Plan Review Details - Permit 05061880
Plan Review Stops For Permit 05061880
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-30 Cont ID  
Sent By jwitmer Date 2006-05-30 Time 12:47 Rev Time 0.77
Received By jwitmer Date 2006-05-30 Time 12:47 Sent To PC
Notes
2006-05-30 00:00:00NEW PRODUCT APPROVALS:
 FL 3230 BESAM AUTO EXTERIOR DOOR
 ARCH 03-121108 STOREFRONT
 ARCH 01-0329.02 FIXED STOREFRONT

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-02-24 Cont ID  
Sent By jwitmer Date 2006-02-24 Time 16:16 Rev Time 1.66
Received By jwitmer Date 2006-02-24 Time 16:15 Sent To PC
Notes
2006-02-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061880
 ADD: 5400 S DIXIE HWY
 CONT: CONSILIUM ATLANTIC
 TEL: (954816-3351
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION
 ACTION: DENIED
  
  
 ****NOTE***
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 1) ARCH THE MIAMI-DADE NOA SUBMITTED
 UNDER ARCH / STOREFRONTS DOES NOT HAVE
 FLORIDA APPROVAL/ LOCALPRODUCT APPROVAL
 WOULD BE REQUIRED.
  
 2) ARCH SHOP DRAWINGS INDICATE THE
 DESIGN TO BE UNDER THE 2004 FBC, CORRECT
 TO 2001 FBC.
  
 3) SHOP DRAWINGS INDICATE USE OF
 STRUCTURAL MULLIONS BUT NO APPROVAL:
 1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 4)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 5) SHOP DRAWINGS INDICATE MULLIONS BY
 BESAM, THERE IS NO PRODUCT APPROVALS
 UNDER THIS NAME FOR MULLIONS.
 SEE RULE 9B72(29)(B) REQUIRING PRODUCT
 APPROVALS FOR MULLIONS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-25 Cont ID  
Sent By jwitmer Date 2006-01-25 Time 15:54 Rev Time 1.55
Received By jwitmer Date 2006-01-25 Time 15:53 Sent To  
Notes
2006-01-25 00:00:00REVISION # 2 11-01-05

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-10-03 Cont ID  
Sent By jwitmer Date 2005-10-03 Time 09:19 Rev Time 1.22
Received By jwitmer Date 2005-10-03 Time 08:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:03 Rev Time 0.77
Received By jwitmer Date 2005-08-07 Time 14:01 Sent To PC
Notes
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061880
 ADD: 5400 S DIXIE HWY
 CONT: CONSILIUM ATLANTIC
 TEL: (954)788-3884
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 THERE ARE PAGES MISSING THE RAISED SEAL,
 AND PAGES MISSING BOTH THE SEAL &
 SIGNATURE.
  
 4) ACCESSIBLE DRESSING ROOM ISMISSING
 BENCH:11-4.35.4 BENCH. EVERY ACCESSIBLE
 DRESSING ROOM SHALL HAVE A 24 IN. BY
 48 IN.(610 MM BY 1220 MM) BENCH FIXED
 TO THE WALL ALONG THE LONGER
 DIMENSION.THE BENCH SHALL BE MOUNTED
 17 IN. TO 19 IN.(430 MM TO 485 MM)
 ABOVE THE FINISH FLOOR.CLEAR FLOOR
 SPACE SHALL BE PROVIDED ALONGSIDE THE
 BENCH TO ALLOW A PERSON USING A
 WHEELCHAIR TO MAKE A PARALLEL TRANSFER
 ONTO THE BENCH.THE STRUCTURAL STRENGTH
 OF THE BENCH AND ATTACHMENTS SHALL
 COMPLY WITH ?11-4.26.3.WHERE INSTALLED
 IN CONJUNCTION WITH SHOWERS, SWIMMING
 POOLS, OR OTHER WET LOCATIONS, WATER
 SHALL NOT ACCUMULATE UPON THE SURFACE OF
 THE BENCH AND THE BENCH SHALL HAVE A
 SLIP-RESISTANT SURFACE.
  
 5) PLANS INDICATE THE USE OF POWER
 ACTIVATED AUTOMATIC SLIDING GLASS DOORS,
 PROVIDE COMPLIANCE WITH :
 1012.4 HORIZONTAL SLIDING DOORS.
 APPROVED AND LISTED HORIZONTAL SLIDING
 DOORS COMPLYING WITH THE FOLLOWING
 CONDITIONS MAY BE USED IN A MEANS OF
 EGRESS WHEN SPECIFICALLY PERMITTED BY
 1012.1.2, EXCEPTION 3.
 FOR A BIPARTING SLIDING DOOR IN THE
 EMERGENCY BREAK-OUT MODE, A DOOR LEAF
 LOCATED WITHIN A MULTIPLE-LEAF OPENING
 SHALL BE EXEMPT FROM THE MINIMUM 32 IN.
 (81-CM) SINGLE-LEAF REQUIREMENT OF IF A
 MINIMUM OF 32 IN.(81 CM) CLEAR OPENING
 IS PROVIDED BY ALL LEAFS BROKEN OUT.
  
 6) RESTROOMS: 1204.2 SURROUNDING
 MATERIALS. THE WALLS AND FLOORS OF ALL
 PUBLIC REST ROOMS SHALL BE LINED WITH
 NONABSORBENT MATERIAL TO A HEIGHT OF 4
 FT (1219 MM) ABOVE THE FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-09 Cont ID  
Sent By dpalmer Date 2006-02-09 Time 18:48 Rev Time 0.00
Received By dpalmer Date 2006-02-09 Time 18:24 Sent To PC
Notes
2006-02-09 00:00:00REDLINED PLANS :
  
 PLEASE SEE MDP IS SHOWN AS MLO, AND A
 MAIN CIRCUIT BREAKER WILL BE REQUIRED
 FOR THE MDP AS THIS SHOWS MORE THAN 6
 MAINS AND SPACES.
 230.70,230.71

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-20 Cont ID  
Sent By dpalmer Date 2005-12-20 Time 20:44 Rev Time 0.00
Received By dpalmer Date 2005-12-20 Time 20:22 Sent To  
Notes
2005-12-20 00:00:00****** UNSAT *****
  
 PLEASE SEE MINOR CHANGES NOTED ON
 REVISION COVER SHEET, HOWEVER THERE AHVE
 BEEN SOME MAJOR CHNAGES NOT ON ORIGINAL
 PLANS.
  
  
 1)NOTE: PLEASE SEE MANY WINDOWS ADDED
 NOT ON PREVIOUS ELECTRICAL PLANS.
 PLEASE SEE 210.62, 220.12A FOR MIN "SHOW
 WINDOWS" NOW REQUIRED ABOVE ALL WINDOWS.
 PLEASE ALSO ADJUST ALL CIRCUITING FOR
 THESE AS THEY ARE REQUIRED TO BE ON
 SEPARATE CIRCUITS.
  
 2)NOTE: PLEASE SEE A PANEL "E" IS SHOWN
 ON ON MDP , HOWEVER NO PANEL "E"
 SCHEDULE WAS SUBMITTED. IS THIS "EM" ON
 PLANS?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE MDP IS NOW SHOWN AS
 MLO ON SCHEDULE AND MCB ON RISER. PLEASE
 SEE 230.70,230.71 ETC, A MAIN CIRCUIT
 BREAKER WILL BE REQUIRED.
 PLEASE MAKE NESS CHANGES.
 PLEASE ALSO SEE MDP SEEMS TO INDICATE A
 "SPARE" 800A 3-P IN SPACE #7?? PLEASE
 VERIFY.
  
 4)NOTE: PLEASE KNOW, DUE TO THE SCOPE OF
 WORK BEING DONE AND THE REQUIREMENTS OF
 CHAPTER 34 OF THE FBC, ALL EXISTING AND
 NEW ELECTRICAL SHALL MEET CURRENT 2002
 NEC.
 PLEASE SEE ALL OCP SHOWN AS EXISITNG FOR
 EQUIPMENT, A/C 'S ETC. THESE SHOULD BE
 VERIFIED IN FEILD AND ADJUSTED IF OCP
 DOES NOT MEET MIN OR IS SIZED TOO HIGH
 FOR UNIT.
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By dpalmer Date 2005-09-30 Time 16:48 Rev Time 0.50
Received By dpalmer Date 2005-09-27 Time 21:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-07 Cont ID  
Sent By dpalmer Date 2005-07-07 Time 12:26 Rev Time 1.50
Received By dpalmer Date 2005-07-07 Time 12:26 Sent To  
Notes
2005-07-07 00:00:00********** UNSAT ******
  
 1)NOTE: PLEASE SEE MISSING TITLE
 BLOCK/TITLE BLOCK INFORMATION AS
 REQUIRED UNDER FAC 61G1-16.004,
 61G15-23.002, FS 471.025
 PLEASE ALSO SEE SOME ARCH SHEETS ARE NOT
 SEALED BY ARCH. FS 481.221
  
  
 2)NOTE: PLEASE CORRLETATE PLANS WITH
 SCOPE OF WORK ON APPLICATION ETC.
 PLEASE SEE PLANS CALL FOR GENERATOR
 ROOM? IS THERE GOING TO BE A GEN
 INSTALLED IN THIS SCOPE OF WORK? IF SO,
 PLEASE INCLUDE ALL INFORMATION AS
 REQUIRED.
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULES SUBMITTED.
 PANEL A/C-2?
 215.5
  
 4)NOTE: PLEASE SEE OCP FOR CU'S, PLEASE
 VERIFY SIZING. SEEMS EXCEED 150% OF FLA.
 ?
 215.5
  
 5)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 AND PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%. 220.10,220.11,220.13 ,
 215.3,230.42 ETC.
  
 6)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 7)NOTE: PLEASE INCLUDE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 8)NOTE: PLEASE CORRELATE PLANS WITH
 PANELS AND RISER DIAGRAM. PLEASE SHOW
 ALL PANELS ON PLANS.
 PLEASE SEE 110.26,408.7 ETC
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS SND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STMAPING. ONE SET OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:01 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-01-26 Cont ID  
Sent By mwennerg Date 2006-01-26 Time 14:33 Rev Time 0.00
Received By mwennerg Date 2006-01-26 Time 14:33 Sent To  
Notes
2006-01-26 00:00:00REVISION DATED 11/1/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By mwennerg Date 2005-09-29 Time 10:14 Rev Time 0.00
Received By mwennerg Date 2005-09-29 Time 10:14 Sent To  
Notes
2005-09-29 00:00:00LIFE SAFETY SHEETS STAMPED
  
 PASSED ON 7/11/05 BY MEC.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 14:14 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 11:24 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 11:24 Sent To P
Notes
2006-03-31 00:00:00TO "PSCHMITZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-16 Cont ID  
Sent By adarroug Date 2006-03-16 Time 11:48 Rev Time 0.00
Received By adarroug Date 2006-03-16 Time 11:48 Sent To P
Notes
2006-03-16 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 14:17 Sent To B
Notes
2006-02-13 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 15:34 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 15:34 Sent To E
Notes
2006-01-31 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 11:14 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 11:14 Sent To B
Notes
2006-01-22 00:00:00TO "JWITMER' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-01 Cont ID  
Sent By adarroug Date 2005-12-01 Time 14:44 Rev Time 0.00
Received By adarroug Date 2005-12-01 Time 14:44 Sent To  
Notes
2005-12-20 00:00:00TO "COMM" BD#3
2005-12-01 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 14:42 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 14:42 Sent To  
Notes
2005-09-22 00:00:00TO "COMM" BD#21
2005-09-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2005-07-01 Time 14:44 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#23

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-25 Cont ID  
Sent By pkrauss Date 2005-07-25 Time 13:42 Rev Time 0.25
Received By pkrauss Date 2005-07-25 Time 13:42 Sent To  
Notes
2005-07-25 00:00:00NO MECHANICAL CONTRACTOR OR WORK
 INDICATED WITH PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-03-31 Cont ID  
Sent By pschmitz Date 2006-03-31 Time 13:06 Rev Time 0.00
Received By pschmitz Date 2006-03-31 Time 13:06 Sent To PC
Notes
2006-03-31 00:00:00SHTA.01 REVISION TO REST ROONS #114,115

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-03-25 Cont ID  
Sent By pschmitz Date 2006-03-25 Time 06:34 Rev Time 0.00
Received By pschmitz Date 2006-03-25 Time 06:34 Sent To PC
Notes
2006-03-25 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1)SHT. A5.01 REVISION DATED 03-01-06
  
 ?11-4.17 TOILET STALLS.
 EXCEPTION: NEW CONSTRUCTION
 (1) THE STANDARD ACCESSIBLE
 RESTROOM STALL SHALL CONTAIN AN
 ACCESSIBLE LAVATORY WITHIN IT, THE
 SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17
 INCHES DEEP, NOMINAL SIZE, AND WALL
 MOUNTED.THE LAVATORY SHALL BE
 MOUNTED SO AS NOT TO OVERLAP THE
 CLEAR FLOOR SPACE AREAS REQUIRED
 BY ?11-4.17 (SEE FIGURE 11-30(A)
 AND FIGURE 11-30(E)) AND TO COMPLY
 WITH ?11-4.19 OF THE CODE.SUCH
 LAVATORIES SHALL BE COUNTED AS
 PART OF THE REQUIRED FIXTURE COUNT FOR
 THE BUILDING.
 (2) THE ACCESSIBLE WATER CLOSET
 SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-02-25 Cont ID  
Sent By pschmitz Date 2006-02-25 Time 06:32 Rev Time 0.00
Received By pschmitz Date 2006-02-25 Time 08:43 Sent To  
Notes
2006-02-25 00:00:00INFORMATION ON SITE PLAN #05110890

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-08-05 Cont ID  
Sent By pschmitz Date 2005-08-05 Time 10:12 Rev Time 0.00
Received By pschmitz Date 2005-08-05 Time 10:12 Sent To  
Notes
2005-08-05 00:00:00PLUMBING PLAN REVIEW FBC2001
 EXISTING REST RM'S PER SCOTT
 954-899-6081
 END OF COMMENTS,PES

Review Stop Z ZONING
Rev No 1 Status N Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 14:01 Rev Time 0.00
Received By lshapiro Date 2006-02-01 Time 15:58 Sent To  
Notes
2006-02-01 00:00:00APPROVAL OF THIS PERMIT IS SUBJECT TO
 REVISIONS TO PERMIT 05110890 (LANDSCAPE,
 SITE PLAN, ELEVATIONS)