Plan Review Details - Permit 05070322
Plan Review Stops For Permit 05070322
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-07 Cont ID  
Sent By dpalmer Date 2005-09-07 Time 13:22 Rev Time 0.25
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By btrobaug Date 2005-08-01 Time 14:36 Rev Time 0.50
Received By btrobaug Date 2005-08-01 Time 14:19 Sent To M
Notes
2005-08-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A CALCULATION FOR THE LOAD
 INTENDED TO BE SERVED BY THE GENERATOR.
 SEE 702.5. LIGHTING LOADS MAY TAKE THE
 DEMAND FROM 220.3. ALL OTHERS AT 100%
 PER 702.5.
  
 2} INDICATE THE CONDUIT AND CONDUCTOR
 SIZE OF ALL BEING INSTALLED FOR THIS
 SYSTEM. SEE 445.13, FEEDER @ 115%
 NAMEPLATE.
  
 3} PLEASE SEE 225.30 THROUGH 225.37 FOR
 DISCONNECT RATING, GROUPING AND SIGNAGE
 REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 15:47 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 15:47 Sent To Z
Notes
2005-07-11 00:00:00TO "Z" BOX