Plan Review Details - Permit 05070247
| Plan Review Stops For Permit 05070247 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-15 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-15 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | ******DENIED****** | | | | | | 1) PERMIT APPLICATION REFERENCES FUEL | | | PIPING ONLY. A DETAIL OF THE NEW | | | GENERATOR IS SHOWN ON THE DRAWINGS. | | | SEPARATE SHOP DRAWINGS AND PERMITS FOR | | | THE GENERATOR AND FUEL SUPPLY ARE | | | REQUIRED. PLEASE PROVIDE ADDITIONAL | | | INFORMATION AND CLARIFICATION IN REGARDS | | | TO SCOPE OF WORK. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 805-6722 OR 835-2951 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-08 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-08 |
Time |
13:22 |
Sent To |
FIRE |
|
| Notes |
| 2005-07-08 00:00:00 | TO "F" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-18 |
Time |
08:12 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-07-18 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2005-07-18 00:00:00 | DENIED: | | | 1.PROVIDE MANUFACTURER'S SUBMITTAL | | | DATA FOR THE GENERATOR. | | | | | | 2.PROVIDE ELEVATION TO BOTTOM OF THE | | | MUFFLER EXHAUST PIPE RUNNING THROUGH THE | | | PARKING GARAGE. | | | | | | 3.PROVIDE DISTANCE PROPERTY LINES. | | | SHOW COMPLIANCE WITH 2001 FBC(M)401.5 | | | | | | 4.EXHAUST OPENINGS SHALL NOT BE | | | DIRECTED ONTO WALKWAYS PER 2001 | | | FBC(M)401.5.2.PLEASE NOTE, EXHAUST | | | SHALL TERMINATE IN SUCH A MANNER THAT IT | | | WILL NOT RECIRCULATE INTO THE GARAGE, | | | FRESH AIR INTAKES, WINDOWS, DOORS, OR | | | VENTILATING SYSTEMS. | | | | | | 5.PLAN INDICATES FUEL PIPING THROUGH | | | THE ELECTRICAL VAULT, PLEASE CLARIFY. | | | | | | 6.PLEASE CLARIFY AREA IN WHICH EF-3 | | | TERMINATES.IS THIS A PARKING AREA? | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|
|
|