| 2005-08-31 00:00:00 | *** UNSAT *** |
| | |
| | 1)NOTE:IF ENGINEER ON PLANS IS NOT AN |
| | EMPLOYEE OF GARRISON DESIGN GROUP,PLEASE |
| | PROVIDE A SIGNED, SEALED LTR FROM |
| | ENGINEER WHICH STATES THIS. |
| | A CA/ LICENSE # IS NOT REQUIRED FOR |
| | GARRISON DESIGN GROUP AS THEY ARE NOT AN |
| | ARCHITECTUAL OR ENGINEERING FIRM TO THIS |
| | OFFICE'S UNDERSTANDING. |
| | |
| | 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLANS DO NOTE AIC RATING FOR MAIN , |
| | HOWEVER PANELS DO NOT INDICATE SERIES |
| | RATINGS? |
| | |
| | 3)NOTE: PLEASE SEE RECEPTS MISSING PER |
| | 210.52. PLEASE SEE THESE ARE REDLINE DON |
| | PLANS AT LOCATIONS. |
| | |
| | 4)NOTE: PLEASE SEE SD AS SHOWN IN |
| | KITCHEN MAY NOT BE CLOSER THAN 20'FROM |
| | COOKING APPLIANCES UNLESS MEETING THE |
| | EXCEPTIONS PERMITTED UNDER NFPA-72 |
| | 8-1.4.2 |
| | PLEASE SEE SD FOR MASTER BEDROOM, MUST |
| | BE INSIDE MASTER BEDRM AREA. NFPA-72 |
| | 8-1.4.1.6.2, AND CHAPTER 2 FOR |
| | PLACEMENT. 3' FROM A PEAK ON SLOPED |
| | CEILING AND WITHIN 12" OF CEILING ON A |
| | FLAT CEILING. PLEASE SEE SD IS SHOWN IN |
| | HALLWAY WHICH ALSO CONTAINS A HEADER |
| | MORE THAN 12". |
| | THIS WAS ALSO REDLINED ON PLANS. |
| | |
| | 5)NOTE: PLEASE SEE LOAD CALCULATIONS NOW |
| | SUBMITTED. |
| | PLEASE SEE TOTALS SHOWN AND LOADS |
| | INDICATED IN LOAD CALCS. SOME OF THESE |
| | #'S DO NOT CORRELATE. PLEASE SEE THESE |
| | ARE REDLINED. |
| | PLEASE ADJUST. |
| | PLEASE SEE THERE ARE SOME ITEMS ON PLANS |
| | WHICH ARE NOT INCLUDED IN LOAD |
| | CALCULATIONS. |
| | PLEASE SEE WINE COOLER(DEDICATED?) |
| | PLEASE SEE 220.4 FOR LOADS OF |
| | RECESSEDLIGHTING. RECESSED LTS SHALL |
| | INDICATE THE WATTAGE OF FIXTURES IN |
| | ELECTRICAL LEGEND AND LOADS SHALL BE |
| | ABOVE GEN LTS LOADS. |
| | |
| | 6)NOTE: PLEASE SEE PANEL SCHEDULE/LOAD |
| | CALCS INDICATE 3-GDO'S, HOWEVER ONLY TWO |
| | ARE SHOWN ON PLANS? |
| | |
| | 7)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES 2-DISHWASHERS? YET ONLY ONE |
| | COULD BE LOCATED ON PLANS? AND ONLY ONE |
| | ON LOAD CALCS? |
| | PLEASE CORRELATE.220,215.5 |
| | |
| | 8)NOTE: PLEASE SEE 210.70 AND LS 101/ |
| | NFPA-101 CHAPTER 5-8.A LT FIXTURE OF |
| | SOME SORT WILL BE REQUIRED AT MEANS OF |
| | EGRESS, HALLWAYS/ STAIRWAYS. PLEASE SEE |
| | REDLINE DPLANS FOR LOCATIONS WHERE A MIN |
| | OF ONE LT FIXTURE WILL BE REQUIRED. |
| | PLEASE RM OFF KITCHEN, AND STAIRS WHERE |
| | A J-BOX IS SHOWN. |
| | |
| | 9)NOTE: PLEASE CORRELATE PLANS WITH |
| | RISER. RISER INDICATES A METER/MAIN |
| | COMBO AND PLANS INDICATE A SEPARATE |
| | METER AND A MAIN PANEL?? |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE PROVIDE ROOM AREA |
| | DESIGNATIONS ON ELECTRICAL PLANS. |
| | |
| | 11)NOTE: PLEASE SEE POSSIBLE COMMENTS |
| | FROM PLUMB/ MEACH, WHEATHER GAS WATER |
| | HEATER CAN BE LOCATED IN SMAE ENCLOSED |
| | CLOSET WITH AHU?? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESIATE IN CONTACTING THIS |
| | OFFICE. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |