Plan Review Details - Permit 05070203
Plan Review Stops For Permit 05070203
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-10 Cont ID  
Sent By mjacobs Date 2005-08-10 Time 11:44 Rev Time 1.50
Received By mjacobs Date 2005-08-10 Time 11:27 Sent To PC
Notes
2005-08-10 00:00:00****CORRECTIONS****
  
 MYRON JACOBS, BUILDING PLANS EXAMINER
 561-805-6726 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC*CITY OF WESTPALM BEACH
 AMENDMENTS. TO THE FBC2001
  
 BLDG: PROVISO.
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-15 Cont ID  
Sent By btrobaug Date 2005-09-15 Time 11:33 Rev Time 0.50
Received By btrobaug Date 2005-09-15 Time 11:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-29 Cont ID  
Sent By btrobaug Date 2005-07-29 Time 12:11 Rev Time 0.50
Received By btrobaug Date 2005-07-29 Time 11:16 Sent To M
Notes
2005-07-29 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE VERIFY THE TRANSFER SWITCH
 RATING OF 600 AMPS FOR A 136 AMP LOAD.
  
 2} THE TRANSFER SWITCH MUST BE SERVICE
 RATED PER 225.36. PLEASE INDICATE SAME.
  
 3} THE RISER DOES NOT SHOW HOW THE
 CIRCUITS WILL BE LIMITED TO THE
 CALCULATIONS INDICATED.THE ATS APPEARS
 TO FEED ALL 4 HOUSE PANELS.
  
 4} A DEMAND FACTOR MAY BE TAKEN ON THE
 LIGHTING CIRCUITS ONLY. THE REST OF THE
 INTENDED LOAD MUST BE AT 100%. SEE
 702.5.
  
 5} THE DESIGNER OF RECORD MUST SIGN AND
 SEAL THE PLAN. SEE 61G15-23.002 FAC.,471
 .025 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 14:15 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 14:15 Sent To E
Notes
2005-09-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 09:32 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 09:32 Sent To E
Notes
2005-07-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 14:10 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 15:36 Sent To  
Notes
2005-07-07 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-01 Cont ID  
Sent By prafter Date 2005-08-01 Time 09:56 Rev Time 1.00
Received By prafter Date 2005-08-01 Time 09:56 Sent To P
Notes
2005-08-01 00:00:00MECH. PLAN REVIEW:
  
 MECH. PROVISO:
  
 IF ELECT. GENERATOR IS 10 FEET FROM
 BUILDING AND EXHAUST IS DIRICTED AWAY
 FROM BUILDING, THIS MEET INTENT OF MECH.
 CODE.
 2001 FBC/M 804.3.3 TERMINATION.
  
 2001 FBC/M SECTION 915
 REQUIREMENT OF NFPA 37 8.2.3.2
 EXHAUST SYSTEM TERMINATION.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By jleech Date 2005-08-01 Time 15:15 Rev Time 0.25
Received By jleech Date 2005-08-01 Time 15:15 Sent To B
Notes
2005-08-01 00:00:00GAS PERMIT REQUIRED BEFORE FINAL RES-GEN
 INSPECTION.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-15 Cont ID  
Sent By mmclean Date 2005-07-15 Time 13:55 Rev Time 0.00
Received By mmclean Date 2005-07-15 Time 13:55 Sent To I
Notes
***NONE***