 |
Sent To |
Z |
|
| Notes |
| 2007-10-01 09:02:39 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-28 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-28 |
Time |
15:01 |
Sent To |
Z |
|
| Notes |
| 2007-09-28 15:01:53 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-18 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-18 |
Time |
11:07 |
Sent To |
B |
|
| Notes |
| 2007-06-18 11:07:58 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-05-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-29 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-29 |
Time |
11:37 |
Sent To |
B |
|
| Notes |
| 2007-05-29 11:38:13 | TO "SHILL" DESK/RESTAMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-04-02 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-02 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2007-04-03 17:52:40 | TO COMM BOARD # 29 | | 2007-04-02 17:40:40 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-17 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-17 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2007-01-17 15:28:47 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-04-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-15 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-15 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2006-05-10 00:00:00 | TO "COMM" BD#45 | | 2006-04-15 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-13 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-13 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2006-03-06 00:00:00 | TO "COMM" BD#48 | | 2006-02-13 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-11 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-11 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2005-11-09 00:00:00 | TO "COMM" BD#32 | | 2005-10-11 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-13 |
Time |
22:53 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-07-12 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2005-07-19 00:00:00 | TO "COMM" BD#15 | | 2005-07-14 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-05-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-05-02 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-05-02 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2007-05-02 15:01:06 | ---------------DENIED----------------- | | | | | | 1. REVISION TO AN APPROVED PLAN SHALL BE DONE/APPROVED | | | BY THE DESIGNER OF RECORD PER FAC 61G15-30. | | | | | | 2. IF THIS PLAN IS TO BE A REVISION UNDER MASTER PERMIT | | | #05070366, IT NEEDS TO BE UNDER THE 2001 FBC WHICH WAS | | | IN EFFECT AT THE TIME OF PERMIT ISSUANCE. | | | | | | 3. PREVIOUS PLAN WAS PASSED WITH A PROVISO. THE PROVISO | | | RELATES TO FBC,M 306.5 (2001) WHICH REQUIRES PERMANENT | | | ACCESS TO EQUIPMENT ON ROOFS AND ELEVATED STRUCTURES. | | | IT NEEDS TO BE ADDRRESSED DURING THE REVISION PROCESS. | | | | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-12-03 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-12-03 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-12-03 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2005-12-03 00:00:00 | PASS PRIVISO | | | PLEASE REFER TO SECTION 306.5 EQUIPMENT | | | AND APPLIANCES ON ROORS.2001 FBC(M) | | | PLAN REVIEW BY HAROLD MOSER.561-805-6732 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-27 |
Time |
20:13 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2005-07-27 |
Time |
19:42 |
Sent To |
|
|
| Notes |
| 2005-07-27 00:00:00 | DENIED: | | | 1. PLAN SHEET A-3-ROOF EQUIPMENT DETAIL | | | CLEARENCE ABOVE FINISHED ROOF SHALL | | | COMPLY WITH ZOOL FBC 1511.7. | | | | | | 2. PROUIDE DETAIL FOR HANGING OF THE | | | AHU. | | | | | | 3. CONDENSATE SHALL TERMINATE A MINIMUM | | | OF 12" AWAY FROM THE BUILDING STRUCTURE, | | | 2001 FBC 1503.4.4. | | | | | | 4. PLAN SHEET MP-2 HVAC SPECIFICATIONS | | | #19 - EMERGENCY DRAIN PAN SHALL HAVE | | | OVERFLOW PROTECTION IN ACCORDANCE WITH | | | 2001 FBC(M)307.2.3. | | | | | | 5.PLEASE INDICATE VENTILATION FOR THE | | | WAREHOUSE AREAS PER 2001 FBC(M) TABLE | | | 403.3. | | | | | | 6. INDICATE ACCESS TO EQUIPMENT LOCATED | | | ON THE ROOF.PERMANENT MEANS OF ACCESS | | | IS REQUIRED FOR HEIGHTS GREATER THAN 16 | | | FEET. 2001 FBC(M)306.5 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-05-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-05-16 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-05-16 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2007-05-16 09:14:22 | DENIED | | | REFERENCE: FLORIDA STATUTES | | | FLORIDA ADMINISTRATIVE CODE | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | | | | 1. THE REVISION SUBMITTED SUPERCEDES THE SHEETS | | | SUBMITTED AND APPROVED FOR THE ORIGINAL PERMIT. BY | | | SUPERCEDING THESE SHEETS, ALL INFORMATION ORIGINALLY | | | SUBMITTED WILL BE DELETED. THIS IS NOT ACCEPTABLE. | | | | | | 2. IF THERE IS REVISIONS FOR THE PLANS, THEY SHALL BE | | | DESIGNED BY THE ARCHITECT AND ENGINEER OF RECORD. IF | | | THERE WILL BE A NEW ARCHITECT AND ENGINEER OF RECORD, | | | THEN A NEW PERMIT WILL BE REQUIRED AND A SHOP DRAWING | | | APPROVED BY THE ORIGINAL ARCHITECT AND ENGINEER SHALL | | | BE SUBMITTED. | | | | | | 3. A SEPARAGE PERMIT WITH THE NEW DESIGN PROFESSIONALS | | | WILL BE ALLOWED AFTER THE CERTIFICATE OF OCCUPANCY | | | WITHOUT APPROVAL OF THE ORIGINAL DESIGN TEAM. | | | | | | 4. SHT A-1 THE BUILDING DATA INDICATES THE OCCUPANCY AS | | | STORAGE. THE FLOOR PLAN INDICATES A MIXED OCCUPANCY | | | WITH BUSINESS AND STORAGE OCCUPANCY. PLEASE INDICATE | | | CORRECT OCCUPANCE. | | | | | | 5. PER TABLE 403.1 A SERVICE SINK IS REQUIRED IN THE | | | STORAGE OCCUPANCY. | | | | | | 6. SHT A-1 THE BREAK ROOM SINK REQUIRES A FORWARD | | | APPROACH MAXIMUM 19" UNDERNEATH THE SINK, AND NOT | | | PARALLEL APPROACH AS SHOWN. SECTION 11-4.16.5. | | | | | | 7. SHT A-1 THE ROOM FINISH SCHEDULE INDICATES PAINT ON | | | THE WALLS OF THE TOILET ROOMS 106 & 107. PER SECTION | | | 1210.2 WALLS WITHIN 2 FEET OF THE WATER CLOSETS SHALL | | | HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. PAINTED | | | WALLS DOES NOT COMPLY WITH THE "HARD" REQUIREMENT. | | | PLEASE INDICATE COMPLIANCE. | | | | | | 8. SUBMIT A DETAIL FOR THE TOILET ROOMS SHOW COMPLIANCE | | | WITH THE FOLLOWING: | | | ___FOR W/C'S | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.3 HEIGHT | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | ___FOR LAVS | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.16.5 FAUCETS | | | THE W/C'S SHALL BE 18" OFF THE WALL TO THE CENTERLINE | | | OF THE FIXTURE & THE LAV SHALL BE A MINIMUM OF 15" OFF | | | THE WALL TO THE CENTERLINE OF THE FIXTURE. SEE FIGURE | | | 29 AND THE LAV SHALL BE CENTERED ON THE 30" DIMENSION | | | OF THE CLEAR FLOOR SPACE. | | | | | | 9. SHT A-2 DETAIL #1. SHOW COMPLIANCE WITH THE | | | FOLLOWING: | | | A. 11-4.24.4 SINK DEPTH | | | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | | REQUIRED) | | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | | D. 11-4.24.7 FAUCETS. | | | | | | 10. SHT P-1 SANITARY RISER DIAGRAM. ONLY THE FIXTURES | | | WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. ADDITIONAL | | | FIXTURES, (BREAK ROOM SINK), SHALL DISCHARGE DOWNSTREAM | | | OF THE WET VENT. SECTION 909.1. | | | | | | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE | | | TO THE BUILDING/SPACE. SECTION 608.13.2.. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-12-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-12-14 |
Time |
07:42 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-12-13 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2005-12-14 00:00:00 | RPZV BACKFLOR REQD. ON WATER SERVICE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-08-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-08 |
Time |
17:50 |
Rev Time |
2.95 |
| Received By |
kstevens |
Date |
2005-08-08 |
Time |
17:50 |
Sent To |
|
|
| Notes |
| 2005-08-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FBC-2001 BUILDING | | | | | | 1. SHT A-2 PER TABLE 403.2 SEPARATE | | | FACILITIES ARE REQUIRED FOR MEN AND | | | WOMEN. | | | 2. SHT A-2 TABLE 403.1 STORAGE | | | FACILITIES REQUIRES A SERVICE SINK. | | | 3. SHT A-2 INDICATES 13,392SF BUILDING | | | AREA, BUT SHT A-3 GUTTER & DOWNSPOUT | | | CALCULATIONS SHOW FLAT ROOF AREA AS | | | 6,128SF. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 4. SHT A-3 GUTTER & DOWNSPOUT | | | CALCULATION FOR PARAPETS DO NOT INCLUDE | | | THE PARAPET WALL FOR THE FRONT OF THE | | | BUILDING. ALSO ALL VERTICAL WALLS FOR | | | THE THREE SIDES OF THE CUPOLA, AND 5 | | | SIDES FOR EACH WALL AT THE A/C EQUIPMENT | | | SHALL BE INCLUDED IN THE CALCULATIONS. | | | SECTION 1106.4. ALSO NOT INCLUDED IN THE | | | CALCULATIONS SHALL BE THE AREA OF THE | | | ROOF FROM THE CUPOLA THAT DRAINS ONTO | | | THE FLAT ROOF AREA FROM ABOVE. PLEASE | | | RECALCULATE SQUARE FOOTAGE FOR ROOF AREA | | | TO BE DRAINED. | | | 5. SUBMIT A DETAIL FOR THE GUTTER | | | SHOWING SIZE OF GUTTER COMPLYING WITH | | | TABLE 1106.6, SLOPE OF GUTTER WITH HIGH | | | POINTS OF GUTTER CALLED OUT ON PLAN, | | | WITH THE SIZE AND LOCATION OF EACH | | | DOWNSPOUT. INDICATE THE TOTAL AREA | | | DRAINING INTO EACH DOWNSPOUT. SECTION | | | 104.2.1. | | | 6. SHT A-6 DETAIL #9 CONTROLS FOR | | | DRINKING FOUNTAIN DO NOT SEEM TO COMPLY | | | WITH SECTION 11-4.27.4. (TWISTING OF THE | | | WRIST). PLEASE CLARIFY. - PLEASE SHOW | | | COMPLIANCE WITH SECTION 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING. | | | 7. SHT A-6 DETAIL #2 SHOW THE FOLLOWING: | | | | | | FOR W/C, 11-4.16.5 FLUSH CONTROLS | | | FOR LAV, 11-4.19.5 FAUCETS | | | 8. SHT ME-2 SANT. RISER DIAGRAM, A 2-WAY | | | CLEANOUT IS REQUIRED NEAR THE JUNCTION | | | OF THE BUILDING DRAIN AND THE BUILDING | | | SEWER. SECTION 708.3.5. | | | 9. SHT MP-2 SANT. RISER DIAGRAM, ALL | | | HORIZONTAL BUILDING DRAINS REQUIRE A | | | CLEANOUT. SECTION 708.3.1. | | | 10. SHT MP-2 WATER RISER DIAGRAM, AN RPZ | | | BACKFLOW IS REQUIRED ON THE WATER | | | SERVICE TO THE BUILDING. | | | 11. A SEPARATE IRRIGATION PERMIT AND | | | PLANS ARE REQUIRED. SECTION 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-10-17 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-10-17 |
Time |
09:27 |
Sent To |
I |
|
| Notes |
| 2007-10-17 14:15:27 | REVISION |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
bpowell |
Date |
2007-10-03 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
bpowell |
Date |
2007-10-03 |
Time |
15:04 |
Sent To |
B |
|
| Notes |
| 2007-10-03 15:05:41 | 1. THE PLANS SHALL REFLECT THE ACTUAL CONDITIONS OF THE | | | SITE. THE PIGMY DATE PALMS THAT HAVE BEEN RELOCATED | | | SHALL SHOW THE NEW LOCATION OF EACH, THE SIDEWALK GOING | | | THROUGH THE LANDSCAPE ISLAND SHALL BE SHOWN, AND ANY | | | OTHER CONDITION SHOWN ON THE PLAN MUST REFLECT WHAT IS | | | ACTUALLY THERE. | | | | | | 2. ALL PLANS WITHIN THE PACKET SHALL BE CONSISTENT. | | | | | | FOR QUESTIONS OR COMMENTS CONTACT;BOBBY POWELL JR., | | | PLANNER, (561) 822-1435, [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-06-30 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2006-06-30 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2006-06-30 |
Time |
17:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-03-22 |
|
|
Cont ID |
|
| Sent By |
ebowers |
Date |
2006-03-22 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
ebowers |
Date |
2006-03-22 |
Time |
09:55 |
Sent To |
I |
|
| Notes |
| 2006-03-07 00:00:00 | NEW SHEET CONTAINING NEW SITE PLAN. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-08-03 |
|
|
Cont ID |
|
| Sent By |
ebowers |
Date |
2005-08-03 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
ebowers |
Date |
2005-08-03 |
Time |
12:12 |
Sent To |
I |
|
| Notes |
|
|