| Plan Review Stops For Permit 05070120 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-29 |
Time |
08:10 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-08-29 |
Time |
07:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-08-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-17 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-08-27 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2005-08-17 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SEE CORRECTIONS FROM PREVIOUS LIST. | | | THE SAME SHEETS WERE SUBMITTED.THE | | | PREVIOUS COMMENTS HAVE BEEN ATTACHED FOR | | | YOUR CONVENIENCE. | | | | | | 2.)A 4X PLAN REVIEW FEE HAS BEEN | | | CHARGED AS REQUIRED BY FS553.80(2)(B). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-08-09 |
Time |
09:00 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-08-04 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2005-08-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)SEE PREVIOUS LIST, PROVIDE A DETAIL | | | FOR THE BREAKROOM SINK, FBC11-4.24. | | | PLEASE PROVIDE A DETAIL SHOWING | | | COMPLIANCE WITH THIS CODES SECTION.A | | | NOTE WAS PLACED ON THE PLAN, "MODIFY | | | BASE & WALL CABINETS TO FIT TENANT'S | | | REFRIGERATOR - EXISTING SINK TO REMAIN - | | | ADA COMPLIANCE NOT REQUIRED".PLEASE | | | READ FBC11-4.1.6(1)(B), FBC11-4.1(1)(A). | | | IN THE FUTURE, TO EXPEDITE PLAN REVIEW, | | | IF YOU DISAGREE WITH A COMMENT PLEASE | | | CALL ME TO DISCUSS PRIOR TO RESUBMITTAL. | | | | | | 2.)SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW FEE IS REQUIRED TO BE | | | CHARGED (AS PER FLORIDA STATUTE) IF | | | COMMENTS ARE NOT ADDRESSED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-08-03 |
Time |
08:38 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-12 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2005-07-12 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)CERTIFICATE OF AUTHORIZATION NUMBER | | | REQUIRED TO BE ON THE TITLE BLOCK FOR | | | THE ARCHITECT CORPORATION.SEE | | | FAC61G15-23.002. | | | | | | 2.)PROVIDE A DETAIL FOR THE BREAKROOM | | | SINK, FBC11-4.24. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-04 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-10-04 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2005-10-04 00:00:00 | ***** UNSAT ***** | | | | | | 1)NOTE: PLEASE SEE MISSING LICENSE | | | INFORMATION REQUIRED ON TITLE BLOCK FOR | | | LETTER. | | | PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER AS REQUIRED UNDER | | | FS 481.219, FAC 61G1-16.004. | | | | | | | | | 2)NOTE: PLEASE SEE LETTER SHOULD | | | REFERENCE THE PERMIT NUMBER. PLEASE SEE | | | THE PCN # FOR THE PROPERTY IS NOTED AS | | | THE PERMIT NUMBER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-24 |
Time |
07:40 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-08-24 |
Time |
07:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-11 |
Time |
19:53 |
Rev Time |
0.40 |
| Received By |
dpalmer |
Date |
2005-08-11 |
Time |
19:31 |
Sent To |
|
|
| Notes |
| 2005-08-11 00:00:00 | **** UNSAT 3RD REVIEW **** | | | | | | PLEASE SEE NOTES BELOW, CARRIED OVER | | | FROM PREVIOUS REVIEW. | | | | | | 1)NOTE: PLEASE SEENOTE #2 SECION ONE | | | OF PREVIOUS REVIEW. | | | PLEASE SEE ALL RECEPT CIRCUITS ARE STILL | | | BEING SHOWN WITH LOADS EXCEEDING RATING | | | OF CIRCUIT. | | | PLEASE SEE A MAX OF 1920VA IS ERMITTED | | | ON A 20A BRANCH CIRCUIT. PLEASE SEE | | | 220.13 FOR 180VA PER RECEPT WHEN RECEPT | | | LOADS ARE KNOW. | | | PLEASE SEE THIS WILL AFFECT CIRCUITING | | | AS SHOWN ON PLANS. | | | | | | 2)NOTE: PLEASE SEE PREVIOUS REVIEW | | | REQUESTED ALL OLD/VOIDED SHEETS TOBE | | | REMOVED FROM SETS AND INSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | 3)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL AND COMMENTS FOR CODE | | | COMPLIANCE 3 OR MORE TIMES. THIS IS ONLY | | | A NOTICE GIVEN AT THIS TIME. | | | | | | *** PLEASE SEE COMMENTS FROM FIRE, BLDG | | | AND PLUMB **** | | | PLEASE SEE FIRE REVIEW COMMENTS AS THEY | | | WILL AFFECT ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-28 |
Time |
21:08 |
Rev Time |
0.40 |
| Received By |
dpalmer |
Date |
2005-07-28 |
Time |
21:01 |
Sent To |
|
|
| Notes |
| 2005-07-28 00:00:00 | **********UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS | | | REVIEW WHICH REQUIRED ALL CIRCUITING FOR | | | EM/EXT LTS PER 700.12E. | | | PLEASE SEE THE BRANCH CIRCUIT FEEDING | | | THE UNIT EQUIPMENT SHALL BE THE SAME | | | BRANCH CIRCUIT AS THAT SERVING THE | | | NORMAL LIGHTING IN THE AREA AND | | | CONNECTED AHEAD OF ANY LOCAL SWITCHES. | | | PLEASE ALSO SEE LOW VOLTAGE FIRE DEVICES | | | ARE NOTED AS BEING WIRED TO EM CIRCUIT? | | | PLEASE SEE THESE SHOULD NOT BE WIRED | | | INTO THE 120V CIRCUITING. | | | | | | 2)NOTE: PLEASE SEE CIRCUITING NOW SHOWN | | | FOR NEW RECEPTS, HOWEVER PLEASE SEE MAX | | | KVA FOR EACH 20A BRANCH CIRCUIT IS 1920 | | | VA. PLEASE SEE 220.13 FOR RECEPT LOADS | | | IN NON-DWELLING INSTALLATIONS.(180VA PER | | | RECEPT). | | | ** PLEASE ALSO SEE ALL ALL LOW VOLTAGE | | | "DATA/PHONE" OUTLETS BEING | | | WIRED/CIRCUITED TO THE LOCAL 120V RECEPT | | | CIRCUIT?? | | | PLEASE CORRECT MISPRINT? | | | | | | 3)NOTE: PLEASE SEE TWO CIRCUIT #26'S | | | SHOWN ON PANEL SCHEDULE. | | | 215.5 | | | | | | PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | ONE COPY OF OLD/VOIDED SHEETS SHALL BE | | | SUBMITTED FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-06 |
Time |
19:52 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-06 |
Time |
19:47 |
Sent To |
|
|
| Notes |
| 2005-07-06 00:00:00 | *************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE MISSING REQUIRED | | | LICENSE INFORMATION ON TITLE BLOCK PER | | | FAC 61G1-16.004, FS 481.219 | | | PLEASE SEE MISSING CERTIFICATE OF | | | AUTHORIZATION #. | | | | | | 2)NOTE: PLEASE SHOW ALL CIRCUTING FOR | | | NEW AND CORRELATE WITH A PANEL SCHEDULE | | | TO BE SUBMITTED. | | | PLEASE VERFIY CIRCUITING; NEW, EXISTING? | | | PLEASE SEE 700.12E FOR EM/EXT LT | | | CIRCUITING. | | | | | | 3)NOTE: PLEASE SEE NOTES MENTIONS 2001 | | | NEC, 1999 NEC, FBC NEC ETC. PLEASE SEE | | | AS OF JULY 7TH, 2003, WE | | | ARE UNDER THE 2002 NEC. | | | PLEASE ADJUST. | | | | | | 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 | | | WHICH REQUIRES ALL 15- AND 20-AMPERE, | | | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE | | | KITCHENS TO BE GFCI PROTECTED. THIS | | | REQUIREMENT APPLIES TO EACH AND EVERY | | | 15- AND 20-AMPERE, 125-VOLT KITCHEN | | | RECEPTACLE, WHETHER OR NOT THE | | | RECEPTACLE SERVES COUNTERTOP APPLIANCES. | | | | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AHVE AN | | | AFFECT ON ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICALPLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-29 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2005-08-29 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2005-08-29 00:00:00 | OK PER M. CARSELLO / JW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2005-08-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-17 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-17 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2005-08-17 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS. | | | | | | 2) FIRE COMMENT #3 FROM PREVIOUS REVIEW | | | DOES NOT APPEAR TO BE ADDRESSED BY | | | LETTER OR ON THE DRAWINGS AS PER | | | CONVERSATION. PLEASE ILLUSTRATE NEW OR | | | EXISTING EQUIPMENT PERTINENT TO THIS | | | SPACE. | | | | | | | | | MIKE WENNERGREN,CAPTAIN/WPBFR | | | FIRE PLAN REVIEW(561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-08-04 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-08-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2005-08-04 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE ELECTRICAL COMMENT #1. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 3) THE FIRST FIRE REVIEW REVEALED NO | | | FIRE ALARM DEVICES, HOWEVER THIS REVIEW | | | ILLUSTRATES ONE STROBE. PLEASE EXPLAIN. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-07-11 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-07-11 |
Time |
09:17 |
Sent To |
|
|
| Notes |
| 2005-07-11 00:00:00 | 1. COULD NOT LOCATE ANY FIRE ALARM | | | DEVICES WITHIN SPACE. ARE THERE ANY | | | EXISTING DEVICES CONTAINED WITHIN THE | | | SPACE THAT WERE NOT SHOWN. | | | | | | 2. ENTRY DOOR AND JAMB ARE TO BE | | | PROPERLY FIRE RATED. | | | | | | 3. INTERIOR FINISH CLASSIFICATION SHALL | | | COMPLY WITH APPLICABLE REQUIREMENTS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-12 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-12 |
Time |
08:49 |
Sent To |
E |
|
| Notes |
| 2005-10-12 00:00:00 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-29 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-29 |
Time |
18:43 |
Sent To |
E |
|
| Notes |
| 2005-09-29 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-23 |
Time |
19:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-23 |
Time |
19:22 |
Sent To |
|
|
| Notes |
| 2005-08-23 00:00:00 | TO "BOB"#3 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-09 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-09 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2005-08-09 00:00:00 | TO "BOB"#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-27 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-27 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2005-07-27 00:00:00 | TO "BOB"#1 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-27 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-06 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2005-07-06 00:00:00 | TO "BUILD-OUT BD#6 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-07-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-08 |
Time |
08:42 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2005-07-08 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2005-07-08 00:00:00 | NO MECHANICAL PLANS OR CONTRACTOR | | | INDICTED WITH PERMIT APPLICATION. | | | PLEASE PROVIDE PLANS WITH MECHANICAL | | | PERMIT APPLICATION SHOULD ANY MECHANICAL | | | WORK NEED TO BE DONE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-08-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-08-27 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-08-27 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2005-08-27 00:00:00 | BREAK ROOM SINK REMOVED, SEC 704.5 | | | NO DEAD ENDS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-08-13 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-08-13 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-08-13 |
Time |
10:53 |
Sent To |
B |
|
| Notes |
| 2005-08-13 00:00:00 | PAUL SCHMITZ, PLUMBING PLANS EXAMINER | | | [email protected] | | | | | | PLUMBING PLAN REVIEW FBC 2001 | | | DENIED 3RD TIME | | | (1)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL AND COMMENTS FOR CODE | | | COMPLIANCE 3 OR MORE TIMES. THIS IS ONLY | | | A NOTICE GIVEN AT THIS TIME. | | | | | | (2) PREVIOUS REVIEW DATED 07-31-05 | | | RE:BREAK ROOM SINK, NOT ADDRESSED. | | | | | | (3)COPY OF PREVIOUS NOTES | | | SEE NOTES FROM SMANTHA HILL,8-4-05 | | | RE: BREAK RM SINK. | | | | | | IF THERE ANY QUESTIONS, PLEASE DO NOT | | | HESITATE TO CALL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-07-30 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-07-30 |
Time |
12:17 |
Sent To |
B |
|
| Notes |
| 2005-07-30 00:00:00 | PAUL SCHMITZ, PLUMBING & GAS PLANS | | | EXAMINER | | | 561-805-6692 | | | [email protected] | | | PLUMBING PLAN REVIEW FBC 2001 CH 11 | | | | | | PROVISO | | | SEE NOTES FROM SMANTHA HILL,8-4-05 | | | RE: BREAK RM SINK | | | | | | END OF COMMENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-14 |
Time |
06:48 |
Rev Time |
0.35 |
| Received By |
kstevens |
Date |
2005-07-14 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2005-07-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS CERTIFICATE OF | | | AUTHORIZATION IS REQUIRED IN THE TITLE | | | BLOCK OF THE INCORPORATED ARCHITECTURAL | | | BUSINESS PER FAC 61G1-16.004(2) AND FS | | | 481.219. | | | 2. SUBMIT A DETAIL FOR THE BREAKROOM | | | SINK SHOWING THE FOLLOWING: | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH | | | D. 11-4.24.5 CLEAR FLOOR SPACE - | | | FORWARD APPROACH REQUIRED EXTENDING A | | | MAXIMUM OF 19" UNDERNEATH THE SINK. - | | | CABINET DOORS IN CLEAR FLOOR SPACE NOT | | | APPROVED. | | | E. 11-4.24.6 EXPOSED PIPES AND SURFACES | | | F. 11-4.24.7 FAUCETS | | | 3. SUBMIT A SANITARY RISER DIAGRAM IN | | | ISOMETRIC FORM, SHOWING ALL PIPE SIZES, | | | VENTS, AND POINTS OF CONNECTIONS. | | | SECTION 104.3.1.1. | | | 4. SUBMIT A WATER RISER DIAGRAM IN | | | ISOMETRIC FORM, SHOWING ALL PIPE SIZES, | | | VALVES, AND POINTS OF CONNECTION. | | | SECTION 104.3.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | (PER CONVERSATION WITH JEROME BROMIEL - | | | NO PLUMBING WORK WILL BE DONE ON THIS | | | JOB. - ARCHITECT STATES THAT ONLY | | | CABINET WORK ADDING A REFRIDGERATOR AND | | | NO WORK ON THE CABINET AT THE SINK THIS | | | JOB. 7-18-5) |
|
|