Plan Review Details - Permit 05070171
Plan Review Stops For Permit 05070171
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-06-23 Cont ID  
Sent By jwitmer Date 2006-06-23 Time 15:05 Rev Time 0.33
Received By jwitmer Date 2006-06-23 Time 15:05 Sent To  
Notes
2006-06-23 00:00:002ND FLOOR LEVEL CHANGE TO STORAGE
 OCCUPANCY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-03-30 Cont ID  
Sent By jwitmer Date 2006-03-30 Time 15:07 Rev Time 1.11
Received By jwitmer Date 2006-03-30 Time 14:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-03-29 Cont ID  
Sent By jwitmer Date 2006-03-29 Time 16:24 Rev Time 0.55
Received By jwitmer Date 2006-03-29 Time 16:24 Sent To PC
Notes
2006-03-29 00:00:00SHOPR DRAWINGS STAIRS & HANDRAIL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-14 Cont ID  
Sent By jwitmer Date 2006-02-14 Time 07:22 Rev Time 0.77
Received By jwitmer Date 2006-02-14 Time 07:22 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-07 Cont ID  
Sent By jwitmer Date 2006-02-07 Time 12:29 Rev Time 0.55
Received By jwitmer Date 2006-02-07 Time 12:28 Sent To PC
Notes
2006-02-07 00:00:00PLANS ARE CODE COMPLIANT, NEEDS IMPACT
 FEE STAMP READY TO PRINTJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-16 Cont ID  
Sent By jwitmer Date 2005-11-14 Time 13:17 Rev Time 2.77
Received By jwitmer Date 2005-11-14 Time 13:12 Sent To  
Notes
2005-11-16 00:00:00PERMIT: 05070171
 ADD: 1335 OKEECHOBEE RD
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT # 3 FROM THE PREVIOUS REVIEW,
 SEE ATTACHED CODE COMMENTS IN
 REGUARDS TO CALCULATING AREA FOR
 MEZZANINES. PLANS ARE OVER 30% OF ROOM
 SIZE. I SPOKE WITH THE DESIGN
 PROFESSIONAL ABOUT THIS ISSUE OVER THE
 PHONE. HE ASSURED ME THAT THE MEZZANINE
 DID MEET THE 33 % REQUIREMENT.
 THE 33% CALCULATION IS TO BE THE ROOM
 OR SPACE IN WHICH THEY ARE LOCATED, SEE
 (503.2.3.2). THE LOADING AND STORAGE
 AREAS CAN NOT BE FIGURED INTO THE
 EQUATION., THESE ARE TWO SEPERATE ROOMS.
 WE ARE FIGURING THE AREA ON THE OTHER
 SIDE OF THIS COMMON WALL, AS THE SO
 CALLED MEZZANINE. THIS AREA DOES
 COMMUNICATE WITH ITSELF. SUBTRACT THE
 AREA OF OFFICE 504 & 507, THIS IS THE
 AREA THAT 33% CAN BE FIGURED AS A
 MEZANINE.
 THIS AREA IS TRUELY A SECOND STORY
 REQUIRING AN ENCLOSEDEGRESS TO THE
 EXTERIOR.1006.1.1 EXIT STAIRWAYS BETWEEN
 FLOORS SHALL BE ENCLOSED IN OR
 SEPARATED BY FIRE RESISTANT CONSTRUCTION
 IN ACCORDANCE WITH 705.2 & TABLE
 705.1.2.
  
 3) COMMENT# 4 FROM THE PEVIOUS REVIEW,
 CONTRACTOR HASN'T SUBMITTED THE REQUIRED
 STATE COVERSHEET WITH ASSOCIATED PRODUCT
 APPROVALS.
 PLANS INDICATE 4 NEW WINDOWS PROVIDE:
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) MAN DOOR
 C) OVERHEAD DOOR
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 15:31 Rev Time 0.66
Received By jwitmer Date 2005-08-07 Time 15:30 Sent To  
Notes
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070171
 ADD: 1335 OKEECHOBEE RD
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) S-1 SHEET NOT SIGNED BY ENGINEER,
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3) SEE ATTACHED CODE COMMENTS IN
 REGUARDS TO CALCULATING AREA FOR
 MEZZANINES. PLANS ARE OVER 30% OF ROOM
 SIZE. ALSO SEE ENCLOSED MEZANINES MEANS
 OF EGRESS IN ACCORDANCE WITH 1005.7.
  
 4) PLANS INDICATE 4 NEW WINDOWS PROVIDE:
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) MAN DOOR
 C) OVERHEAD DOOR
  
 5) PLANS DO NOT PROVIDE WHERE NEW
 OPENINGS WILL BE LINTELS, NEW COLUMNS
 ETC?
  
 6) MEZANINE LEVEL INDICATES THE USE OF A
 PRIVATE BATHROOM. 11-4.1.3(11) TOILET
 FACILITIES: IF TOILET ROOMS ARE
 PROVIDED, THEN ACH PUBLIC AND COMMON USE
 TOILET ROOM SHALL COMPLY WITH ?11-4.22.
 OTHER TOILET ROOMS PROVIDED FOR THE USE
 OF OCCUPANTS OF SPECIFIC SPACES (I.E., A
 PRIVATE TOILET ROOM FOR THE OCCUPANT OF
 A PRIVATE OFFICE) SHALL BE ADAPTABLE.
 IF BATHING ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE BATHROOM SHALL
 COMPLY WITH ?11-4.23.ACCESSIBLE TOILET
 ROOMS AND BATHING FACILITIES SHALL BE ON
 AN ACCESSIBLE ROUTE.
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THE
 MEZZANINE LEVEL INDICATES A DOOR 524 BUT
 DOES NOT DETAIL THE ROOMS?
  
 8) SHEET 10.1 SNACK TABLE WITH SINK 36"
 TALL, SEE 11-4.24.2 SINKS, HEIGHT. SINKS
 SHALL BE MOUNTED WITH THE COUNTER NO
 HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 9) STAIR HANDRAIL TO COMPLY WITH
 :11-4.9.4(2) IF HANDRAILS ARE NOT
 CONTINUOUS, THEY SHALL EXTEND AT LEAST
 12 INCHES (305 MM) BEYOND THE TOP RISER
 AND AT LEAST 12 INCHES(305 MM) PLUS
 THE WIDTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.AT THE TOP, THE EXTENSION SHALL
 BE PARALLEL WITH THE FLOOR OR GROUND
 SURFACE. AT THE BOTTOM, THE HANDRAIL
 SHALL CONTINUE TO SLOPE FOR A DISTANCE
 OF THE WIDTH OF ONE TREAD FROM THE
 BOTTOM RISER; THE REMAINDER OF THE
 EXTENSION SHALL BE HORIZONTAL (SEE
 FIGURE 11-19(C) AND FIGURE 11-19(D)).
 HANDRAIL EXTENSIONS SHALL COMPLY WITH
 ?11-4.4.
  
 10)1-4.9.2 TREADS AND RISERS. ON ANY
 GIVEN FLIGHT OF STAIRS, ALL STEPS SHALL
 HAVE UNIFORM RISER HEIGHTS AND UNIFORM
 TREAD WIDTHS.STAIR TREADS SHALL BE NO
 LESS THAN 11 INCHES (280 MM) WIDE,
 MEASURED FROM RISER TO RISER (SEE FIGURE
 11-18(A)). OPEN RISERS ARE NOT
 PERMITTED.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-08-21 Cont ID  
Sent By dpalmer Date 2007-08-21 Time 12:45 Rev Time 0.00
Received By dpalmer Date 2007-08-21 Time 12:45 Sent To PC
Notes
2007-08-21 12:48:59REV FOR ELECTRIC ONLY. MECH AND PLUMB SHOWN ON SHEETS
 WERE CROSSED OUT AND REDLINED NOT REVIEWED OR REVISED.
 SHEETS FOR ELEC ONLY.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-08-06 Cont ID  
Sent By dpalmer Date 2007-08-06 Time 15:38 Rev Time 0.00
Received By dpalmer Date 2007-08-06 Time 15:38 Sent To  
Notes
2007-08-06 15:38:26** DENIED **
  
  
 1) NOTE: PLEASE SEE THE REVISED PLANS SUBMITTED NEED TO
 CONTAIN THE REVISED AS IMPLIED ON THE REVISION COVER
 SHEET AS FILED BY CONTRACTOR.
 PLEASE SEE THIS SHEET MENTIONS REVISED THE LIGHTING AND
 NUMBER OF FIXTURES YET NO INFORMATION COULD BE LOCATED
 FOR REVISED LOADS PER CHAPTER 13. 103.101, 13-415.2
 PLEASE BE SURE TO REVISE ENERGY CALCULATIONS FOR
 INCREASED LIGHTING.
  
 2) NOTE: PLEASE REVISE PANEL SCHEDULE TO INDICATE ALL
 CIRCUITS TO THE SPECIFIC AREAS/ROOMS IN WHICH THEY
 FEED. PLEASE SEE THE USE OF *LIGHTING* OR *RECEPTACLES*
 IS NOT ACCEPTABLE PER 408.4.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-17 Cont ID  
Sent By dpalmer Date 2006-08-17 Time 12:22 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 12:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 16:23 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 15:57 Sent To  
Notes
2006-08-06 00:00:00** UNSAT **
  
  
 ** PLEASE SEE ELECTRICAL PLANS ARE OK
 AND STAMPED, HOWEVER SHALL REMAIN IN "F"
 STATUS UNTIL SUCH TIME A STATEMENT WHICH
 HAS BEEN "TAPED" TO COVER SHEET CAN BE
 VERIFIED HOW AND WHEN ITBECAME "TAPED
 TO PLANS WHICH ARE SIGNED, DATED AND
 SEALED BY THE ARCHITECT.
 PLEASE ALSO SEE THE CONDO AGREEMENT
 WHICH IS ON SAID PLANS IS NOT PROPERLY
 NOTARIZED UNDER FS 117.05. PLEASE KNOW,
 BY STAMPING THE "RUBBER STAMP" ON PLANS
 WITH A SIGNATURE DOES NOT MAKE THE
 STATEMENT OR PAPERWORK A LEGAL DOCUMENT.
  
  
 ** AN E-MAIL HAS BEEN SENT TO MR. ERIC
 SCHNEIDER FOR VERIFICATION. IN EITHER
 CASE IF THE STATEMENT IS REQUIRED TO BE
 NOTORIZED THEN THIS SHALL BE REDONE OR
 PROPERLY CORRECTD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 19:21 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 19:07 Sent To  
Notes
2006-06-23 00:00:00**** UNSAT ***
  
 1) NOTE: PLEASE SEE ELECTRICAL SHEETS
 ARE SIGNED, DATED OR SEALED BY THE
 RESPONSIBLE DESIGNER OF RECORD FROM
 "CHANE ENGINEERING".
 FS 471.025
  
 2) NOTE: PLEASE SEE PREVIOUS PLANS WERE
 REDLINED WITH RESPECT TO THE MIN FT
 CANDLES REQUIRED PER 2003 NFPA-101
 7.8.1.3.
 PLEASE SEE MIN REQUIRED UNDER EM PER
 7.9.2.2
 ** PLEASE SEE STAIRS AS SHOWN MAY NOT
 APPEAR TO MEET THIS REQUIREMENT , PLEASE
 VERIFY AND NOTE ACCORDINGLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-24 Cont ID  
Sent By dpalmer Date 2006-01-24 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2006-01-24 Time 13:48 Sent To  
Notes
2006-01-24 00:00:00*********** NOTES REDLINED ***********
  
  
  
 1)NOTE: PLEASE SEE STAIRWAY IS REQUIRED
 TO HAVE A BATTERY BACK UP LIGHT FIXTURE
 AS REQUIRED UNDER LS 101 7.8,7.9.2.1
  
 ** PLEASE SEE A MIN OF 10FT CANDLES(108
 LUX)IS REQUIRED UNDER NORMAL POWER AND
 1FT CANDLE (10.8 LUX) UNDER
 EM.7.9.2.2,7.8.1.3
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-05 Cont ID  
Sent By dpalmer Date 2005-10-05 Time 16:54 Rev Time 0.30
Received By dpalmer Date 2005-10-05 Time 16:38 Sent To  
Notes
2005-10-05 00:00:00****UNSAT ****
  
  
 1)NOTE: PLEASE SEE SHEET 9.1 IS NOT
 SIGNED, DATED AND SEALED BY THE ENGINEER
 RESPONSIBLE FOR THE DESIGN AND LISTED ON
 THE TITLE BLOCK.
 PLEASE SEE FS 471.025
 TO HELP IN EXPEDITING PROCESS AND PLANS,
 PLEASE HAVE ENGINEER OF RECORD CALL. TO
 SET UP A TIME TO COME IN AND SIGN, DATE
 AND SEAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By dpalmer Date 2005-07-12 Time 07:22 Rev Time 0.40
Received By dpalmer Date 2005-07-12 Time 07:19 Sent To  
Notes
2005-07-12 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE 310.16,240.4 FOR MIN
 SIZING FOR FEEDERS FROM 200A MAIN
 DISCONNECT TO INSIDE PANEL "A". PLEASE
 SEE MAIN IS SHOWN W/ 200A OCP ON
 CONDUCTORS ONLY RATED FOR 150A'S.
  
 2)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS. THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 3)NOTE: PLEASE SEE THE ENGINEER AS SHOWN
 ON TITLE BLOCK RESPONSIBLE FOR DESIGN
 AND/OR PLANS, SHALL SIGN, DATE AND SEAL
 PLANS AS REQUIRED UNDER FS 471.025
 PLEASE SEE THIS IS REQUIRED OF ALL SAID
 SHEETS WHEATHER OR NOT COMMENT IS MADE
 BY OTHER TRADES.
  
 PLEASE BE SURE TO REMOVE ANY OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF OLD SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESTITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-06-29 Cont ID  
Sent By mwennerg Date 2006-06-29 Time 16:01 Rev Time 0.00
Received By mwennerg Date 2006-06-29 Time 16:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-01-24 Cont ID  
Sent By mcarsill Date 2006-01-24 Time 12:00 Rev Time 0.00
Received By mcarsill Date 2006-01-24 Time 12:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-10-06 Cont ID  
Sent By mwennerg Date 2005-10-06 Time 16:01 Rev Time 0.00
Received By mwennerg Date 2005-10-06 Time 16:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By mwennerg Date 2005-08-03 Time 15:42 Rev Time 0.00
Received By mwennerg Date 2005-08-03 Time 15:42 Sent To  
Notes
2005-08-03 00:00:00******DENIED******
  
 1) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND GUARDS.
  
 2) WHAT CONTENTS ARE PLANNED FOR STORAGE
 AREAS?
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 14:28 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 14:28 Sent To  
Notes
2007-08-01 14:12:19TO "COMM" BD#46
2007-07-24 14:28:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 14:19 Sent To  
Notes
2006-08-05 00:00:00TO COMM BOARD #24

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 13:47 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 14:00 Sent To  
Notes
2006-07-12 00:00:00WAITING FOR "COMM" BD-REV/NEW MECH AND
 PLUMB SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-12 Cont ID  
Sent By adarroug Date 2006-06-12 Time 16:36 Rev Time 0.00
Received By adarroug Date 2006-06-12 Time 16:36 Sent To  
Notes
2006-06-23 00:00:00TO "COMM" BD#35
2006-06-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 14:38 Sent To B
Notes
2006-03-24 00:00:00TO JW'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 11:58 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 11:58 Sent To B
Notes
2006-03-02 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-22 Cont ID  
Sent By adarroug Date 2005-12-22 Time 11:50 Rev Time 0.00
Received By adarroug Date 2005-12-22 Time 11:50 Sent To  
Notes
2006-01-24 00:00:00TO "COMM" BD#52
2005-12-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-03 Cont ID  
Sent By adarroug Date 2005-10-03 Time 15:42 Rev Time 0.00
Received By adarroug Date 2005-10-03 Time 15:41 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 18:32 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 18:32 Sent To  
Notes
2005-09-23 00:00:00TO "JWITMER" DESK/AS PER MASTER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-08 Cont ID  
Sent By kstevens Date 2005-08-08 Time 15:16 Rev Time 0.00
Received By kstevens Date 2005-07-07 Time 11:28 Sent To  
Notes
2005-07-07 00:00:00TO "COMM" BD#25

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-08-09 Cont ID  
Sent By hmoser Date 2007-08-09 Time 09:10 Rev Time 0.00
Received By hmoser Date 2007-08-09 Time 09:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 14:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-02 Cont ID  
Sent By pkrauss Date 2005-12-02 Time 07:55 Rev Time 0.40
Received By pkrauss Date 2005-12-02 Time 06:37 Sent To  
Notes
2005-12-02 00:00:00PROVISO:
 1.PLAN SHEET ME.2 GENERAL MECHANICAL
 NOTE #9 INDICATES OUTSIDE EQUIPMENT TO
 BE SECURED TO WITHSTAND 120 MPH WINDS.
 THIS SHOULD READ 140 MPH.
  
 2.PLEASE REVISE PLAN TO INDICATE
 LOCATION OF THE CONDENSING UNITS.
 SHOULD UNITS BE LOCATED ON THE ROOF,
 PLEASE SHOW COMPLIANCE WITH 2001 FBC
 1511.7 FOR PROPER CLEARANCE BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL OF THE STAND.IF UNITS ARE
 LOCATED AT GROUND LEVEL SHOW COMPLIANCE
 WITH 2001 FMC 301.13 FOR ANCHORING.
  
 PLEASEREVISE PLANS TO REFLECT THE
 ABOVE INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 16:43 Rev Time 0.40
Received By pkrauss Date 2005-07-26 Time 16:27 Sent To  
Notes
2005-07-26 00:00:00DENIED:
 1.PLAN SHEET ME-1 IT APPEARS THE
 EXISTING 6" OA DUCT IS TIED INTO AHU #2
 ONLY.THE OA CALCULATION GIVEN ON PLAN
 SHEET ME-2 ONLY GIVES OA CALCS FOR
 SYSTEM #1.PLEASE CLARIFY.
  
 2.PLEASE CLARIFY EXHAUAST FROM THE 1ST
 FLOOR UNISEX BATHROOM AS WELL AS THE 2ND
 FLOOR PRIVATE BATHROOM.
  
 3.PLEASE CLARIFY VENTILATION FROM THE
 1ST FLOOR STORAGE & LOADING AREAS.
  
 4.PLEASE NOTE, DUCTS PENETRATING THE
 RATED WALL FROM OFFICE #507 INTO OFFICE
 #501, THESE DUCTS WILL NOT REQUIRE FIRE
 DAMPERS AS LONG AS IT MEETS THE
 REQUIREMENTS OF 2001 FBC(M)607.1.3 ITEM
 #3 1 THROUGH 4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-08-09 Cont ID  
Sent By kstevens Date 2006-08-09 Time 08:58 Rev Time 0.00
Received By kstevens Date 2006-08-08 Time 13:50 Sent To  
Notes
2006-08-09 00:00:00REVISION OK - DELETED PRIVATE BATHROOM
 AND BREAK ROOM, AND ADDED A UNISEX
 TOILET ROOM. (RM. 509). NEW SANT. AND
 WATER RISER DIAGRAMS. SHT ME-1 AND SHT
 3.1 (FLOOR PLAN).

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-07-08 Cont ID  
Sent By pschmitz Date 2006-07-08 Time 13:44 Rev Time 0.00
Received By pschmitz Date 2006-07-08 Time 13:43 Sent To  
Notes
2006-07-08 00:00:00REVISION:
 MOVE 2ND FLR REST ROOM TO 1ST FLR ROOM
 #509.
 DELETE 2ND FLR BREAK ROOM SINK.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-04 Cont ID  
Sent By pschmitz Date 2006-02-04 Time 11:40 Rev Time 0.00
Received By pschmitz Date 2006-02-04 Time 11:40 Sent To  
Notes
2006-02-04 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2001
 FBC 2001 BUILDING CH 11
 PROVISO:
 1)?P607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH ?P607.3.1 AND ?P607.3.2.
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-11-26 Cont ID  
Sent By kstevens Date 2005-11-26 Time 15:22 Rev Time 0.65
Received By kstevens Date 2005-11-26 Time 15:22 Sent To  
Notes
2005-11-26 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 2. SINKS ON FIRST FOOR AND ON MEZZANINE
 LEVEL SHALL BE ACCESSIBLE. PLEASE SUBMIT
 A DETAIL FOR SINKS COMPLYING WITH THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT - MEZZANINE LEVEL
 SHOWS 3'6" HEIGHT.
 C. 11-4.24.4 SINK DEPTH - NOT ADDRESSED
 D. 11-4.24.5 CLEAR FLOOR SPACE. -
 FORWARD APPROACH REQUIRED AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. - NOT SHOWN ON MEZZANINE LEVEL.
 F. 11-4.24.7 FAUCETS. - NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By kstevens Date 2005-08-08 Time 15:17 Rev Time 0.00
Received By kstevens Date 2005-08-05 Time 13:47 Sent To  
Notes
2005-08-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT 3.1 MEZZANINE FLOOR PLAN. PRIVATE
 BATHROOM SHALL BE ADAPTABLE. INDICATE
 BACKING FOR ALL GRAB BARS FOR TOILET &
 SHOWER, 5' TURNING AREA. WATER CLOSET
 SHALL BE 18" FROM WALL TO CENTERLINE OF
 FIXTURE. (SEE SECTION 11-4.16.4).
 SECTION 11-4.1.3(11).
 2. SINKS ON FIRST FOOR AND ON MEZZANINE
 LEVEL SHALL BE ACCESSIBLE. PLEASE SUBMIT
 A DETAIL FOR SINKS COMPLYING WITH THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE. -
 FORWARD APPROACH REQUIRED AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS.
 3. SHT 10.1 DRINKING FOUNTAIN DETAIL,
 SHOW COMPLIANCE WITH 11-15.4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 4. SHTS ME.1 & ME.2 IF THE DESIGN
 PROFESSIONAL IS AN ENGINEER THEN HE/SHE
 SHALL AFFIX HIS/HER OFFICIAL SEAL TO
 SAID DRAWINGS AS REQUIRED BY FLORIDA
 STATUTES. SECTION 104.2.2.
 5. SHT ME.1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. THE SNACK SINK SHALL NOT CONNECT TO
 THE WET VENT FOR THE BATHROOM FIXTURES.
 THE SINK SHALL DISCHARGE DOWNSTREAM OF
 THE BATHROOM FIXTURES. SECTION 909.1.
 B. THE BATHROOM FIXTURES OF THE
 MEZZANINE SHALL NOT DRAIN PAST THE VENT
 FOR THE 1ST FLOOR FIXTURES. SECTION
 908.3.
 C. THE MEZZANINE LEVEL SINK IN THE OPEN
 OFFICE (521) IS NOT SHOWN ON THE SANT.
 RISER DIAGRAM. SECTION 104.2.1.
 D. MEZZANINE PIPING DOES NOT REFLECT
 THE FLOOR PLAN. RISER SHOWS THE LAV AND
 SHOWER ON THE SAME SIDE OF THE ROOM.
 SECTION 104.2.1.
 6. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By eschneid Date 2006-07-17 Time 17:04 Rev Time 0.00
Received By eschneid Date 2006-07-17 Time 17:04 Sent To  
Notes
2006-07-17 00:00:00APPROVED FOR STORAGE MEZZANINE.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-02-13 Cont ID  
Sent By eschneid Date 2006-02-13 Time 16:39 Rev Time 0.00
Received By eschneid Date 2006-02-13 Time 16:39 Sent To  
Notes
***NONE***