| 2005-07-25 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC 1606.1.4SHUTTERS. |
| | INSTALLATION/DESIGN INFORMATION |
| | REQUIRED.SUBMIT AN INSTALLATION |
| | SCHEDULE INCLUDING THE FOLLOWING |
| | DETAILS: |
| | (A) BUILDING CONSTRUCTION TYPE (EG CBS) |
| | (B) BUILDING (OR INSTALLATION) HEIGHT |
| | (C) DESIGN PRESSURE FOR EACH OPENING |
| | (D) OPENING SIZES |
| | (E) SHUTTER SPAN (VERTICAL/HORIZONTAL?) |
| | (F) ANCHOR TYPE, SIZE AND SPACING |
| | A FORM IS AVAILABLE FROM THIS OFFICE |
| | GIVING THE RECOMMENDED INSTALLATION |
| | SCHEDULE FORMAT.SUBMIT THE ABOVE |
| | INFORMATION WHICH IS REQUIRED FOR |
| | REVIEW.A COPY OF THE RECOMMENDED |
| | INSTALLATION SCHEDULE FORM IS ATTACHED. |
| | |
| | 2) THE SUBMITTED STATEWIDE PRODUCT |
| | APPROVAL FL1850 REFERS TO DRAWING |
| | 03-0135.THE VERSION OF THAT DRAWING ON |
| | THE STATEWIDE PRODUCT APPRVAL WEBSITE |
| | INCLUDES THE SIGNATURE AND SEAL OF |
| | WALTER A. TILLIT JR. P.E.THE TWO |
| | COPIES SUBMITTED FOR REVIEW DO NOT |
| | INCLUDE THE SIGNATURE AND SEAL AND SO |
| | CANNOT BE VERIFIED AS HAVING BEEN |
| | PREPARED/REVIEWED BY THE ENGINEER. |
| | DOWNLOAD AND SUBMIT TWO COPIES OF |
| | DRAWING 03-0135 SO THAT THEY ARE AN |
| | EXACT MATCH FOR THAT APPROVED BY THE |
| | STATE. |
| | |
| | 3) SOME THE OPTIONS COVERED BY THE |
| | SUBMITTED PRODUCT APPROVALS MAY NOT BE |
| | CODE COMPLIANT IF USED FOR THIS PROJECT. |
| | THE PRODUCT APPROVAL SHEETS SHALL BE |
| | MARKED, AS APPROPRIATE, TO IDENTIFY |
| | WHICH PRODUCT OPTIONS/SPANS/FASTENERS |
| | AND ANCHORING CONDITIONS ARE TO BE USED. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |