Plan Review Details - Permit 05070030
Plan Review Stops For Permit 05070030
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-23 Cont ID  
Sent By alange Date 2005-08-23 Time 07:48 Rev Time 2.00
Received By alange Date 2005-08-22 Time 15:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By alange Date 2005-08-01 Time 06:57 Rev Time 3.50
Received By alange Date 2005-08-01 Time 06:50 Sent To  
Notes
2005-08-01 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2. SINCE BBQ OPTION WILL NOT BE USED.
 REMOVE ALL REFERENCE ON PLANS REGARDING
 BBQ.
  
 3.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 4.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION HAS BEEN
 CHANGED TO $284,256.ADDITIONAL PERMIT
 FEES ARE DUE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-10 Cont ID  
Sent By dpalmer Date 2006-03-10 Time 06:54 Rev Time 0.00
Received By dpalmer Date 2006-03-10 Time 06:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 20:47 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 20:26 Sent To PC
Notes
2006-02-09 00:00:00*** PLANS REDLINED**
  
 RISER IS A 400A SERVICE, MIN GEC SHALL
 BE SIZED PER 250.66, 1/0 MIN.
  
 REQUIRES A MIN OF 2 GRND RODS/ FOOTER
 STEEL.
 250.50,250.56.
 FOOTER STEEL WAS REMOVED FROM RISER,
 HOWEVER THIS IS REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-14 Cont ID  
Sent By dpalmer Date 2005-07-14 Time 20:46 Rev Time 0.33
Received By dpalmer Date 2005-07-14 Time 20:33 Sent To M
Notes
2005-07-14 00:00:00ELEC FOR REVIEW.
 REDLINED THE FOLLOWING.
  
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM MAIN TO POOL SUB PANEL.
 250.110,250.122 ETC
  
 POOL PUMP, 125% FOR CONTINUOUS LOAD.(3
 OR MORE HOURS).
  
 THERE IS NO NEED FOR CORRECTIONS,
 HOWEVER OF PLANS ARE REVISED FOR JOBSITE
 CHANGES, PLEASE MAKE THE ABOVE
 CORRECTIONS/ADJUSTMENTS AT THAT TIME.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 15:42 Sent To E
Notes
2006-03-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-07 Cont ID  
Sent By adarroug Date 2006-02-07 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-02-07 Time 15:21 Sent To E
Notes
2006-02-07 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 16:31 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 16:31 Sent To B
Notes
2005-08-18 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 10:43 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 10:39 Sent To E
Notes
2005-07-14 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By alange Date 2005-08-01 Time 07:13 Rev Time 0.00
Received By alange Date 2005-07-01 Time 17:16 Sent To  
Notes
2005-07-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By hmoser Date 2005-07-20 Time 16:39 Rev Time 0.00
Received By hmoser Date 2005-07-20 Time 16:24 Sent To P
Notes
2005-07-20 00:00:00NO PLANS

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 10:29 Rev Time 0.33
Received By jleech Date 2005-07-23 Time 10:29 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-13 Cont ID  
Sent By mmclean Date 2005-07-13 Time 17:12 Rev Time 0.00
Received By mmclean Date 2005-07-13 Time 17:12 Sent To I
Notes
***NONE***