| Plan Review Stops For Permit 05070124 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-01-31 |
Time |
09:26 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2006-01-31 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | | | | *** ISSUED PERMIT*** | | | REVISION # 2 | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 05070124 | | | ADDRESS: 460 S ROSEMARY AV | | | CONT: ANDERSON & MOORE | | | TELL # (561)662-1819 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | | | BUILDING PROVISO; | | | | | | 1)THE REVISION INDICATES A 4" DIFFERENCE | | | IN FLOOR LEVEL FROM THE EXISTING FLOOR | | | TO THE NEW PORTION WHERE WORK IS TO | | | OCCUR. SEE CHANGES IN GRADE: | | | | | | 11-4.5.2 CHANGES IN LEVEL. CHANGES IN | | | LEVEL UP TO 1/4 IN. (6 MM) MAYBE | | | VERTICAL AND WITHOUT EDGE TREATMENT (SEE | | | FIGURE 11-7(C)).CHANGES IN | | | LEVEL BETWEEN 1/4 IN. AND 1/2 IN. (6 MM | | | AND 13 MM) SHALL BE BEVELED WITH A SLOPE | | | NO GREATER THAN 1:2 (SEE FIGURE | | | 11-7(D)).CHANGES IN LEVELGREATER | | | THAN 1/2 IN. (13 MM) SHALL BE | | | ACCOMPLISHED BY MEANS OF A RAMP THAT | | | COMPLIES WITH 11-4.7 OR 11-4.8. | | | | | | 1003.2.7 CHANGES IN LEVEL IN MEANS OF | | | EGRESS SHALL BE EITHER BY A RAMP OR A | | | STAIR.THE PRESENCE AND LOCATION OF | | | RAMPED WALKWAYS SHALL BE READILY | | | APPARENT. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-10-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-10-13 |
Time |
09:06 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2005-10-13 |
Time |
09:06 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-09-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-09-14 |
Time |
07:09 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2005-09-14 |
Time |
07:09 |
Sent To |
|
|
| Notes |
| 2005-09-14 00:00:00 | PERMIT: 05070124 | | | ADD: 460 S ROSEMARY AV# 182 | | | CONT: ANDERSON-MOORE | | | TEL: (561)662-1819 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT# 3 FROM THE PREVIOUS REVIEW, | | | A-1 INDICATES THE REUSE OF STOREFRONT | | | DOOR & SIDELIGHT.PROVIE PRODUCT APPROVAL | | | INDICATING COMPLIANCE. DOES THIS DOOR | | | AND SIDELIGHT ALSO HAVE LARGE MISSLE | | | IMPACT TESTING INDICATE BY APPROVAL.IF | | | THE EXISTING DOOR DOESN'T HAVE LARGE | | | MISSLE IMPACT TESTING, STORM SHUTTERS | | | WILL BE REQUIRED. | | | | | | 3) COMMENT# 5 FROM THE PREVIOUS REVIEW, | | | DEALS WITH PENETRATIONS THROUGH RATED | | | WALLS. THE RESPONSE WAS TO SEE CHANE | | | RESPONSE ME-1 NO NOTE MENTIONING: | | | 704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | SUBMITTALS FOR PRODUCT APPROVALS BROUGHT | | | IN AFTER REVIEW, WILL BE LOOKED AT AFTER | | | PLANS ARE RESUBMITTED.10-04-05 JW | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-07 |
Time |
14:38 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2005-08-07 |
Time |
14:34 |
Sent To |
PC |
|
| Notes |
| 2005-08-07 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05070124 | | | ADD: 460 S ROSEMARY AV# 182 | | | CONT: ANDERSON-MOORE | | | TEL: (561)662-1819 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, THERE | | | SEEMS TO BE A DISCREPANCY AS TO THE | | | SUITE NUMBER 180 VS 182. PLANS INDICATE | | | 180. | | | | | | 3) A-1 INDICATES THE REUSE OF STOREFRONT | | | DOR, BUT THERE IS A NEW SIDELIGHT NEXT | | | TO THE DOOR REQUIRING PRODUCT APPROVAL. | | | | | | THE OTHER ISSUE IS THE EXISTING DOOR | | | LARGE MISSLE IMPACT RATED? | | | | | | 4) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 6)11-5.2 COUNTERS AND BARS.WHERE FOOD OR | | | DRINK IS SERVED AT COUNTERS EXCEEDING 34 | | | IN. (865 MM) INHEIGHT FOR CONSUMPTION | | | BY CUSTOMERS SEATED ON STOOLS OR | | | STANDING AT THE COUNTER, A PORTION OF | | | THE MAIN COUNTER WHICH IS 60 IN. (1525 | | | MM) IN LENGTH MINIMUM SHALL BE PROVIDED | | | IN COMPLIANCE WITH ?11-4.32 OR SERVICE | | | SHALL BE AVAILABLE AT ACCESSIBLE TABLES | | | WITHIN THE SAME AREA. | | | | | | 7)BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-30 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-30 |
Time |
17:30 |
Sent To |
B |
|
| Notes |
| 2006-01-30 00:00:00 | REV, UPGRADED SERVICE, EXT LTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-27 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-09-27 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2005-09-27 00:00:00 | ENGINEER CAME IN AND SIGNED AND SEALED | | | PLANS. | | | | | | ELEC OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-10 |
Time |
22:42 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-09-10 |
Time |
22:32 |
Sent To |
|
|
| Notes |
| 2005-09-10 00:00:00 | ******* UNSAT ******** | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL PLANS FROM | | | ENGINEER OF RECORD ARE REQUIRED TO BE | | | SIGNED,DATED AND SEALED AS REQUIRED | | | UNDER FAC 61G15-23.002, FS 471.025 | | | PLEASE SEE ONE SET. | | | | | | 2)NOTE: PLEASE SEE RESPONSE LTR MENTIONS | | | A NOTE WAS ADDED TO PLANS WITH RESPECT | | | TO GFI PROTECTION FOR ALL 15/20A 125V | | | RECEPTS IN KITCHEN IN NON-DWELLING UNITS | | | PER 2002 NEC 210.8B3, HOWEVER THIS NOTE | | | COULD NOT BE LOCATED? | | | | | | 3)NOTE: PLEASE SEE RESPONSE LTR FROM | | | ARCHITECT MENTIONS TO SEE ENGINEER'S | | | RESPONSE FOR REQUIRED EM / EXT LTS, | | | HOWEVER ENGINEER'S RESPONCE LTR DOES NOT | | | MENTION THIS. PLEASE ALSO SEE PLANS SEEM | | | TO ONLY INDICATE NEW EXT LTS? | | | PLEASE SEE FIRE REVIEW COMMENTS. | | | NFPA-101 7.8, 7.9 | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM | | | SETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | PLEASE BE SURE TO SEE ANY POSSIBLE | | | COMMENTS FROM OTHER REVIEWER(S) WHICH | | | MAY AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-12 |
Time |
19:05 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-07-12 |
Time |
19:05 |
Sent To |
|
|
| Notes |
| 2005-07-12 00:00:00 | ******* UNSAT ******* | | | | | | 1)NOTE: PLEASE PROVIDE KW RATINGS FOR | | | EQUIPMENT ON PANEL SCHEDULES. | | | PLEASE SHOW ALL TRACK LIGHTING AND ANY | | | SHOW/WINDOW RECEPTS CIRCUITS PER | | | 220.12A&B. | | | PLEASE DOUBLE CHECK ADDED AMERAGES | | | SHOWN, "A" PHASE. | | | 215.5,220 | | | | | | 2)NOTE: PLEASE SEE 210.8B3 UNDER 2002 | | | NEC WHICH REQUIRES ALL 15- AND | | | 20-AMPERE, 125-VOLT RECEPTACLES IN | | | NONDWELLING-TYPE KITCHENS TO BE GFCI | | | PROTECTED. THIS REQUIREMENT APPLIES TO | | | EACH AND EVERY 15- AND 20-AMPERE, | | | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR | | | NOT THE RECEPTACLE SERVES COUNTERTOP | | | APPLIANCES. | | | | | | 3)NOTE: PLEASE SHOW ALL OTHER ELEC WHICH | | | IS EXISTING? UNABLE TO VERIFY LOADS AS | | | INDICATED AT THIS TIME. | | | PLEASE SEE PANEL SEEMS TO BE GETTING | | | VERY CLOSE TO EXCEEDING CAPACITY AND | | | THERE MAY BE A POSSIBLE NEED FOR | | | UPGRADING. | | | ALL LOADS NEED TO VERIFIED AT THIS TIME. | | | 215.5 | | | | | | 4)NOTE: PLEASE SEE CIRCUITING FOR WHAT | | | APPEARS TO BE A "WALK-IN COOLER". SHOWS | | | N-2,4, HOWEVER PANEL SCHEDULE INDICATES | | | THIS CIRCUIT AS CONVECTION OVEN? | | | | | | 5)NOTE: PLEASE SEE PLANS INDICATE AN | | | EXISTING WATER HEATER, HOWEVER THIS IS | | | NOT ON PANEL SCHEDULE OR LOAD CALCS. IS | | | THIS WH BEING REMOVED? | | | | | | 6)NOTE: PLEASE MAKE NOTE OR REFERENCE TO | | | NEW OR EXSITNG SHUNT-TRIPS FOR HOOD? | | | NFPA-96 | | | | | | 7)NOTE: PLEASE VERIFY ALL KITCHEN | | | EQUIPMENT WHICH MAY NOT BE | | | THERMOSTATICALLY CONTROLLED. (SOUP | | | WELLS)? IF NOT, PLEASE SEE CONTINUOUS | | | LOADS AT 125% FOR 3OR MORE HRS. THIS IS | | | ONLY A NOTE. | | | | | | 8)NOTE: PLEASE SEE ARCH FIRM'S LICENSE | | | NUMBER AS PRINTED ON PLANS DOES NOT SEEM | | | TO CORRELATE WITH STATE DBPR SITE. | | | PLEASE VERIFY AND INCLUDE LICENSE NUMBER | | | AS REQUIRED. FAC 61G1-16.004. | | | PLEASE SEE PRINT-OUT FROM STATE SHOWS | | | OTHER FIRMS/NAMES. A COPY OF PRINT-OUT | | | IS ATTACHED TO NOTES. | | | THIS IS NOTED FOR ARCHITECTUAL FIRM ONLY | | | AND NOT FOR ENGINEERING FIRM. | | | | | | 9)NOTE: PLEASE SEE SOME EQUIPMENT ON | | | PLANS NOT CIRCUITED AND/OR NOTED ON | | | PANEL SCHEDULE."LO-BOYS"? | | | | | | 10)NOTE: PLEASE SEE PLANS ARE DATED BY | | | ENGINEER AS 10/5/05? MISPRINT? SHOULD | | | READ 5/10/05? | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STMAPING. | | | ONE SET OF OLD/VOIDED SHEETS SHOULD BE | | | SUBMITTED FOR REFERENCE ONLY. | | | | | | PLEASE SEE OTHER COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2005-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-07 |
Time |
14:34 |
Rev Time |
|
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-01-31 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-01-31 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | REVISION DATED 1/17/06 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-10-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-10-07 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-10-07 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2005-10-07 00:00:00 | PER TELEPHONE CONVERSATION WITH | | | ARCHITECT, EQUIPMENT IN QUESTION IS | | | EXISTING CONDITION AND SHALL BE SUBJECT | | | TO FIELD INSPECTOR APPROVAL AT THE TIME | | | OF INSPECTION. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-09-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-14 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-14 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2005-09-14 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE THAT LAST REVIEW ASKS FOR | | | EXIT LIGHT AND EMERGENCY LIGHTING | | | LOCATIONS. NO MENTION OF EMERGENCY | | | LIGHTS WITH THIS RESPONSE. | | | | | | 2) ARE EXIT LIGHTS PLACED IN MANNER THAT | | | MAKES EXITING CLEAR AND NOT CONFUSING? | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-08-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-05 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-05 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2005-08-05 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SHOW THE LOCATION OF NEW AND | | | OR EXISTING ILLUMINATED EXIT SIGNS AND | | | EMERGENCY LIGHTING FACILITIES ON PLANS. | | | | | | 2) NO COOKING OF FOODS THAT PRODUCE | | | GREASE LADEN VAPORS WITHOUT APPROVED | | | HOOD/SUPPRESSION SYSTEMS. THIS IS ALSO | | | ADDRESSED BY THE DIVISION OF HOTELS AND | | | RESTAURANTS. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL IF APPLICABLE WITHIN THE | | | SCOPE OF THIS PROJECT. | | | | | | 4) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-30 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-30 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2006-01-30 00:00:00 | WAITING FOR "COMM" BD | | | 1/30/06-ROUTED TO "DPALMER" PER "RBROWN" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-29 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-29 |
Time |
11:30 |
Sent To |
B |
|
| Notes |
| 2005-09-29 00:00:00 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-06 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-06 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2005-09-06 00:00:00 | TO "COMM" BD#23 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-07 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2005-07-06 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2005-07-06 00:00:00 | TO "COMM" BD#41 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-10-04 |
Time |
07:51 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-10-03 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2005-10-04 00:00:00 | ADDITIONAL PERMIT REQUIRED FOR THE | | | WALK-IN COOLER.PLEASE PROVIDE | | | MANUFACTURER'S INSTALLATION DATA WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | PLANS INDICATE NO A/C WORK REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-26 |
Time |
21:34 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-07-26 |
Time |
21:13 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | DENIED: | | | INSUFFICIENT INFORMATION, PLEASE PROVIDE | | | THE FOLLOWING INFORMATION FOR REVIEW: | | | 1.PLAN SHEET ME1 INDICATES HEAT HOOD. | | | PLEASE PROVIDE ELEVATION OF THE | | | TERMINATION.PLEASE CLARIFY THE | | | TERMIATION, I.E. PARKING AREA, SIDE | | | WALK, ALLEY?PROVIDE DISTANCES TO | | | PROPERTY LINES AND ADJACTENT BUILDINGS. | | | PLEASE CLARIFY. | | | | | | 2.PLEASE CLARIFY IF THE TERMINATION IS | | | A PROTECTIVE OPENING. | | | | | | 3.PROVIDE INFORMATION FOR MAKE-UP AIR. | | | | | | 4.PROVIDE INFORMATION ON THE | | | VENTILATION RECONFIGURATION AND EXISTING | | | OR NEW FRESH AIR CALCULATIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-10-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-10-05 |
Time |
15:48 |
Rev Time |
0.30 |
| Received By |
kstevens |
Date |
2005-10-05 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2005-09-23 00:00:00 | NEW SHEET |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-08-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-05 |
Time |
17:34 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-08-05 |
Time |
17:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-07 |
Time |
14:34 |
Rev Time |
|
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|