Plan Review Details - Permit 05070357
| Plan Review Stops For Permit 05070357 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-07-20 |
Time |
11:37 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-07-20 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-07-13 |
Time |
12:23 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2005-07-13 |
Time |
12:23 |
Sent To |
PC |
|
| Notes |
| 2005-07-13 00:00:00 | THIRD CHECKLIST: | | | 1- CONTRACTOR RE-SUBMITTED EXACTLY THE | | | SAME PACKAGE THAT WAS DENIED ON 7-12-05 | | | WITHOUT ADDRESSING ANY OF THE COMMENTS. | | | NEED TO ADDRESS COMMENTS LISTED ON | | | SECOND CHECKLIST DATED 7-12-05 AND | | | RE-SUBMITTAL FEES ARE DUE. SEE ATTACHED | | | COPIES OF PREVIOUS CHECKLISTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-07-12 |
Time |
13:26 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2005-07-12 |
Time |
13:26 |
Sent To |
PC |
|
| Notes |
| 2005-07-12 00:00:00 | SECOND CHECKLIST: | | | | | | 1- INFORMATION SUBMITTED IS INCOMPLETE. | | | ONLY FLORIDA PRODUCT APPROVALS WERE | | | SUBMITTED AND DADE COUNTY NOA'S | | | SUBMITTED THE FIRST TIME ARE NOT | | | INCLUDED NOW. | | | | | | 2- STILL THERE IS NOT INFORMATION | | | SUBMITTED FOR SPECIFIC SYSTEM TO BE USED | | | FOR MODIFIED BITUMEN SYSTEM AT FLAT | | | ROOF. | | | | | | 3- PROVIDE COMPLETE SPECIFICATIONS THAT | | | WERE SUBMITTED FOR FLORIDA PRODUCT | | | APPROVAL FOR FAST 90 SELF ADHERING TILE | | | UNDERLAYMENT. CEMENT TILE WILL BE | | | INSTALLED WITH POLYFOAM AND ATTACHED TO | | | THE UNDERLAYMENT. NEED UNDERLAYMENT | | | SPECS TO VERIFY UPLIFT PRESSURES TO HOLD | | | TILE SINCE THEY ARE NOT MECHANICALLY | | | ATTACHED TO THE ROOF DECKING. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT(561) 805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-07-11 |
Time |
14:12 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2005-07-11 |
Time |
14:12 |
Sent To |
PC |
|
| Notes |
| 2005-07-11 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | | | 1- PROVIDE FLORIDA PRODUCT APPROVAL OR | | | APPLY FOR LOCAL PRODUCT APPROVAL FOR | | | CONCRETE TILE AND MODIFIED BITUMEN. | | | DADE COUNTY NOA ALONE IS NOT | | | AUTOMATICALLY A FLORIDA PRODUCT | | | APPROVAL. | | | | | | 2- MODIFIED BITUMEN REPORT IS MISSING | | | THE SPECIFIC SYSTEM THAT IS GOING TO BE | | | INSTALLED. EG: WOOD DECK WITH INSULATION | | | OR WITHOUT INSULATION. ALSO, CHECK | | | LIMITATION #7 OR #9. | | | | | | 3- CEMENT TILES ARE GOING TO BE | | | INSTALLED WITH POLYFOAM AND UNDERLAYMENT | | | TO BE USED IS SELF ADHESIVE. PROVIDE | | | COMPLETE MANUFATURER SPECS SHOWING | | | UPLIFT PRESSURES. SINCE THE UNDERLAYMENT | | | IS THE ONE HOLDING THE TILE. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-13 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-13 |
Time |
11:09 |
Sent To |
B |
|
| Notes |
| 2005-07-13 00:00:00 | TO "JGOMEZ" BOX/RESUB |
|
|
|