Plan Review Details - Permit 05070357
Plan Review Stops For Permit 05070357
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-20 Cont ID  
Sent By alange Date 2005-07-20 Time 11:37 Rev Time 0.33
Received By alange Date 2005-07-20 Time 11:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-13 Cont ID  
Sent By jgomez Date 2005-07-13 Time 12:23 Rev Time 0.33
Received By jgomez Date 2005-07-13 Time 12:23 Sent To PC
Notes
2005-07-13 00:00:00THIRD CHECKLIST:
 1- CONTRACTOR RE-SUBMITTED EXACTLY THE
 SAME PACKAGE THAT WAS DENIED ON 7-12-05
 WITHOUT ADDRESSING ANY OF THE COMMENTS.
 NEED TO ADDRESS COMMENTS LISTED ON
 SECOND CHECKLIST DATED 7-12-05 AND
 RE-SUBMITTAL FEES ARE DUE. SEE ATTACHED
 COPIES OF PREVIOUS CHECKLISTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-12 Cont ID  
Sent By jgomez Date 2005-07-12 Time 13:26 Rev Time 0.33
Received By jgomez Date 2005-07-12 Time 13:26 Sent To PC
Notes
2005-07-12 00:00:00SECOND CHECKLIST:
  
 1- INFORMATION SUBMITTED IS INCOMPLETE.
 ONLY FLORIDA PRODUCT APPROVALS WERE
 SUBMITTED AND DADE COUNTY NOA'S
 SUBMITTED THE FIRST TIME ARE NOT
 INCLUDED NOW.
  
 2- STILL THERE IS NOT INFORMATION
 SUBMITTED FOR SPECIFIC SYSTEM TO BE USED
 FOR MODIFIED BITUMEN SYSTEM AT FLAT
 ROOF.
  
 3- PROVIDE COMPLETE SPECIFICATIONS THAT
 WERE SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL FOR FAST 90 SELF ADHERING TILE
 UNDERLAYMENT. CEMENT TILE WILL BE
 INSTALLED WITH POLYFOAM AND ATTACHED TO
 THE UNDERLAYMENT. NEED UNDERLAYMENT
 SPECS TO VERIFY UPLIFT PRESSURES TO HOLD
 TILE SINCE THEY ARE NOT MECHANICALLY
 ATTACHED TO THE ROOF DECKING. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT(561) 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By jgomez Date 2005-07-11 Time 14:12 Rev Time 0.33
Received By jgomez Date 2005-07-11 Time 14:12 Sent To PC
Notes
2005-07-11 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 CONCRETE TILE AND MODIFIED BITUMEN.
 DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY A FLORIDA PRODUCT
 APPROVAL.
  
 2- MODIFIED BITUMEN REPORT IS MISSING
 THE SPECIFIC SYSTEM THAT IS GOING TO BE
 INSTALLED. EG: WOOD DECK WITH INSULATION
 OR WITHOUT INSULATION. ALSO, CHECK
 LIMITATION #7 OR #9.
  
 3- CEMENT TILES ARE GOING TO BE
 INSTALLED WITH POLYFOAM AND UNDERLAYMENT
 TO BE USED IS SELF ADHESIVE. PROVIDE
 COMPLETE MANUFATURER SPECS SHOWING
 UPLIFT PRESSURES. SINCE THE UNDERLAYMENT
 IS THE ONE HOLDING THE TILE. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 11:09 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 11:09 Sent To B
Notes
2005-07-13 00:00:00TO "JGOMEZ" BOX/RESUB