Plan Review Details - Permit 05070124
Plan Review Stops For Permit 05070124
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-01-31 Cont ID  
Sent By jwitmer Date 2006-01-31 Time 09:26 Rev Time 1.22
Received By jwitmer Date 2006-01-31 Time 09:26 Sent To  
Notes
2006-01-31 00:00:00 
 *** ISSUED PERMIT***
 REVISION # 2
 -PLAN REVIEW HISTORY-
  
 PERMIT# 05070124
 ADDRESS: 460 S ROSEMARY AV
 CONT: ANDERSON & MOORE
 TELL # (561)662-1819
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 BUILDING PROVISO;
  
 1)THE REVISION INDICATES A 4" DIFFERENCE
 IN FLOOR LEVEL FROM THE EXISTING FLOOR
 TO THE NEW PORTION WHERE WORK IS TO
 OCCUR. SEE CHANGES IN GRADE:
  
 11-4.5.2 CHANGES IN LEVEL. CHANGES IN
 LEVEL UP TO 1/4 IN. (6 MM) MAYBE
 VERTICAL AND WITHOUT EDGE TREATMENT (SEE
 FIGURE 11-7(C)).CHANGES IN
 LEVEL BETWEEN 1/4 IN. AND 1/2 IN. (6 MM
 AND 13 MM) SHALL BE BEVELED WITH A SLOPE
 NO GREATER THAN 1:2 (SEE FIGURE
 11-7(D)).CHANGES IN LEVELGREATER
 THAN 1/2 IN. (13 MM) SHALL BE
 ACCOMPLISHED BY MEANS OF A RAMP THAT
 COMPLIES WITH 11-4.7 OR 11-4.8.
  
 1003.2.7 CHANGES IN LEVEL IN MEANS OF
 EGRESS SHALL BE EITHER BY A RAMP OR A
 STAIR.THE PRESENCE AND LOCATION OF
 RAMPED WALKWAYS SHALL BE READILY
 APPARENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-13 Cont ID  
Sent By jwitmer Date 2005-10-13 Time 09:06 Rev Time 1.55
Received By jwitmer Date 2005-10-13 Time 09:06 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-14 Cont ID  
Sent By jwitmer Date 2005-09-14 Time 07:09 Rev Time 0.77
Received By jwitmer Date 2005-09-14 Time 07:09 Sent To  
Notes
2005-09-14 00:00:00PERMIT: 05070124
 ADD: 460 S ROSEMARY AV# 182
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT# 3 FROM THE PREVIOUS REVIEW,
 A-1 INDICATES THE REUSE OF STOREFRONT
 DOOR & SIDELIGHT.PROVIE PRODUCT APPROVAL
 INDICATING COMPLIANCE. DOES THIS DOOR
 AND SIDELIGHT ALSO HAVE LARGE MISSLE
 IMPACT TESTING INDICATE BY APPROVAL.IF
 THE EXISTING DOOR DOESN'T HAVE LARGE
 MISSLE IMPACT TESTING, STORM SHUTTERS
 WILL BE REQUIRED.
  
 3) COMMENT# 5 FROM THE PREVIOUS REVIEW,
 DEALS WITH PENETRATIONS THROUGH RATED
 WALLS. THE RESPONSE WAS TO SEE CHANE
 RESPONSE ME-1 NO NOTE MENTIONING:
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
 SUBMITTALS FOR PRODUCT APPROVALS BROUGHT
 IN AFTER REVIEW, WILL BE LOOKED AT AFTER
 PLANS ARE RESUBMITTED.10-04-05 JW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:38 Rev Time 0.55
Received By jwitmer Date 2005-08-07 Time 14:34 Sent To PC
Notes
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070124
 ADD: 460 S ROSEMARY AV# 182
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THERE
 SEEMS TO BE A DISCREPANCY AS TO THE
 SUITE NUMBER 180 VS 182. PLANS INDICATE
 180.
  
 3) A-1 INDICATES THE REUSE OF STOREFRONT
 DOR, BUT THERE IS A NEW SIDELIGHT NEXT
 TO THE DOOR REQUIRING PRODUCT APPROVAL.
  
 THE OTHER ISSUE IS THE EXISTING DOOR
 LARGE MISSLE IMPACT RATED?
  
 4) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6)11-5.2 COUNTERS AND BARS.WHERE FOOD OR
 DRINK IS SERVED AT COUNTERS EXCEEDING 34
 IN. (865 MM) INHEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR
 STANDING AT THE COUNTER, A PORTION OF
 THE MAIN COUNTER WHICH IS 60 IN. (1525
 MM) IN LENGTH MINIMUM SHALL BE PROVIDED
 IN COMPLIANCE WITH ?11-4.32 OR SERVICE
 SHALL BE AVAILABLE AT ACCESSIBLE TABLES
 WITHIN THE SAME AREA.
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-30 Cont ID  
Sent By dpalmer Date 2006-01-30 Time 17:30 Rev Time 0.00
Received By dpalmer Date 2006-01-30 Time 17:30 Sent To B
Notes
2006-01-30 00:00:00REV, UPGRADED SERVICE, EXT LTS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-27 Cont ID  
Sent By dpalmer Date 2005-09-27 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2005-09-27 Time 11:36 Sent To  
Notes
2005-09-27 00:00:00ENGINEER CAME IN AND SIGNED AND SEALED
 PLANS.
  
 ELEC OK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 22:42 Rev Time 0.33
Received By dpalmer Date 2005-09-10 Time 22:32 Sent To  
Notes
2005-09-10 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS FROM
 ENGINEER OF RECORD ARE REQUIRED TO BE
 SIGNED,DATED AND SEALED AS REQUIRED
 UNDER FAC 61G15-23.002, FS 471.025
 PLEASE SEE ONE SET.
  
 2)NOTE: PLEASE SEE RESPONSE LTR MENTIONS
 A NOTE WAS ADDED TO PLANS WITH RESPECT
 TO GFI PROTECTION FOR ALL 15/20A 125V
 RECEPTS IN KITCHEN IN NON-DWELLING UNITS
 PER 2002 NEC 210.8B3, HOWEVER THIS NOTE
 COULD NOT BE LOCATED?
  
 3)NOTE: PLEASE SEE RESPONSE LTR FROM
 ARCHITECT MENTIONS TO SEE ENGINEER'S
 RESPONSE FOR REQUIRED EM / EXT LTS,
 HOWEVER ENGINEER'S RESPONCE LTR DOES NOT
 MENTION THIS. PLEASE ALSO SEE PLANS SEEM
 TO ONLY INDICATE NEW EXT LTS?
 PLEASE SEE FIRE REVIEW COMMENTS.
 NFPA-101 7.8, 7.9
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By dpalmer Date 2005-07-12 Time 19:05 Rev Time 1.00
Received By dpalmer Date 2005-07-12 Time 19:05 Sent To  
Notes
2005-07-12 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE PROVIDE KW RATINGS FOR
 EQUIPMENT ON PANEL SCHEDULES.
 PLEASE SHOW ALL TRACK LIGHTING AND ANY
 SHOW/WINDOW RECEPTS CIRCUITS PER
 220.12A&B.
 PLEASE DOUBLE CHECK ADDED AMERAGES
 SHOWN, "A" PHASE.
 215.5,220
  
 2)NOTE: PLEASE SEE 210.8B3 UNDER 2002
 NEC WHICH REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 3)NOTE: PLEASE SHOW ALL OTHER ELEC WHICH
 IS EXISTING? UNABLE TO VERIFY LOADS AS
 INDICATED AT THIS TIME.
 PLEASE SEE PANEL SEEMS TO BE GETTING
 VERY CLOSE TO EXCEEDING CAPACITY AND
 THERE MAY BE A POSSIBLE NEED FOR
 UPGRADING.
 ALL LOADS NEED TO VERIFIED AT THIS TIME.
 215.5
  
 4)NOTE: PLEASE SEE CIRCUITING FOR WHAT
 APPEARS TO BE A "WALK-IN COOLER". SHOWS
 N-2,4, HOWEVER PANEL SCHEDULE INDICATES
 THIS CIRCUIT AS CONVECTION OVEN?
  
 5)NOTE: PLEASE SEE PLANS INDICATE AN
 EXISTING WATER HEATER, HOWEVER THIS IS
 NOT ON PANEL SCHEDULE OR LOAD CALCS. IS
 THIS WH BEING REMOVED?
  
 6)NOTE: PLEASE MAKE NOTE OR REFERENCE TO
 NEW OR EXSITNG SHUNT-TRIPS FOR HOOD?
 NFPA-96
  
 7)NOTE: PLEASE VERIFY ALL KITCHEN
 EQUIPMENT WHICH MAY NOT BE
 THERMOSTATICALLY CONTROLLED. (SOUP
 WELLS)? IF NOT, PLEASE SEE CONTINUOUS
 LOADS AT 125% FOR 3OR MORE HRS. THIS IS
 ONLY A NOTE.
  
 8)NOTE: PLEASE SEE ARCH FIRM'S LICENSE
 NUMBER AS PRINTED ON PLANS DOES NOT SEEM
 TO CORRELATE WITH STATE DBPR SITE.
 PLEASE VERIFY AND INCLUDE LICENSE NUMBER
 AS REQUIRED. FAC 61G1-16.004.
 PLEASE SEE PRINT-OUT FROM STATE SHOWS
 OTHER FIRMS/NAMES. A COPY OF PRINT-OUT
 IS ATTACHED TO NOTES.
 THIS IS NOTED FOR ARCHITECTUAL FIRM ONLY
 AND NOT FOR ENGINEERING FIRM.
  
 9)NOTE: PLEASE SEE SOME EQUIPMENT ON
 PLANS NOT CIRCUITED AND/OR NOTED ON
 PANEL SCHEDULE."LO-BOYS"?
  
 10)NOTE: PLEASE SEE PLANS ARE DATED BY
 ENGINEER AS 10/5/05? MISPRINT? SHOULD
 READ 5/10/05?
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:34 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-01-31 Cont ID  
Sent By mwennerg Date 2006-01-31 Time 10:30 Rev Time 0.00
Received By mwennerg Date 2006-01-31 Time 10:30 Sent To  
Notes
2006-01-31 00:00:00REVISION DATED 1/17/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-10-07 Cont ID  
Sent By mwennerg Date 2005-10-07 Time 09:48 Rev Time 0.00
Received By mwennerg Date 2005-10-07 Time 09:48 Sent To  
Notes
2005-10-07 00:00:00PER TELEPHONE CONVERSATION WITH
 ARCHITECT, EQUIPMENT IN QUESTION IS
 EXISTING CONDITION AND SHALL BE SUBJECT
 TO FIELD INSPECTOR APPROVAL AT THE TIME
 OF INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 11:20 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 11:20 Sent To  
Notes
2005-09-14 00:00:00******DENIED******
  
 1) PLEASE SEE THAT LAST REVIEW ASKS FOR
 EXIT LIGHT AND EMERGENCY LIGHTING
 LOCATIONS. NO MENTION OF EMERGENCY
 LIGHTS WITH THIS RESPONSE.
  
 2) ARE EXIT LIGHTS PLACED IN MANNER THAT
 MAKES EXITING CLEAR AND NOT CONFUSING?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-05 Cont ID  
Sent By mwennerg Date 2005-08-05 Time 15:24 Rev Time 0.00
Received By mwennerg Date 2005-08-05 Time 15:24 Sent To  
Notes
2005-08-05 00:00:00******DENIED******
  
 1) PLEASE SHOW THE LOCATION OF NEW AND
 OR EXISTING ILLUMINATED EXIT SIGNS AND
 EMERGENCY LIGHTING FACILITIES ON PLANS.
  
 2) NO COOKING OF FOODS THAT PRODUCE
 GREASE LADEN VAPORS WITHOUT APPROVED
 HOOD/SUPPRESSION SYSTEMS. THIS IS ALSO
 ADDRESSED BY THE DIVISION OF HOTELS AND
 RESTAURANTS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE WITHIN THE
 SCOPE OF THIS PROJECT.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2006-01-30 Time 13:49 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 13:49 Sent To  
Notes
2006-01-30 00:00:00WAITING FOR "COMM" BD
 1/30/06-ROUTED TO "DPALMER" PER "RBROWN"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 11:30 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 11:30 Sent To B
Notes
2005-09-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 16:21 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 16:21 Sent To  
Notes
2005-09-06 00:00:00TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:34 Rev Time 0.00
Received By jwitmer Date 2005-07-06 Time 16:07 Sent To  
Notes
2005-07-06 00:00:00TO "COMM" BD#41

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-10-04 Cont ID  
Sent By pkrauss Date 2005-10-04 Time 07:51 Rev Time 0.30
Received By pkrauss Date 2005-10-03 Time 13:55 Sent To  
Notes
2005-10-04 00:00:00ADDITIONAL PERMIT REQUIRED FOR THE
 WALK-IN COOLER.PLEASE PROVIDE
 MANUFACTURER'S INSTALLATION DATA WITH
 MECHANICAL PERMIT APPLICATION.
  
 PLANS INDICATE NO A/C WORK REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 21:34 Rev Time 0.55
Received By pkrauss Date 2005-07-26 Time 21:13 Sent To  
Notes
2005-07-26 00:00:00DENIED:
 INSUFFICIENT INFORMATION, PLEASE PROVIDE
 THE FOLLOWING INFORMATION FOR REVIEW:
 1.PLAN SHEET ME1 INDICATES HEAT HOOD.
 PLEASE PROVIDE ELEVATION OF THE
 TERMINATION.PLEASE CLARIFY THE
 TERMIATION, I.E. PARKING AREA, SIDE
 WALK, ALLEY?PROVIDE DISTANCES TO
 PROPERTY LINES AND ADJACTENT BUILDINGS.
 PLEASE CLARIFY.
  
 2.PLEASE CLARIFY IF THE TERMINATION IS
 A PROTECTIVE OPENING.
  
 3.PROVIDE INFORMATION FOR MAKE-UP AIR.
  
 4.PROVIDE INFORMATION ON THE
 VENTILATION RECONFIGURATION AND EXISTING
 OR NEW FRESH AIR CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-05 Cont ID  
Sent By kstevens Date 2005-10-05 Time 15:48 Rev Time 0.30
Received By kstevens Date 2005-10-05 Time 15:48 Sent To  
Notes
2005-09-23 00:00:00NEW SHEET

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-08-05 Cont ID  
Sent By kstevens Date 2005-08-05 Time 17:34 Rev Time 0.75
Received By kstevens Date 2005-08-05 Time 17:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:34 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***