Plan Review Details - Permit 05061909
Plan Review Stops For Permit 05061909
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-07 Cont ID  
Sent By alange Date 2005-09-07 Time 07:29 Rev Time 2.50
Received By alange Date 2005-09-06 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-02 Cont ID  
Sent By alange Date 2005-08-02 Time 07:04 Rev Time 3.50
Received By alange Date 2005-08-02 Time 07:04 Sent To  
Notes
2005-08-02 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUE HAS BE ADJUSTED TO
 $442,146.00.THE BALANCE OF PERMIT FEES
 DUE IS $3542.71.
  
 3.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 NOTE:PROPERTY IS IN FLOOD ZONE "A".
 THE FINISH FLOOR SHALL BE 6" ABOVE THE
 BASE FLOOD ELEVATION OF 7FT..
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 17:59 Rev Time 1.00
Received By dpalmer Date 2005-08-31 Time 17:59 Sent To P
Notes
2005-08-31 00:00:00*** UNSAT ***
  
 1)NOTE:IF ENGINEER ON PLANS IS NOT AN
 EMPLOYEE OF GARRISON DESIGN GROUP,PLEASE
 PROVIDE A SIGNED, SEALED LTR FROM
 ENGINEER WHICH STATES THIS.
 A CA/ LICENSE # IS NOT REQUIRED FOR
 GARRISON DESIGN GROUP AS THEY ARE NOT AN
 ARCHITECTUAL OR ENGINEERING FIRM TO THIS
 OFFICE'S UNDERSTANDING.
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLANS DO NOTE AIC RATING FOR MAIN ,
 HOWEVER PANELS DO NOT INDICATE SERIES
 RATINGS?
  
 3)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52. PLEASE SEE THESE ARE REDLINE DON
 PLANS AT LOCATIONS.
  
 4)NOTE: PLEASE SEE SD AS SHOWN IN
 KITCHEN MAY NOT BE CLOSER THAN 20'FROM
 COOKING APPLIANCES UNLESS MEETING THE
 EXCEPTIONS PERMITTED UNDER NFPA-72
 8-1.4.2
 PLEASE SEE SD FOR MASTER BEDROOM, MUST
 BE INSIDE MASTER BEDRM AREA. NFPA-72
 8-1.4.1.6.2, AND CHAPTER 2 FOR
 PLACEMENT. 3' FROM A PEAK ON SLOPED
 CEILING AND WITHIN 12" OF CEILING ON A
 FLAT CEILING. PLEASE SEE SD IS SHOWN IN
 HALLWAY WHICH ALSO CONTAINS A HEADER
 MORE THAN 12".
 THIS WAS ALSO REDLINED ON PLANS.
  
 5)NOTE: PLEASE SEE LOAD CALCULATIONS NOW
 SUBMITTED.
 PLEASE SEE TOTALS SHOWN AND LOADS
 INDICATED IN LOAD CALCS. SOME OF THESE
 #'S DO NOT CORRELATE. PLEASE SEE THESE
 ARE REDLINED.
 PLEASE ADJUST.
 PLEASE SEE THERE ARE SOME ITEMS ON PLANS
 WHICH ARE NOT INCLUDED IN LOAD
 CALCULATIONS.
 PLEASE SEE WINE COOLER(DEDICATED?)
 PLEASE SEE 220.4 FOR LOADS OF
 RECESSEDLIGHTING. RECESSED LTS SHALL
 INDICATE THE WATTAGE OF FIXTURES IN
 ELECTRICAL LEGEND AND LOADS SHALL BE
 ABOVE GEN LTS LOADS.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE/LOAD
 CALCS INDICATE 3-GDO'S, HOWEVER ONLY TWO
 ARE SHOWN ON PLANS?
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES 2-DISHWASHERS? YET ONLY ONE
 COULD BE LOCATED ON PLANS? AND ONLY ONE
 ON LOAD CALCS?
 PLEASE CORRELATE.220,215.5
  
 8)NOTE: PLEASE SEE 210.70 AND LS 101/
 NFPA-101 CHAPTER 5-8.A LT FIXTURE OF
 SOME SORT WILL BE REQUIRED AT MEANS OF
 EGRESS, HALLWAYS/ STAIRWAYS. PLEASE SEE
 REDLINE DPLANS FOR LOCATIONS WHERE A MIN
 OF ONE LT FIXTURE WILL BE REQUIRED.
 PLEASE RM OFF KITCHEN, AND STAIRS WHERE
 A J-BOX IS SHOWN.
  
 9)NOTE: PLEASE CORRELATE PLANS WITH
 RISER. RISER INDICATES A METER/MAIN
 COMBO AND PLANS INDICATE A SEPARATE
 METER AND A MAIN PANEL??
 215.5
  
 10)NOTE: PLEASE PROVIDE ROOM AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
  
 11)NOTE: PLEASE SEE POSSIBLE COMMENTS
 FROM PLUMB/ MEACH, WHEATHER GAS WATER
 HEATER CAN BE LOCATED IN SMAE ENCLOSED
 CLOSET WITH AHU??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESIATE IN CONTACTING THIS
 OFFICE.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By btrobaug Date 2005-07-13 Time 12:38 Rev Time 1.00
Received By btrobaug Date 2005-07-13 Time 11:01 Sent To M
Notes
2005-07-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} FIRM LICENSE NUMBER MUST BE ON THE
 TITLE BLOCK PER 61G15-23.002.
  
 2} THE LOAD CALCULATION EXCEEDS THE
 SERVICE RATING, IN VIOLATION OF 230.42.
  
 3} THE PANEL SCHEDULE INDICATES A 70 AMP
 BREAKER FEEDING THE SUB PANEL, RISER
 NOTE INDICATESS A 60 AMP. THE LOAD CALC
 LISTED AT 16839/240=70.16, THE FEEDER
 WIRE IS #6. PLEASE CORRELATE.
  
 4} THE SERVICE IS SHOWN AT TWO DIFFERENT
 LOCATIONS ON THE BUILDING, PLEASE
 INDICATE ACTUAL PROPOSED CONDITIONS.
  
 5} RECEPTACLES ARE REQUIRED OUTDOORS,
 FRONT AND REAR, PER 210.52(E).
  
 6} THE A/C DISCONNECTS APPEAR TO BE
 LOCATED IN CLEARANCE VIOLATION 110.26.
  
 7} SHOW LOCATION OF AHU#2 ON PLANS, SO
 DISCONNECT, LIGHT AND RECEPTACLE
 COMPLIANCE CAN BE DETERMINED.
  
 8} UPSTAIR BATHS (NO NUMBER) MUST HAVE A
 GFI RECEPTACLE WITHIN 3' OF THE BASINS
 PER 210.52(D), 210.8(A)(1).
  
 9} ALL ROOMS UPSTAIRS WITH TH EXCEPTION
 OF THE BATH ON THE SOUTH SIDE, ARE IN
 VIOLATION OF SPACING REQUIIREMENTS OF
 210.52(A)(1)&(2). SEE REVIEWED PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-25 Cont ID  
Sent By adarroug Date 2005-08-25 Time 09:48 Rev Time 0.00
Received By adarroug Date 2005-08-25 Time 09:47 Sent To E
Notes
2005-08-25 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-17 Cont ID  
Sent By adarroug Date 2005-08-17 Time 13:30 Rev Time 0.00
Received By adarroug Date 2005-08-17 Time 13:30 Sent To Z
Notes
2005-08-17 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 15:34 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 15:34 Sent To E
Notes
2005-07-12 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-02 Cont ID  
Sent By alange Date 2005-08-02 Time 07:10 Rev Time 0.00
Received By alange Date 2005-07-01 Time 18:14 Sent To  
Notes
2005-07-01 00:00:00TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By prafter Date 2005-09-06 Time 08:09 Rev Time 1.00
Received By prafter Date 2005-09-06 Time 08:09 Sent To B
Notes
2005-09-06 00:00:00MECH. PLAN REVIEW:
  
 1. MASTER BATH REQUIRES EXHAUST FAN IN
 AREAS TUB/ SHOWERS.2003 FBC/M
 402.3.1..
  
 2. GAS CLOTHES DRYER REQUIRES MANF.
 INSTRUCTIONS FOR COMBUSTION/MAKE UP AIR.
 2001 FBC/M CHAPTER 7
  
 3. GAS HOT WATER HEATER, LOCATER IN
 GARAGE CLOSIT REQUIRES COMBUSTION AIR
 AND A/C AHU MUST BE DUCTED R/A .
 2001 FBC/M CHAPTER 7.
  
 GARAGE CLOSIT MUST HAVE ADQUIT
 CLEARANCE TO REMOVE LARGEST PEACE OF
 EQUIPMENT AND ADQUIT SERVICE CLEARANCE.
 2003 FBC/M 306.1 CLEARANCES FOR
 MAINTENANCE AND REPLANCEMENT.
  
  
 4. RETURN AIR OUT OF SECOND FLOOR S/W
 BEDROOM MUST BE SAME SIZE AS SUPPLY AIR
 ON DUCTED RETURN AIR SYSTEM.
 2003 FBC/M 601.4 .
  
 5. A/C PLANS REQUIRE TO BE
 SIGINED/SEALED.
 FAC 61GI - 16.002 .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By hmoser Date 2005-07-20 Time 15:59 Rev Time 0.00
Received By hmoser Date 2005-07-20 Time 15:59 Sent To P
Notes
2005-07-20 00:00:00PLAN DENIED
 1) REFER TO SECTION 104.2.DRAWING AND
 SPECIFICATIONS FBC.
 2) REFER TO SECTION 307.2.4 FBC(M)
 AUXILIARY DRAIN PANS.
 3) PLEASE SIZE ALL DUCT ON PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-09-01 Cont ID  
Sent By jleech Date 2005-09-01 Time 09:14 Rev Time 0.75
Received By jleech Date 2005-09-01 Time 09:14 Sent To M
Notes
2005-09-01 00:00:00DENIED;
 1.AIR HANDLER MUST HAVE A DUCTED RETURN.
 GAS WATER HEATER CONNOT BE INSTALLED IN
 A PLENUM. FBC FUEL GAS SEC. 304.3.
 2.SHOW HOW W/H VENT IS TO BE INSTALLED.
 SHOW SIZE, MATERIAL AND VENT CLEARANCE
 PER. MANUFACTORS INSTALLATION
 INSTRUCTIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 09:30 Rev Time 0.33
Received By jleech Date 2005-07-23 Time 09:30 Sent To B
Notes
2005-07-23 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTES COMENT
 # 1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-24 Cont ID  
Sent By mmclean Date 2005-08-24 Time 16:35 Rev Time 0.00
Received By mmclean Date 2005-08-24 Time 16:35 Sent To I
Notes
2005-08-24 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/DECK.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 18:20 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 18:20 Sent To I
Notes
2005-07-11 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION OF THE
 CIRCULAR DRIVEWAY (LENGHT & WIDTH)
 2. MUST HAVE 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FRONT SETBACK
 (25FT)
 3. MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720