Plan Review Details - Permit 05070029
Plan Review Stops For Permit 05070029
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-27 Cont ID  
Sent By alange Date 2005-09-27 Time 09:48 Rev Time 1.66
Received By alange Date 2005-09-27 Time 09:48 Sent To  
Notes
2005-09-27 00:00:00STAMPED AND ISSUED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By alange Date 2005-08-01 Time 07:43 Rev Time 3.25
Received By alange Date 2005-08-01 Time 07:43 Sent To Z
Notes
2005-08-01 00:00:00DENIED
  
 BUILDING REVIEW OK.
 SEE ELECTRICAL REVIEW NOTE # 1.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-05 Cont ID  
Sent By btrobaug Date 2006-06-05 Time 18:01 Rev Time 0.50
Received By btrobaug Date 2006-06-05 Time 17:50 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-09 Cont ID  
Sent By dpalmer Date 2006-05-09 Time 20:22 Rev Time 0.00
Received By dpalmer Date 2006-05-09 Time 20:17 Sent To PC
Notes
2006-05-09 00:00:00REV'S.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-20 Cont ID  
Sent By dpalmer Date 2005-09-20 Time 18:29 Rev Time 0.50
Received By dpalmer Date 2005-09-20 Time 18:18 Sent To P
Notes
2005-09-20 00:00:00 
 ** PLEASE SEE ONLY ELECTRICAL SHEETS
 CONTAINS THE RE-SIGNED SHEETS PER THE
 ARCHITECT'S SIGNATURE ON FILE.
  
 *** PLANS REDLINED ****
  
 3-#4'S SHOWN FOR POOL FEEDERS ALONG WITH
 NEUTRAL AND GROUNDING CONDUCTOR?
  
 110.26 FOR POOL PANEL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 06:55 Rev Time 0.40
Received By dpalmer Date 2005-07-14 Time 20:49 Sent To M
Notes
2005-07-15 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE PLANS ARE TO BE
 SIGNED BY THE ARCHITECT OF RECORD AND
 SHALL MATCH WITH SIGNATURE ON FILE.
 FS 481.221
 ONE COPY OF PLANS RETAINED AND SHALL BE
 RETAINED WITH SAID FILE.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO POOL
 PANEL.
 250.110,250.122 ETC.
  
 3)NOTE: PLEASE SEE CONTINUOUS LOADS ON
 POOL PANEL ARE TO BE SHOWN AT 125%.
 (POOL PUMP).
  
 4)NOTE: PLEASE SEE RECEPTS MISSING ALONG
 COUNTERSPACE PER 210.52C1 OUTSIDE WALL
 AND CORNER WALL.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-14 00:00:00IN ELEC FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 16:11 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 16:11 Sent To E
Notes
2006-05-26 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 14:49 Sent To E
Notes
2006-05-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-16 Cont ID  
Sent By adarroug Date 2005-09-16 Time 17:02 Rev Time 0.00
Received By adarroug Date 2005-09-16 Time 17:02 Sent To E
Notes
2005-09-16 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 10:44 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 10:44 Sent To E
Notes
2005-07-14 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-08-01 Time 11:51 Rev Time 0.00
Received By mmclean Date 2005-07-01 Time 17:19 Sent To  
Notes
2005-07-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By hmoser Date 2005-07-20 Time 16:47 Rev Time 0.00
Received By hmoser Date 2005-07-20 Time 16:42 Sent To P
Notes
2005-07-20 00:00:00NO PLANS

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By jleech Date 2005-09-22 Time 09:26 Rev Time 0.33
Received By jleech Date 2005-09-22 Time 09:26 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 10:11 Rev Time 0.33
Received By jleech Date 2005-07-23 Time 10:11 Sent To B
Notes
2005-07-23 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW'S NOTE 1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-01 Cont ID  
Sent By mmclean Date 2005-07-13 Time 10:43 Rev Time 0.00
Received By mmclean Date 2005-07-13 Time 10:43 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy