Plan Review Details - Permit 05070071
Plan Review Stops For Permit 05070071
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-26 Cont ID  
Sent By jwitmer Date 2006-07-26 Time 14:37 Rev Time 2.22
Received By jwitmer Date 2006-07-26 Time 14:07 Sent To PC
Notes
2006-07-26 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 05070071
 ADDRESS: 833 BISCAYNE
 CONT: H. CANO CONSTRUCTION
 TELL # (561)543-1290
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2* ADMINISTRATIVE CODE.
  
 REVIEWED UNDER 2001 F.B.C.
  
 (*) NOTES WITH ASTERISK (*) ARE 2001
 AMENDMENTS TO THE CODE.
  
 BUILDING PROVISOS:
  
 1) SEPERATE PLANS,PERMITS & ASSOCIATED
 FEES FOR MECHANICAL, ELECTRIC & PLUMBING
 SUBPERMITS.
  
 2) ENERGY CALS TO BE SUBMITTED WITH
 ELECTRICAL PLANS.
  
 3) 905.2.1905.2.1 APPROVED
 SINGLE-STATION OR MULTIPLE-STATION SMOKE
 DETECTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, CHAPTER 11,
 WITHIN EVERYDWELLING AND EVERY
 DWELLING UNIT WITHIN AN APARTMENT HOUSE,
 CONDOMINIUM ORTOWNHOUSE; AND EVERY
 GUEST OR SLEEPING ROOM IN A MOTEL, HOTEL
 OR DORMITORYAND SLEEPING ROOMS IN
 RESIDENTIAL CARE/ASSISTED LIVING
 OCCUPANCIES.WHEREMORE THAN ONE
 DETECTOR IS REQUIRED TO BE INSTALLED
 WITHIN AN INDIVIDUAL DWELLING UNIT, THE
 DETECTORS SHALL BE WIRED IN SUCH A
 MANNER THAT THE ACTUATION OF ONE ALARM
 WILL ACTUATE ALL OF THE ALARMS IN THE
 INDIVIDUAL UNIT.
  
 4) GFCI OUTLETS TO BE BROUGHT 210.A.NEC
  
 5) BEFORE A CERTIFICATE OF COMPLITION
 WILL BE ISSUED FOR THIS PERMIT, THE
 WINDOWS THAT WERE INSTALLED UNDER THE
 VOIDED PERMIT 03080376 MUST REAPPLY AND
 RECEIVE A PERMIT FOR WINDOWS AND
 SHUTTERS AS WELL AS PASS AND FINAL EACH
 PERMIT BEFORE A CERTIFICATE OF
 COMPLETION WILL BE ISSUED FOR THIS
 RENOVATION AND ADDITION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-26 Cont ID  
Sent By jwitmer Date 2006-07-26 Time 12:57 Rev Time 2.22
Received By jwitmer Date 2006-07-13 Time 12:24 Sent To PC
Notes
2006-07-26 00:00:00ADD: 833 BISCAYNE DR
 CONT: H. CANO
 TEL: (561)543-1290
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THERE IS AN ISSUE OF WEATHER WINDOWS
 INSTALLED UNDER PERMIT# 03080376 WERE
 EVER INSTECTED. I HAD CALLED THE
 ARCHITECT AND DISCUSED AT LENGTH THE
 REFRENCED PERMIT NEVER HAD INSPECTIONS
 AND WAS NULL AND VOID. THE WINDOWS WERE
 TO BE PLACED UNDER THIS PERMIT AND
 RELEVENT INSPECTIONS. SINCE THIS
 STRUCTURES WALLS ARE CONSTRUCTED FROM
 TERRA-COTTA TILE ,THE PRODUCT APPROVALS
 SUBMITTED FOR WINDOWS AND STORM SHUTTERS
 WILL NEED SITE SPECIFIC ENGINEERING
 SINCE THE PRODUCT APPROVALS WERE NOT
 TESTED IN THIS TYPE INSTALLATION.
 ARCHITECT RAFAEL RODRIGUEZ CALLED
 TODAY AND INDICATED THIS SITE SPICIFIC
 ENGINEERING WOULD BE HANDLED THROUGH THE
 CONTRACTOR OF RECORD.
 IF ANY FURTHER INFORMATION IS
 REQUIRED PLEASE CONTACT ME AT:
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-19 Cont ID  
Sent By jwitmer Date 2005-12-19 Time 09:21 Rev Time 1.22
Received By jwitmer Date 2005-12-19 Time 09:21 Sent To PC
Notes
2005-12-19 00:00:00PERMIT: 05070071
 ADD: 833 BISCAYNE DR
 CONT: H. CANO
 TEL: (561)543-1290
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS NO LARGE MISSLE RATING
 REQUIRES STORM SHUTTERS
 B) EXTERIOR DOORS NO LARGE MISSLE RATING
  
 REQUIRES SYORM SHUTTERS
 D) ROOFING ASSEMBLIES
 THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _3__ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
  
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
 2E) STORM SHUTTER WILL BE REQUIRED
 PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 3) PLANS INDICATE A PERMIT WAS PULLED TO
 REPLACE WINDOWS, NO PERMIT IS INDICATED
 FOR THIS ADDRESS, SEE ATTACHMENT.
  
 4) COMMENT # 7 FROM THE PREVIOUS REVIEW
 DEALS WITH THE USE OF PECKY CYPRESS 1X3
 UNDER THE 5/8 PLYWOOD ROOF DECK, SEE A-3
  
 INDICATE LENGTH OF NAIL FOR THE 5/8"
 PLYWOOD TO PENETRATE THE ROOF FRAMING
 MEMBERS?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By jwitmer Date 2005-08-02 Time 06:56 Rev Time 1.33
Received By jwitmer Date 2005-08-02 Time 06:32 Sent To PC
Notes
2005-08-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070071
 ADD: 833 BISCAYNE DR
 CONT: H. CANO
 TEL: (561)543-1290
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 C) TRUSS/ WOOD TO WOOD ANCHORS
 D) ROOFING ASSEMBLIES
  
 3) PLANS INDICATE A PERMIT WAS PULLED TO
  
 REPLACE WINDOWS, NO PERMIT IS INDICATED
 FOR THIS ADDRESS, SEE ATTACHMENT.
  
 4) PLANS DO NOT INDICATE THE
 MANUFACTURING COMPANY FOR HOLDOWN
 ANCHORS. ALSO INDICATE LOADS TO BE
 IMPOSED UPLIFT, LATERAL & GRAVITY LOADS.
 PROVIDE THE MANUFATURES DESIGN PRESSURES
 TO BE USED.
 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 5)TRUSS ANCHORS:1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 6) PLANAS DO NOT INDICATE TERMITE
 TREATMENT OF SOILS:1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION.SEE 202,
 REGISTERED TERMITICIDE.UPON COMPLETION
 OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST
 CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT:"THE BUILDING HAS
 RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES
 AND LAWS ESTABLISHED BY THE FLORIDA
 DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES."
 1816.1.4 IF SOIL TREATMENT IS USED FOR
 SUBTERRANEAN TERMITE PREVENTION,
 CHEMICALLY TREATED SOIL SHALL BE
 PROTECTED WITH A MINIMUM 6 MIL VAPOR
 RETARDER TO PROTECT AGAINST RAINFALL
 DILUTION.IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT
 IS REQUIRED.ANY WORK, INCLUDING
 PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE
 CONCRETE FLOOR IS POURED, SHALL BE
 DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTUBING TREATED
  
 7) PLANS INDICATE THE USE OF 1X3 PECKY
 CYPRESS UNDER THE ROOF, 5/8" CDX PLYWOOD
  
 WILL NEED TO BE OVER THE PECKY CYPRESS
 TO NAIL ROOFING MATERIALS TOO.
  
 8) PROVIIDE FOR ATTIC VENTING:
 2309.7.2 FOR FLAT ROOFS, BLOCKING AND
 BRIDGING SHALL BE ARRANGED SOAS NOT
 TO INTERFERE WITH THE MOVEMENT OF AIR.
 SUCH ROOFS SHALL BEVENTILATED ALONG
 THE OVERHANGING EAVES, WITH THE NET AREA
 OF OPENINGBEING NOT LESS THAN 1/250
 OF THE AREA OF THE CEILING BELOW.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) PLANS DO NOT INDICATE ELECTRICAL
 NOR PLUMBING WORK WHICH WILL REQUIRE
 REVIEW AND SEPERATE PERMITS.
  
 11) PLANS INDICATE REPAIR OF EXISTING
 DRIVEWAY AND SIDEWALK, PROVIDE WHAT
 REPAIR, APPLICATION INDICATES
 REPLACEMENT? PROVIDE MORE INFORMATION?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2006-07-26 Time 15:13 Rev Time 0.00
Received By dpalmer Date 2006-07-26 Time 15:13 Sent To  
Notes
2006-07-26 00:00:00ALL SD'S ARE TO BE BROUGHT UP TO CODE
 ALONG WITH GFI'S

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2006-06-25 Time 13:48 Sent To P
Notes
2006-06-25 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE SUBMIT COMPLETED
 ELECTRICAL PLANS FOR NEW SCOPE OF WORK
 PER 2002 NEC NFPA-70
 PLEASE SHOW ALL EXISTING OR NEW
 ELECTRICAL MEETING RECEPT SPACING,
 EGRESS LIGHTING, LIGHTING CONTROLS,
 SMOKE DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS, DEDICATED CIRUCITS FOR
 KITCHENS, BATHS, APPLIANCES, ETC
 PLEASE SEE PLANS INDICATE A NEW SERVICE,
 HOWEVER NO ELECTRICAL RISER DIAGRAM WAS
 SUBMITTED. PANEL SCHEDULE SHOWING ALL
 CONDUCTOR SIZES, OCP ETC.
 FBC ADMIN SECT 106.1.2, 106.3.5.4,
 215.5, 110.9,240.4,310.16,210.52,210.11,
 210.70, LS 101 7.8,220.16, 220.31, 408.4
 ETC
 NFPA-72,11.5.1.1,11.8.3,
 R313
  
 2) NOTE: PLEASE SEE THAT MIN ENERGY
 CALCULATIONS REQUIRED AND SHALL BE
 SUBMITTEDCORRELATE WITH ELECTRICAL
 PLANS.
 THESE SHALL ALSO BE SIGNED, DATED AND
 SEALED BY THE DESIGN PROFESSIONAL OF
 RECORD.
 FBC CHAPTER 13
  
 3) NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO SETS FOR
 REVIEW AND STAMPING. PLEASE KNOW, AN
 REVISED SHEETS WILL BE REQUIRED TO BE
 STAMPED THE "HISTORIC REVIEW".
 PLEASE SUBMIT ONE COPY OF ANY OLD/VOIDED
 SHEETS SEPARATELY FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 11:43 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 11:43 Sent To E
Notes
2006-06-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 08:39 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 08:39 Sent To Z
Notes
2006-06-19 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-15 Cont ID  
Sent By adarroug Date 2005-12-15 Time 10:22 Rev Time 0.00
Received By adarroug Date 2005-12-15 Time 10:22 Sent To B
Notes
2005-12-15 00:00:00TO "JWITMER"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-08 Cont ID  
Sent By adarroug Date 2005-07-08 Time 14:05 Rev Time 0.00
Received By adarroug Date 2005-07-08 Time 14:05 Sent To B
Notes
2005-07-08 00:00:00TO "MISC" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2005-08-02 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2005-07-01 Time 18:17 Sent To  
Notes
2005-07-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-07-10 Cont ID  
Sent By tgordon Date 2006-07-10 Time 11:17 Rev Time 0.15
Received By tgordon Date 2006-07-10 Time 11:17 Sent To B
Notes
2006-07-10 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-07-26 Cont ID  
Sent By jleech Date 2006-07-26 Time 13:42 Rev Time 0.00
Received By jleech Date 2006-07-26 Time 13:42 Sent To  
Notes
2006-07-26 00:00:00NO PLUMBING ON THIS PLAN . PLANS MUST BE
 SUBMITED WITH PLUMBING PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 06:35 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 06:35 Sent To M
Notes
2006-07-08 00:00:00DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING
 REVIEW. DRAW A SANITARY RISER DIAGRAM OF
 THE NEW WORK. SIZE ALL PIPE, VENTS,
 CLEANOUTS AND HOW NEW WORK WILL TIE INTO
 EXISTING BUILDING DRAIN OR SEWER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-06-21 Cont ID  
Sent By mmclean Date 2006-06-21 Time 07:30 Rev Time 0.00
Received By mmclean Date 2006-06-21 Time 07:30 Sent To I
Notes
2006-06-21 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 THE CBS WALL WITHIN THE FRONT SETBACK,
 WITH UTILITY EASEMENT APPROVAL FROM THE
 CITY OF WEST PALM UTILITY DEPT. MAXIMUM
 HEIGHT ALLOWED IS 4FT ONLY.
  
 NOTE: THE REPAIR OF EXISTING DRIVEWAY
 WILL NOT AFFECT THE DIEMENSION.IF THE
 REPAIRS REQUIRE A WIDER OR LONGER
 DRIVEWAY, PLEASE DO REVISON FOR SUCH
 CHANGES.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-07 Cont ID  
Sent By mmclean Date 2005-07-07 Time 16:40 Rev Time 0.00
Received By mmclean Date 2005-07-07 Time 16:40 Sent To I
Notes
***NONE***