Plan Review Details - Permit 05070224
Plan Review Stops For Permit 05070224
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-25 Cont ID  
Sent By jwitmer Date 2006-01-25 Time 17:27 Rev Time 0.77
Received By jwitmer Date 2006-01-25 Time 17:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-14 Cont ID  
Sent By jwitmer Date 2005-11-14 Time 09:19 Rev Time 0.00
Received By jwitmer Date 2005-11-14 Time 09:19 Sent To  
Notes
2005-11-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:05070224
 ADD: 250 S AUSTRALIAN AV# 600
 CONT: SHAKMAN
 TEL: (561)750-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)COMMENT# 3FROM THE PREVIOUS REVIEW:
 EVEN THOUGH THIS AREA IS NOT NEW WORK
 SEE 20% DISPROPORTIONATE COST.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 OFFICE 604 & 605 MISSING THE 18"
 REQUIRED ON THE PULL SIDE,11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 2) NEW WORK OFFICE# 623 IS STILL MISSING
 THE REQUIRED CLEAR SPACE AT THE LATCH
 SIDE OF DOOR WHEN THE DOOR IS PULLED
 TOWARD YOU. SEE 11-4.13.6
  
 3) COMMENT# 5 FROM THE PEVIOUS REVIEW
 DEALS WITH WOOD BACKING IN WALLS.SHEET
 A-9 INDICATES WOOD BACKING IN
 WALLS AND SUB-BUCKS.609.2.1 TYPE I AND
 TYPE II CONSTRUCTION. PARTITIONS SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE
 MATERIALS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2005-08-07 Time 17:14 Sent To P
Notes
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT:05070224
 ADD: 250 S AUSTRALIAN AV# 600
 CONT: SHAKMAN
 TEL: (561)750-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 MISSING THE CERTIFICATE OF AUTHERIZATION
 NUMBER ON PLAN, FAC 61G1-16,004 FL SS
 481.219.
  
 3) OFFICE 604 & 605 MISSING THE 18"
 REQUIRED ON THE PULL SIDE,11-4.13.6
 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4) SHEET A-3 MISSING EXIT LIGHTS AND
 DIRECTIONALS.1016.1.1 ILLUMINATION OF
 MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY
 BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS, RAMPS, ESCALATORS,
 WALKWAYS AND EXIT PASSAGEWAYS LEADING
 TO A PUBLIC WAY.
  
 5) SHEET A-9 INDICATES WOOD BACKING IN
 WALS AND SUB-BUCKS.609.2.1 TYPE I AND
 TYPE II CONSTRUCTION. PARTITIONS SHALL
 BE CONSTRUCTED OF NONCOMBUSTIBLE
 MATERIALS.
  
 6) SHEET A-3 INDICATES THE USE OF
 SIDELIGHTS FOR VARIOUS OFFICES BUT NO
 MENTION OF SIDELIGHT.2405.2 HAZARDOUS
 LOCATIONS.GLAZING IN AN INDIVIDUAL FIXED
 OR OPERABLE PANEL ADJACENT TO A DOOR
 WHERE THE NEAREST VERTICAL EDGE IS
 WITHIN A 24-INCH (610 MM) RADIUS OF THE
 DOOR IN A CLOSED POSITION AND WHOSE
 BOTTOM EDGE IS LESS THAN 60 INCHES (1524
 MM) ABOVE THE FLOOR OR WALKING SURFACE.
  
 7) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-05-03 Cont ID  
Sent By dpalmer Date 2006-05-03 Time 07:57 Rev Time 0.00
Received By dpalmer Date 2006-05-03 Time 07:43 Sent To FIRE
Notes
2006-05-03 00:00:00REVISED
 1.1,1.2,2.0

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-27 Time 20:12 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 19:58 Sent To  
Notes
2005-12-27 00:00:00PLEASE KNOWTHE NOC WHICH WAS SUBMITTED
 BACK WITH PLANS IS VOID AS IT HAS
 EXPIRED SINCE THE RECORDING OF 7/22/05
 PER FS 713.13(2). DVPALMER.
 PLEASE KNOW THIS NOC JUST NEEDS TO BE
 RE-RECORDED BEFORE PICKING UP PERMIT.
 PER FS713.13(2), IF WORK HAS NOT
 COMMENCED WITHIN 90 DAYS OF SUCH
 RECORDING OF NOC, THEN THE NOC BECOMES
 VOID.
  
  
 ELECTRICAL PLANS STAMPED FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 23:05 Rev Time 0.25
Received By dpalmer Date 2005-09-10 Time 22:58 Sent To  
Notes
2005-09-10 00:00:00*********UNSAT ***********
  
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 WAS NOT SUBMITTED BACK WITH PLANS, AND
 MUST BE TURNED IN ASAP.
  
 2)NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 WITH ALL SHEETS SIGNED DATED AND
 SEALED BY THE ENGINEER OF RECORD.
 PLEASE SEE ONE SET FOR ELECTRICAL SHEETS
 ARE OK, HOWEVER 2ND SET IS NOT COMPLETED
 FOR THIS. PLEASE ALSO SEE MISSING SIGNED
 AND SEALED MECHANICAL SHEETS. FS
 471.025, FAC 61G15-23.002
  
 3)NOTE: PLEASE ALSO SEE IT WAS REQUESTED
 ON THE PREVIOUS REVIEW TO "REMOVE" ALL"
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 PLEASE SEE ONE SET STILL CONTAINS ALL
 THE OLD/VOIDED SHEETS WHICH SHOULD BE
 REMOVED.
 PLEASE SEE THE OLD/VOIDED SHEETS SHOULD
 BE PLACED BY THEMSELVES IN ONE SET AND
 SUBMITTED WITH THE OTHER TWO FULL SETS
 FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 18:01 Rev Time 1.00
Received By dpalmer Date 2005-07-15 Time 18:01 Sent To  
Notes
2005-07-15 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE ONY ONE SET OF PLANS
 FOR MP'S WERE SIGNED, DATED AND
 SEALED.
 PLEASE SEE FS 471.025
 THIS IS REQUIRED OF ALL TRADES AND FOR
 ALL SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE BLDG REVIEW NOTES FOR
 ARCHITECT'S TITLE BLOCK MISSING
 INFORMATION AS REQUIRED UNDER FAC
 61G1-16.004, FS 481.219
 REQUIRED WHEATHER OR NOT COMMENT IS MADE
 BY BLDG REVIEW.
  
 3)NOTE: PLEASE SEE 2002 NEC FOR BRANCH
 CIRCUITS IN KITCHENS WHICH REQUIRES ALL
 15- AND 20-AMPERE, 125-VOLT RECEPTACLES
 IN NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 4)NOTE: PLEASE SEE EM/EXT LIGHTING
 CIRCUITS ARE NOTED AS BEING WIRED INTO
 AN EM PANEL?? PLEASE CLARIFY THIS AS IT
 SEEM EM BACK-UP GEN IS HAS BEEN REMOVED.
 PLEASE ALSO SEE CIRCUITING SEEMS TO
 NOTED TO A PANEL "?". PLEASE SEE DUE TO
 CIRCUITING NOT BEING SHOWN, IT IS
 UNCLEAR IF PANELS SUBMITTED CONTAIN
 CIRCUITS?
 PLEASE CLARIFY FIXTURE TYPE "B" FOR
 BATTERY BACK UP?
 IT APPEARS EXT LTS ARE BATTERY BACK-UP.
 PLEASE CLARIFY IF THESE FIXTURES WILL
 NOW BECOME BATTERY BACK. PLEASE ALSO SEE
 LS 101 7-9 FOR CIRCUITING.
 700.12E,700.16 ETC.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 PLEASE SEE CONTROL WIRING FOR ATS SHALL
 ALSO BE REMOVED. PLEASE NOTE THIS ON
 PLANS.
 ***************************************
 PLEASE KNOW A GENERATOR WILL NOT BE
 PERMITTED ON ROOF, EVEN IF THERE WAS ONE
 THERE PREVIOUSLY. THIS IS ONLY A NOTE:
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHERREVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 **************************************
 PLEASE BE SURE TO REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 POSSIBLE STAMPING. ONE COPY OF
 OLD/VOIDED SHEETS SHALL BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-05-22 Cont ID  
Sent By nmccray Date 2006-05-22 Time 15:37 Rev Time 0.00
Received By nmccray Date 2006-05-22 Time 15:37 Sent To  
Notes
2006-05-22 00:00:00REVISION DATED 04-20-06
 E1.1, E1.2, & E2.0

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By mwennerg Date 2005-09-22 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2005-09-22 Time 14:29 Sent To  
Notes
2005-09-22 00:00:00******OK******
  
 IN ACCORDANCE WITH LOCAL REQUIREMENTS,
 NEW DUCT SMOKE DETECTORS WHERE PROVIDED,
 SHALL BE WIRED TO CAUSE A GENERAL FIRE
 ALARM CONDITION IF COMPATABLE WITH
 EXISTING FIRE ALARM SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-05 Cont ID  
Sent By mwennerg Date 2005-08-05 Time 13:30 Rev Time 0.00
Received By mwennerg Date 2005-08-05 Time 13:30 Sent To  
Notes
2005-08-05 00:00:00******DENIED******
  
 1) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR CEILINGS AND WALLS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHER
 SHALL BE MOUNTED TO SATISFY THE 75'
 TRAVEL DISTANCE.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FIR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 14:16 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 14:16 Sent To M
Notes
2006-05-06 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 12:46 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 12:46 Sent To E
Notes
2006-05-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-29 Cont ID  
Sent By adarroug Date 2006-04-29 Time 15:50 Rev Time 0.00
Received By adarroug Date 2006-04-29 Time 15:49 Sent To M
Notes
2006-04-29 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-26 Cont ID  
Sent By adarroug Date 2006-04-26 Time 12:43 Rev Time 0.00
Received By adarroug Date 2006-04-26 Time 12:43 Sent To FIRE
Notes
2006-04-26 00:00:00TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-27 Cont ID  
Sent By adarroug Date 2006-02-27 Time 09:42 Rev Time 0.00
Received By adarroug Date 2006-02-27 Time 09:42 Sent To  
Notes
2006-02-27 00:00:00WAITING FOR "COMM" BD-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-01 Cont ID  
Sent By adarroug Date 2005-12-01 Time 17:00 Rev Time 0.00
Received By adarroug Date 2005-12-01 Time 17:00 Sent To  
Notes
2005-12-27 00:00:00TO "COMM" BD#32
2005-12-01 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-09 Cont ID  
Sent By adarroug Date 2005-09-09 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-09-09 Time 16:06 Sent To  
Notes
2005-09-09 00:00:00TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-08 Cont ID  
Sent By kstevens Date 2005-08-08 Time 08:25 Rev Time 0.00
Received By kstevens Date 2005-07-07 Time 16:38 Sent To  
Notes
2005-07-15 00:00:00IN COMM SPACE #42
2005-07-07 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-05-12 Cont ID  
Sent By tgordon Date 2006-05-12 Time 16:52 Rev Time 0.20
Received By tgordon Date 2006-05-12 Time 16:52 Sent To  
Notes
2006-05-12 00:00:00MECH. REV. PAGE M1.1.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-05-12 Cont ID  
Sent By tgordon Date 2006-05-12 Time 13:59 Rev Time 0.30
Received By tgordon Date 2006-05-12 Time 13:59 Sent To  
Notes
2006-05-12 00:00:00*** MECH. REVISION DENIED ***
 1) MECHANICAL REVISION HAS CHANGES MADE
 IN PEN ON A PHOTO-COPIED PLAN WITH AN
 ENGINEER'S SEAL ON THEM, CHANGES MAY NOT
 BE DONE IN PEN AS THE PLANS MAY BE
 ALTERED AT ANY TIME.
  
 2) THE ENGINEER DID NOT PUT THE DATE ON
 HIS SEAL, PER FAC 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-05-08 Cont ID  
Sent By tgordon Date 2006-05-08 Time 10:27 Rev Time 0.30
Received By tgordon Date 2006-05-08 Time 10:27 Sent To  
Notes
2006-05-08 00:00:00REVISION TO MECH. PLANS PAGE M 1.1 .

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-05-02 Cont ID  
Sent By tgordon Date 2006-05-02 Time 11:15 Rev Time 0.30
Received By tgordon Date 2006-05-02 Time 11:15 Sent To  
Notes
2006-05-02 00:00:00REVISION TO MECH. PLANS PAGE M1.0 &
 M1.1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-01-23 Cont ID  
Sent By pkrauss Date 2006-01-23 Time 10:14 Rev Time 0.00
Received By pkrauss Date 2006-01-23 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-10-15 Cont ID  
Sent By hmoser Date 2005-10-15 Time 10:09 Rev Time 0.00
Received By hmoser Date 2005-10-15 Time 09:02 Sent To  
Notes
2005-10-15 00:00:00PLAN DENIED
 IN REGARDS TO MECHANICAL NOTES
 #11.PLEASE REFER TO SECTION 602.2.1
 MATERIALS EXPOSED WITHIN PLENUMS.2001
 FBD(M).IF YOU HAVE COMBUSTIBLE MATERIALS
 IN THE PLENUM PLEASE REFER TO SECTION
 103.7 ALTERNATE MATERIALS AND
 METHODS.2001 FBC(M).
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By pkrauss Date 2005-07-27 Time 09:42 Rev Time 1.00
Received By pkrauss Date 2005-07-27 Time 09:02 Sent To  
Notes
2005-07-27 00:00:00DENIED:
 1.PLANS ARE TO BE SIGNED, SEALED AND
 DATED BY THE ENGINEER PER FS 471.025.
  
 2.PLAN SHEET M0.1 MECHANICAL NOTE #10
 STATES "CONDENSATE SHALL BE SCHEDULE 40
 PVC OR COPPER IF LOCATED IN A RETURN AIR
 PLENUM".PLAN SHEET M 1.1, INDICATES
 RETURN AIR PLENUM THEREFORE PVC WILL NOT
 BE ALLOWED.
  
 3.PLEASE INDICATE IF THE OUTSIDE AIR
 WILL BE REQUIRED TO BE CHANGED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-03-09 Cont ID  
Sent By kstevens Date 2006-03-09 Time 07:45 Rev Time 0.00
Received By kstevens Date 2006-03-09 Time 07:45 Sent To  
Notes
2006-03-09 00:00:00PASSED/PROVISO
  
 SINK TRAP SHALL NOT EXCEED 8' FROM
 EXISING VENT. - NO DEAD ENDS

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-01-21 Cont ID  
Sent By pschmitz Date 2006-01-21 Time 07:30 Rev Time 0.00
Received By pschmitz Date 2006-01-21 Time 07:29 Sent To  
Notes
2006-01-21 00:00:00PAUL SCHMITZ
 FBC 2001 PLUMBING CODE PLAN REVIEW
 FBC 2001 CH 11, FL ACESSIBILITY CODE
 DENIED 3RD TIME
  
 1)SHT A-1 DEMOLITION PLAN NOTES.
 ?P704.5 DEAD ENDS. IN THE INSTALLATION
 OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED.
 2. SHT A-1A SHOWS A KITCHEN SINK.
 THE SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL, SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS, TO THIS COMMENT.
 FORWARD APPROACH REQUIRED WITH NO
 CABINET DOORS ALLOWDED.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BEPROVIDED
 UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.( NO GARBAGE DISPOSAL)
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 11-4.22.2 DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR A FIXTURE
 3. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM IN ISOMETRIC FORM. SHOW ALL PIPE
 SIZES, TRAP, VENT/SANT CONNECTIONS FOR
 THE SANT. AND SHOW ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS, (IF
 REQUIRED BY SECTION 604.9), AND POINT OF
 CONNECTION. SECTION 104.3.1.1. - NO
 RESPONSE TO COMMENT.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-11-12 Cont ID  
Sent By kstevens Date 2005-11-12 Time 12:25 Rev Time 0.45
Received By kstevens Date 2005-11-12 Time 12:25 Sent To  
Notes
2005-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. BOTH SETS OF MECHINCAL AND ELECTRICAL
 SHEETS SHALL BE SIGNED, SEALED, AND
 DATED PER FAC 61G15-23.002(1) & FS
 471.2055. - STILL SHEET NOT SIGNED,
 SEALED, DATED
 2. SHT A-1 SHOWS A KITCHEN SINK, AND
 SINCE THERE IS NO DEMO SHEET, EXISTING
 FLOOR PLAN, OR NOT INDICATED AS AN
 EXISTING SINK, THE SINK SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS. - NO RESPONSE NOTED
 TO THIS COMMENT. - FORWARD APPROACH
 REQUIRED WITH NO CABINET DOORS ALLOWDED.
 ALSO DOOR CAN NOT SWING INTO CLEAR FLOOR
 SPACE OF ANY FIXTURE.
 3. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM IN ISOMETRIC FORM. SHOW ALL PIPE
 SIZES, TRAP, VENT/SANT CONNECTIONS FOR
 THE SANT. AND SHOW ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS, (IF
 REQUIRED BY SECTION 604.9), AND POINT OF
 CONNECTION. SECTION 104.3.1.1. - NO
 RESPONSE TO COMMENT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By kstevens Date 2005-08-08 Time 08:25 Rev Time 0.62
Received By kstevens Date 2005-08-06 Time 15:23 Sent To  
Notes
2005-08-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS: PER FAC
 61G1-16.004(2) & FS 481.219 THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET.
 2. BOTH SETS OF MECHINCAL AND ELECTRICAL
 SHEETS SHALL BE SIGNED, SEALED, AND
 DATED PER FAC 61G15-23.002(1) & FS
 471.2055.
 3. SHT A-1 SHOWS A KITCHEN SINK, AND
 SINCE THERE IS NO DEMO SHEET, EXISTING
 FLOOR PLAN, OR NOT INDICATED AS AN
 EXISTING SINK, THE SINK SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 4. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM IN ISOMETRIC FORM. SHOW ALL PIPE
 SIZES, TRAP, VENT/SANT CONNECTIONS FOR
 THE SANT. AND SHOW ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS, (IF
 REQUIRED BY SECTION 604.9), AND POINT OF
 CONNECTION. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]