Plan Review Details - Permit 05070123
Plan Review Stops For Permit 05070123
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-21 Cont ID  
Sent By jgomez Date 2005-07-21 Time 18:12 Rev Time 0.50
Received By jgomez Date 2005-07-21 Time 18:12 Sent To PC
Notes
2005-07-21 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- NEED COMPLETE KEY PLAN AND
 INSTALLATION SCHEDULE. SEE ATTACHED COPY
  
 3- GENERIC DESIGN PRESSURES CHART
 DRAWING #02-061 CAN'T NOT BE USED. SEE
 ENGINEER'S LIMITATIONS ON NOTES AT
 BOTTOM OF PAGE. NEED TO COMPLY WITH ALL
 NOTES TO USE THIS CHART.
  
 4- VALUE DECLARED IN THE APPLICATION IS
 TOO LOW. PROVIDE CURRENT REALISTIC
 VALUATION OR FEE WILL BE RE-ESTIMATED
 USING THE MARSHALL VALUATION SERVICE AND
 VALUATION UPDATED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 10:54 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 10:54 Sent To B
Notes
2005-07-06 00:00:00TO "MISC" BOX