Plan Review Details - Permit 05070317
Plan Review Stops For Permit 05070317
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-04 Cont ID  
Sent By jwitmer Date 2007-04-04 Time 09:57 Rev Time 0.77
Received By jwitmer Date 2007-04-04 Time 09:57 Sent To PC
Notes
2007-04-04 09:58:49LOCATION REVISION 2'-0" FROM STRUCTURE, EMAILED KOHLER
 SPEC OKING 18" FROM STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-03 Cont ID  
Sent By jwitmer Date 2007-04-03 Time 13:49 Rev Time 1.22
Received By jwitmer Date 2007-04-03 Time 13:49 Sent To PC
Notes
2007-04-03 13:56:05BUILDING PLAN REVIEW
 PERMIT: 05070317
 ADD: 6815 S FLAGLER
 CONT: HINCKLEY CONSTRUCTION
 TEL: (561)718-9051
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1)104.1.2* /2001 FBCADDITIONAL INFORMATION
 REQUIRED,
 PLEASE PROVIDE MANUFACTURERS SPECS FOR LOCATION OF UNIT
 NEXT TO
 STRUCTURES. THIS OFFICE INDICATES IN THE KOHLER SPECS
 THE GENERATOR
 PLACEMENT A MINIMUM OF 3'-0" FROM OTHER STRUCTURES.
 110.3 NEC
 90.7 NEC
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-30 Cont ID  
Sent By jwitmer Date 2006-05-30 Time 12:03 Rev Time 0.77
Received By jwitmer Date 2006-05-30 Time 12:03 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-13 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 08:26 Rev Time 0.33
Received By jwitmer Date 2005-08-13 Time 08:26 Sent To PC
Notes
2005-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070317
 ADD: 6815 S FLAGLER DR
 CONT: HINKLEY CONSTRUCTION
 TEL: (561)718-9051
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) NO SURVEY SITE PLAN, NOTE!
 FL S S 472.025 / 61G17-6.002(8)(E)
  
 61G17-6.002(8)(E) ALL SURVEY MAPS AND
 REPORTS OR COPIES THEREOF ARE NOT VALID
 WITHOUT THE ORIGINAL SIGNATURE, AND THE
 ORIGINAL RAISED SEAL OF A FLORIDA FOR
 LICENSED SURVEYORS AND MAPPERS.
  
 61G17-6.002(8)(C) ALL SURVEY MAPS AND
 REPORTS MUST BEAR THE NAME, "CERTIFICATE
 OF AUTHORIZATION NUMBER", AND THE STREET
 MAILING ADDRESS OF THE BUSINESS ENITITY
 ISSUING THE MAP OR REPORT, ALONG WITH
 NAME AND LICENSE NUMBER OF THE SURVEYOR
 AND MAPPER IN RESPONSIBLE CHARGE.
  
 2) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By btrobaug Date 2006-05-11 Time 15:02 Rev Time 0.50
Received By btrobaug Date 2006-05-11 Time 14:20 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By btrobaug Date 2005-08-01 Time 10:46 Rev Time 0.50
Received By btrobaug Date 2005-08-01 Time 10:20 Sent To M
Notes
2005-08-01 00:00:00 
 1} PLEASE PROVIDE A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF ALL SERVICE AND
 GENERATOR EQUIPMENT SO SIGNAGE(225.37)
 AND DISCONNECT(230.71) ISSUES CAN BE
 REVIEWED.
  
 2} PLEASE PROVIDE MANUFACTURERS
 SPECIFICATIONS FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 SEE OTHER REVIEWS FOR ALL REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 15:22 Sent To B
Notes
2007-03-24 15:22:43TO "JWITMER"DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 11:45 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 11:45 Sent To E
Notes
2006-05-11 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 09:57 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 09:57 Sent To Z
Notes
2006-04-24 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 09:26 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 09:26 Sent To E
Notes
2005-07-21 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 09:21 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 09:21 Sent To Z
Notes
2005-07-11 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By rregueir Date 2005-08-01 Time 16:06 Rev Time 0.00
Received By rregueir Date 2005-08-01 Time 16:06 Sent To P
Notes
2005-08-01 00:00:00PLANS CALL FOR SEPERATE PERMIT
 APPLICATION TO COVER FUEL.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-02 Cont ID  
Sent By jleech Date 2005-08-02 Time 14:53 Rev Time 0.25
Received By jleech Date 2005-08-02 Time 14:53 Sent To B
Notes
2005-08-02 00:00:00FUEL PERMIT IS REQUIRED. SUBMIT APP WITH
 PLANS

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-09 Cont ID  
Sent By mmclean Date 2006-05-09 Time 15:49 Rev Time 0.00
Received By mmclean Date 2006-05-09 Time 15:49 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-19 Cont ID  
Sent By mmclean Date 2005-07-19 Time 09:03 Rev Time 0.00
Received By mmclean Date 2005-07-19 Time 09:03 Sent To I
Notes
2005-07-19 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEY,
 SHOWING LOCATION OF GENERATOR.
 2. MUST PROVIDE THE SETBACK OF THE
 GENERATOR (ON TWO COPY OF SURVEY) AND
 DIMENSION OF GENERATOR.
 **GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK**.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720