Plan Review Details - Permit 05070365
Plan Review Stops For Permit 05070365
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By btrobaug Date 2007-04-27 Time 12:35 Rev Time 0.50
Received By btrobaug Date 2007-04-27 Time 12:10 Sent To P
Notes
2007-04-27 12:35:16 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 INDICATE HOW THE PUMP IS BEING FED, FROM WHERE,
 CONDUIT,CONDUCTOR SIZE AND TYPE, OVERCURRENT
 PROTECTION.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF THIS
 WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2007-04-20 Cont ID  
Sent By rchokshi Date 2007-04-20 Time 09:05 Rev Time 0.00
Received By rchokshi Date 2007-04-20 Time 09:02 Sent To  
Notes
2007-04-20 09:05:10THERE IS NO ENGINEERING REVIEW REQUIRED PER LUIS
 MARTINEZ.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-07-15 Cont ID  
Sent By mamini Date 2005-07-15 Time 09:51 Rev Time 1.00
Received By mamini Date 2005-07-15 Time 09:51 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-07-15 Cont ID  
Sent By mwennerg Date 2005-07-15 Time 13:09 Rev Time 0.00
Received By mwennerg Date 2005-07-15 Time 13:09 Sent To  
Notes
2005-07-15 00:00:00******PROVISO******
  
 1) WITH THE UNDERSTANDING THAT THESE
 BUILDINGS WILL BE FIRE SPRINKLERED, FIRE
 LINES AND INDICATING CONTROL VALVES,
 (PIV'S) FOR EACH BUILDING WILL BE
 REQUIRED. PLEASE ILLUSTRATE WHEN
 DRAWINGS ARE SUBMITTED FOR REVIEW.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 16:42 Sent To ENG
Notes
2007-04-20 08:24:18TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 13:54 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 13:54 Sent To ENG
Notes
2005-07-12 00:00:00TO "ENG" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By mperson Date 2007-04-30 Time 13:42 Rev Time 0.45
Received By mperson Date 2007-04-30 Time 13:42 Sent To PC
Notes
2007-04-30 14:02:07DENIED REVISION
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 3 OF 4: CLEARLY INDICATE ON THE REVISION
 RESUBMITTAL IF THE BOOSTER PUMPS ARE FOR THE POTABLE
 WATER SYSTEM OR THE FIRE SYSTEM.
  
 2. PLEASE INDICATE ON THE RESUBMITTAL HOW THE BOOSTER
 PUMPS ARE ANCHORED TO MEET 140 MPH WIND LOADS PER
 FBC-2004 SECTION 1603.1.4 WIND DESIGN DATA AND SECTION
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDING. (DETAIL REQUIRED)
  
 3. PER FBC-2004 PLUMBING, SECTION 606.5.5 LOW-PRESSURE
 CUTOFF REQUIRED ON BOOSTER PUMPS: A LOW-PRESSURE CUTOFF
 SHALL BE INSTALLED ON ALL BOOSTER PUMPS IN A WATER
 PRESSURE BOOSTER SYSTEM TO PREVENT THE CREATION OF A
 VACUUM OR NEGATIVE PRESSURE ON THE SUCTION SIDE OF THE
 PUMP WHEN A POSITIVE PRESSURE OF 10 PSI OR LESS OCCURS
 ON THE SUCTION SIDE OF THE PUMP. (PLEASE INDICATE A
 LOW-PRESSURE CUTOFF ON THE RESUBMITTED REVISION)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721