Plan Review Details - Permit 05070120
Plan Review Stops For Permit 05070120
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-29 Cont ID  
Sent By shill Date 2005-08-29 Time 08:10 Rev Time 0.50
Received By shill Date 2005-08-29 Time 07:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-17 Cont ID  
Sent By shill Date 2005-08-17 Time 08:53 Rev Time 0.00
Received By pschmitz Date 2005-08-27 Time 10:17 Sent To  
Notes
2005-08-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE CORRECTIONS FROM PREVIOUS LIST.
 THE SAME SHEETS WERE SUBMITTED.THE
 PREVIOUS COMMENTS HAVE BEEN ATTACHED FOR
 YOUR CONVENIENCE.
  
 2.)A 4X PLAN REVIEW FEE HAS BEEN
 CHARGED AS REQUIRED BY FS553.80(2)(B).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-04 Cont ID  
Sent By pschmitz Date 2005-08-09 Time 09:00 Rev Time 0.50
Received By shill Date 2005-08-04 Time 09:02 Sent To  
Notes
2005-08-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE PREVIOUS LIST, PROVIDE A DETAIL
 FOR THE BREAKROOM SINK, FBC11-4.24.
 PLEASE PROVIDE A DETAIL SHOWING
 COMPLIANCE WITH THIS CODES SECTION.A
 NOTE WAS PLACED ON THE PLAN, "MODIFY
 BASE & WALL CABINETS TO FIT TENANT'S
 REFRIGERATOR - EXISTING SINK TO REMAIN -
 ADA COMPLIANCE NOT REQUIRED".PLEASE
 READ FBC11-4.1.6(1)(B), FBC11-4.1(1)(A).
 IN THE FUTURE, TO EXPEDITE PLAN REVIEW,
 IF YOU DISAGREE WITH A COMMENT PLEASE
 CALL ME TO DISCUSS PRIOR TO RESUBMITTAL.
  
 2.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED (AS PER FLORIDA STATUTE) IF
 COMMENTS ARE NOT ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By pschmitz Date 2005-08-03 Time 08:38 Rev Time 0.50
Received By shill Date 2005-07-12 Time 07:38 Sent To  
Notes
2005-07-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED TO BE ON THE TITLE BLOCK FOR
 THE ARCHITECT CORPORATION.SEE
 FAC61G15-23.002.
  
 2.)PROVIDE A DETAIL FOR THE BREAKROOM
 SINK, FBC11-4.24.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-10-04 Cont ID  
Sent By dpalmer Date 2005-10-04 Time 08:09 Rev Time 0.00
Received By dpalmer Date 2005-10-04 Time 08:09 Sent To  
Notes
2005-10-04 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCK FOR
 LETTER.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED UNDER
 FS 481.219, FAC 61G1-16.004.
  
  
 2)NOTE: PLEASE SEE LETTER SHOULD
 REFERENCE THE PERMIT NUMBER. PLEASE SEE
 THE PCN # FOR THE PROPERTY IS NOTED AS
 THE PERMIT NUMBER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-24 Cont ID  
Sent By dpalmer Date 2005-08-24 Time 07:40 Rev Time 0.25
Received By dpalmer Date 2005-08-24 Time 07:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 19:53 Rev Time 0.40
Received By dpalmer Date 2005-08-11 Time 19:31 Sent To  
Notes
2005-08-11 00:00:00**** UNSAT 3RD REVIEW ****
  
 PLEASE SEE NOTES BELOW, CARRIED OVER
 FROM PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEENOTE #2 SECION ONE
 OF PREVIOUS REVIEW.
 PLEASE SEE ALL RECEPT CIRCUITS ARE STILL
 BEING SHOWN WITH LOADS EXCEEDING RATING
 OF CIRCUIT.
 PLEASE SEE A MAX OF 1920VA IS ERMITTED
 ON A 20A BRANCH CIRCUIT. PLEASE SEE
 220.13 FOR 180VA PER RECEPT WHEN RECEPT
 LOADS ARE KNOW.
 PLEASE SEE THIS WILL AFFECT CIRCUITING
 AS SHOWN ON PLANS.
  
 2)NOTE: PLEASE SEE PREVIOUS REVIEW
 REQUESTED ALL OLD/VOIDED SHEETS TOBE
 REMOVED FROM SETS AND INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 3)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND COMMENTS FOR CODE
 COMPLIANCE 3 OR MORE TIMES. THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 *** PLEASE SEE COMMENTS FROM FIRE, BLDG
 AND PLUMB ****
 PLEASE SEE FIRE REVIEW COMMENTS AS THEY
 WILL AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-28 Cont ID  
Sent By dpalmer Date 2005-07-28 Time 21:08 Rev Time 0.40
Received By dpalmer Date 2005-07-28 Time 21:01 Sent To  
Notes
2005-07-28 00:00:00**********UNSAT *************
  
 1)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS
 REVIEW WHICH REQUIRED ALL CIRCUITING FOR
 EM/EXT LTS PER 700.12E.
 PLEASE SEE THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
 PLEASE ALSO SEE LOW VOLTAGE FIRE DEVICES
 ARE NOTED AS BEING WIRED TO EM CIRCUIT?
 PLEASE SEE THESE SHOULD NOT BE WIRED
 INTO THE 120V CIRCUITING.
  
 2)NOTE: PLEASE SEE CIRCUITING NOW SHOWN
 FOR NEW RECEPTS, HOWEVER PLEASE SEE MAX
 KVA FOR EACH 20A BRANCH CIRCUIT IS 1920
 VA. PLEASE SEE 220.13 FOR RECEPT LOADS
 IN NON-DWELLING INSTALLATIONS.(180VA PER
 RECEPT).
 ** PLEASE ALSO SEE ALL ALL LOW VOLTAGE
 "DATA/PHONE" OUTLETS BEING
 WIRED/CIRCUITED TO THE LOCAL 120V RECEPT
 CIRCUIT??
 PLEASE CORRECT MISPRINT?
  
 3)NOTE: PLEASE SEE TWO CIRCUIT #26'S
 SHOWN ON PANEL SCHEDULE.
 215.5
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS SHALL BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 19:52 Rev Time 0.30
Received By dpalmer Date 2005-07-06 Time 19:47 Sent To  
Notes
2005-07-06 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCK PER
 FAC 61G1-16.004, FS 481.219
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION #.
  
 2)NOTE: PLEASE SHOW ALL CIRCUTING FOR
 NEW AND CORRELATE WITH A PANEL SCHEDULE
 TO BE SUBMITTED.
 PLEASE VERFIY CIRCUITING; NEW, EXISTING?
 PLEASE SEE 700.12E FOR EM/EXT LT
 CIRCUITING.
  
 3)NOTE: PLEASE SEE NOTES MENTIONS 2001
 NEC, 1999 NEC, FBC NEC ETC. PLEASE SEE
 AS OF JULY 7TH, 2003, WE
 ARE UNDER THE 2002 NEC.
 PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AHVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-08-29 Cont ID  
Sent By jwitmer Date 2005-08-29 Time 17:40 Rev Time 0.00
Received By jwitmer Date 2005-08-29 Time 17:39 Sent To  
Notes
2005-08-29 00:00:00OK PER M. CARSELLO / JW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-08-17 Cont ID  
Sent By mwennerg Date 2005-08-17 Time 11:20 Rev Time 0.00
Received By mwennerg Date 2005-08-17 Time 11:20 Sent To  
Notes
2005-08-17 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS.
  
 2) FIRE COMMENT #3 FROM PREVIOUS REVIEW
 DOES NOT APPEAR TO BE ADDRESSED BY
 LETTER OR ON THE DRAWINGS AS PER
 CONVERSATION. PLEASE ILLUSTRATE NEW OR
 EXISTING EQUIPMENT PERTINENT TO THIS
 SPACE.
  
  
 MIKE WENNERGREN,CAPTAIN/WPBFR
 FIRE PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-08-04 Cont ID  
Sent By mwennerg Date 2005-08-04 Time 14:48 Rev Time 0.00
Received By mwennerg Date 2005-08-04 Time 14:48 Sent To  
Notes
2005-08-04 00:00:00******DENIED******
  
 1) PLEASE SEE ELECTRICAL COMMENT #1.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 3) THE FIRST FIRE REVIEW REVEALED NO
 FIRE ALARM DEVICES, HOWEVER THIS REVIEW
 ILLUSTRATES ONE STROBE. PLEASE EXPLAIN.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 09:22 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 09:17 Sent To  
Notes
2005-07-11 00:00:001. COULD NOT LOCATE ANY FIRE ALARM
 DEVICES WITHIN SPACE. ARE THERE ANY
 EXISTING DEVICES CONTAINED WITHIN THE
 SPACE THAT WERE NOT SHOWN.
  
 2. ENTRY DOOR AND JAMB ARE TO BE
 PROPERLY FIRE RATED.
  
 3. INTERIOR FINISH CLASSIFICATION SHALL
 COMPLY WITH APPLICABLE REQUIREMENTS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 08:49 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 08:49 Sent To E
Notes
2005-10-12 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 18:43 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 18:43 Sent To E
Notes
2005-09-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 19:23 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 19:22 Sent To  
Notes
2005-08-23 00:00:00TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 11:27 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 11:27 Sent To  
Notes
2005-08-09 00:00:00TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-27 Cont ID  
Sent By adarroug Date 2005-07-27 Time 16:48 Rev Time 0.00
Received By adarroug Date 2005-07-27 Time 16:48 Sent To  
Notes
2005-07-27 00:00:00TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-27 Cont ID  
Sent By adarroug Date 2005-07-27 Time 16:47 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 10:50 Sent To  
Notes
2005-07-06 00:00:00TO "BUILD-OUT BD#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-08 Cont ID  
Sent By pkrauss Date 2005-07-08 Time 08:42 Rev Time 0.20
Received By pkrauss Date 2005-07-08 Time 08:42 Sent To  
Notes
2005-07-08 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICTED WITH PERMIT APPLICATION.
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION SHOULD ANY MECHANICAL
 WORK NEED TO BE DONE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-08-27 Cont ID  
Sent By pschmitz Date 2005-08-27 Time 10:19 Rev Time 0.00
Received By pschmitz Date 2005-08-27 Time 10:17 Sent To  
Notes
2005-08-27 00:00:00BREAK ROOM SINK REMOVED, SEC 704.5
 NO DEAD ENDS

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-08-13 Cont ID  
Sent By pschmitz Date 2005-08-13 Time 10:53 Rev Time 0.00
Received By pschmitz Date 2005-08-13 Time 10:53 Sent To B
Notes
2005-08-13 00:00:00PAUL SCHMITZ, PLUMBING PLANS EXAMINER
 [email protected]
  
 PLUMBING PLAN REVIEW FBC 2001
 DENIED 3RD TIME
 (1)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND COMMENTS FOR CODE
 COMPLIANCE 3 OR MORE TIMES. THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 (2) PREVIOUS REVIEW DATED 07-31-05
 RE:BREAK ROOM SINK, NOT ADDRESSED.
  
 (3)COPY OF PREVIOUS NOTES
 SEE NOTES FROM SMANTHA HILL,8-4-05
 RE: BREAK RM SINK.
  
 IF THERE ANY QUESTIONS, PLEASE DO NOT
 HESITATE TO CALL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-09 Cont ID  
Sent By pschmitz Date 2005-07-30 Time 12:18 Rev Time 0.00
Received By pschmitz Date 2005-07-30 Time 12:17 Sent To B
Notes
2005-07-30 00:00:00PAUL SCHMITZ, PLUMBING & GAS PLANS
 EXAMINER
 561-805-6692
 [email protected]
 PLUMBING PLAN REVIEW FBC 2001 CH 11
  
 PROVISO
 SEE NOTES FROM SMANTHA HILL,8-4-05
 RE: BREAK RM SINK
  
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By kstevens Date 2005-07-14 Time 06:48 Rev Time 0.35
Received By kstevens Date 2005-07-14 Time 06:48 Sent To  
Notes
2005-07-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF THE INCORPORATED ARCHITECTURAL
 BUSINESS PER FAC 61G1-16.004(2) AND FS
 481.219.
 2. SUBMIT A DETAIL FOR THE BREAKROOM
 SINK SHOWING THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH REQUIRED EXTENDING A
 MAXIMUM OF 19" UNDERNEATH THE SINK. -
 CABINET DOORS IN CLEAR FLOOR SPACE NOT
 APPROVED.
 E. 11-4.24.6 EXPOSED PIPES AND SURFACES
 F. 11-4.24.7 FAUCETS
 3. SUBMIT A SANITARY RISER DIAGRAM IN
 ISOMETRIC FORM, SHOWING ALL PIPE SIZES,
 VENTS, AND POINTS OF CONNECTIONS.
 SECTION 104.3.1.1.
 4. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM, SHOWING ALL PIPE SIZES,
 VALVES, AND POINTS OF CONNECTION.
 SECTION 104.3.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
 (PER CONVERSATION WITH JEROME BROMIEL -
 NO PLUMBING WORK WILL BE DONE ON THIS
 JOB. - ARCHITECT STATES THAT ONLY
 CABINET WORK ADDING A REFRIDGERATOR AND
 NO WORK ON THE CABINET AT THE SINK THIS
 JOB. 7-18-5)