Plan Review Details - Permit 05070229
Plan Review Stops For Permit 05070229
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-05 Cont ID  
Sent By jwitmer Date 2005-08-05 Time 16:25 Rev Time 0.00
Received By JWITMER Date 2005-08-05 Time 19:45 Sent To PC
Notes
2005-08-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070229
 ADD: 210 SUNSET RD
 CONT: MIRAGE POOLS
 TEL: (561)644-0302
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ACTION: REVIEWED
  
 BUILDING PROVISO:
  
 BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE
 PROVIDED WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH
 424.2.17.1.14.
 424.2.17.1.15 CHILD SAFETY BARRIER
  
 2)13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 EXCEPTION: OUTDOOR POOLS DERIVING OVER
 70 PERCENT OF THE ENERGY FOR HEATING
 FROM NON-DEPLETABLE ON SITE-RECOVERED
 SOURCES COMPUTED OVER AN OPERATING
 SEASON ARE EXEMPT FROM THIS
 REQUIREMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By jleahy Date 2005-09-29 Time 19:44 Rev Time 0.30
Received By jleahy Date 2005-09-29 Time 19:44 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-20 Cont ID  
Sent By jleahy Date 2005-07-20 Time 15:11 Rev Time 0.30
Received By jleahy Date 2005-07-20 Time 15:11 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 11:03 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 11:03 Sent To E
Notes
2005-09-29 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 15:15 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 15:15 Sent To P
Notes
2005-09-06 00:00:00TO "JLEECH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 09:29 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 09:29 Sent To E
Notes
2005-07-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 16:41 Sent To Z
Notes
2005-07-07 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-10-12 Cont ID  
Sent By jleech Date 2005-10-12 Time 07:24 Rev Time 1.00
Received By jleech Date 2005-10-12 Time 07:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-09-21 Cont ID  
Sent By jleech Date 2005-09-21 Time 07:34 Rev Time 0.75
Received By jleech Date 2005-09-21 Time 07:34 Sent To  
Notes
2005-09-21 00:00:00DENIED; 2ND TIME
 1) FBC-2001 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)
 2) FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING.THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND
 REMOVAL.SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER
 FUNCTION OF THE FILTRATION AND PIPING
 SYSTEMS.SEC 424.2.8.3 WHERE CHECK
 VALVES ARE INSTALLED THEY SHALL BE OF
 THE SWING OR VERTICAL CHECK PATTERNS.
 SEC 424.2.8.4 COMBINATION VALVES SHALL
 REQUIRE APPROVAL OF THE ADMINISTRATIVE
 AUTHORITY PRIOR TO THEIR INSTALLATION.
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 4)424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 5)FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLUMBING SEC. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPING.
 (ADD TO NOTES)
 6)424.2.15 GAS PIPING SHALL COMPLY WITH
 FBC FUEL GAS. SEPARATE PLANS AND PERMIT
 REQUIRED. (ADD TO NOTES)
 PLANS WERE NEVER SENT BACK TO ENGINEER
 FOR REQUESTED CHANGES. ENGINEER'S SEAL
 DATE IS 6/12/05 FIRST REVIEW WAS DONE
 7/26/05. COPY OF FIRST REVIEW INCLOSED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By jleech Date 2005-07-26 Time 07:52 Rev Time 0.75
Received By jleech Date 2005-07-26 Time 07:52 Sent To B
Notes
2005-07-26 00:00:00DENIED;
 1.SEC.424.2.7.1 EQUIPMENT SLAB TO BE
 4"THICK. SHOW ON PLAN
 2.424.2.8.1 VALVESSHALL BE READLY
 ACCESSIBLE FOR MAINT. AND REMOVAL. FULL
 WAY VALVES SHALL BE INSTALLED. WHERE
 CHECK VALVES ARE USED THEY SHALL BEOF
 THE SWING OR VERTICAL CHECK PATTERNS. (
 ADD TO NOTES)
 3.WATER SUPPLY LOCAL ORD. #2853-95,
 BACKFLOW REQUIRED ON WATER SERVICES.
 (ADD TO NOTES)
 4.PRESSURE TESTS. PER. MANUFACTURE
 RECOMMENDATIONS, NO AIR TEST SHALL BE
 APPROVED FOR PVC PIPE AND FITTINGS. (ADD
 TO NOTES)
 5.FBC PLUMBING SEC.605.21 PURPLE PRIMER
 REQUIRED ON PVC PIPE AND FITTINGS. (ADD
 TO NOTES)
 6.424.2.14.4 ALL WATER HEATER EQUIPMENT
 SHALL BE INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO HEATER. (ADD TO
 NOTES)
 7.GAS PIPING SHALL COMPLY TO FBC FIEL
 GAS. SEPARATE PLANS AND PERMIT REQUIRED.
 ADD TO NOTES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-15 Cont ID  
Sent By mmclean Date 2005-07-15 Time 14:20 Rev Time 0.00
Received By mmclean Date 2005-07-15 Time 14:20 Sent To I
Notes
***NONE***