Plan Review Details - Permit 05070175
Plan Review Stops For Permit 05070175
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-05 Cont ID  
Sent By jwitmer Date 2005-08-05 Time 07:03 Rev Time 0.33
Received By jwitmer Date 2005-08-05 Time 06:59 Sent To PC
Notes
2005-08-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070175
 ADD: 720 BISCAYNE DR
 CONT: BLUE FIN BUILDERS
 TEL: (561)736-7615
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION:BUILDING PROVISO
  
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE
 PROVIDED WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH
 424.2.17.1.14.
  
  
 2)13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 EXCEPTION: OUTDOOR POOLS DERIVING OVER
 70 PERCENT OF THE ENERGY FOR HEATING
 FROM NON-DEPLETABLE ON SITE-RECOVERED
 SOURCES COMPUTED OVER AN OPERATING
 SEASON ARE EXEMPT FROM THIS
 REQUIREMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-28 Cont ID  
Sent By dpalmer Date 2005-09-28 Time 16:06 Rev Time 1.00
Received By dpalmer Date 2005-09-28 Time 16:05 Sent To  
Notes
2005-09-28 00:00:00REDLINED,
  
 OCP AND AWG FROM ELECTRICLA CONTRACTOR
 TO CORRELATE WITH ENGINEER'S PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-09-23 Cont ID  
Sent By dpalmer Date 2005-09-23 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2005-09-23 Time 12:50 Sent To  
Notes
2005-09-23 00:00:00*** CALLED POOL CONT , WAITING FORNEW
 LOADS CALCS TO MEET CODE.
 PLANS WILL BE PLACED OUTFRONT.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 17:44 Rev Time 0.00
Received By dpalmer Date 2005-09-02 Time 17:44 Sent To  
Notes
2005-09-02 00:00:00************ UNSAT 2ND REVIEW ********
  
 1)NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW BY MR. BILL TROBAUGH.
 PLEASE INDICATE OCP FEEDING NEW PANEL.
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR PER 250.110,250.122
  
 2)NOTE: PLEASE SEE HAND DRAWN LOAD CALCS
 AND RISER WAS SUBMITTED HOWEVER RISER
 DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE LOAD CALCULATIONS SUBMITTED
 ARE REQUIRED TO MEET NEC 220.31B,
 220.215.3,680.9
 PLEASE SEE A/C AND HEAT PUMP LOADS MAY
 NOT BE DE-RATED AT 40%???
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%, (HEAT PUMP, POOL PUMP)
 PLEASE SEE OTHER INFORMATION AS
 PREVIOUSLY REQUESTED CAN NOT BE VERIFIED
 AT THIS TIME.
 215.3,215.5,230.42, 680.9, 240.4,310.16
 ETC.
  
 3)NOTE: PLEASE SUBMIT MANUFACTURE
 CUT/SPEC SHEETS ON NEW PROPOSED HEAT
 PUMP. THIS MUST INDICATE THE LISTING
 FROM A NRTL. (NATIONALLY RECOGNIZED
 TESTING LAB.)
  
 4)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 THE DESIGN PROFESSIONAL AND PLANS WITH
 REPEAT CODE COMPLIANCE COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 5)NOTE: PLEASE SEE WHEN ADDITTIONAL
 PLANS FOR LOADS CALCS ETC IS SUBMITTED,
 MUST BE TWO COPIES AND EACH MUST CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS/DRAWINGS.
 FBC 104.2.1, CITY-WIDE ADMINISTRATIVE
 CODE.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By btrobaug Date 2005-07-20 Time 11:20 Rev Time 0.33
Received By btrobaug Date 2005-07-20 Time 10:47 Sent To P
Notes
2005-07-20 00:00:00 
 DENIED
 ~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAIN
 SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-22 Cont ID  
Sent By adarroug Date 2005-09-22 Time 15:06 Rev Time 0.00
Received By adarroug Date 2005-09-22 Time 15:06 Sent To E
Notes
2005-09-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 14:13 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 14:13 Sent To E
Notes
2005-09-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-19 Cont ID  
Sent By adarroug Date 2005-07-19 Time 15:23 Rev Time 0.00
Received By adarroug Date 2005-07-19 Time 15:23 Sent To E
Notes
2005-07-19 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 13:55 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 13:55 Sent To Z
Notes
2005-07-07 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-25 Cont ID  
Sent By jleech Date 2005-07-25 Time 12:32 Rev Time 0.50
Received By jleech Date 2005-07-25 Time 12:32 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-18 Cont ID  
Sent By mmclean Date 2005-07-18 Time 16:35 Rev Time 0.00
Received By mmclean Date 2005-07-18 Time 16:35 Sent To I
Notes
***NONE***