Plan Review Details - Permit 05061769
Plan Review Stops For Permit 05061769
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-27 Cont ID  
Sent By jwitmer Date 2006-02-27 Time 15:58 Rev Time 2.22
Received By jwitmer Date 2006-02-27 Time 15:58 Sent To PC
Notes
2006-02-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061769
 ADD: 2090 N CONGRESS AVE
 CONT: DOOLEY MACK CONST.
 TEL: (561)635-6935
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION:
 ACTION: DENIED
  
 1) PLANS NEED TO INDICATE TO WHICH CODE
 THEY ARE DESIGNED TOO. IT APPEARS THIS
 IS AN ADDITION TO THE ORIGINAL BUILDING.
 IF THIS IS A REVISION TO THE ORIGINAL
 PERMIT PLEASE UP THE VALUE OF THE
 PROJECT.
  
 2) 2001 FL. BLD CODE 1606.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOOR
 B) EFIS SYSTEM/ DENSEGLASS
 C) EXTERIOR LOUVER
 D) ROOFING ASSEMBLIES
  
 4) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) NOTE ONPLAN INDICATES WORK TO BE
 COMPLETED AT N 130, IS THIS A NEW
 EXTERIOR MECHANICAL CLOSET OR A INTERIOR
  
 CLOSET?
  
 6) PROVIDE THE MINIMUM BLDG TYPE PER
 TABLE 500.
  
 7)1403.1.6 IN ORDER TO PROVIDE FOR
 INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE
 EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 11:37 Rev Time 0.77
Received By jwitmer Date 2005-12-01 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 13:31 Rev Time 0.77
Received By jwitmer Date 2005-08-07 Time 12:56 Sent To PC
Notes
2005-08-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061769
 ADD: 2090 N CONGRESS
 CONT: DOOLEYMACK CONSTRUCTORS
 TEL: (941)809-7272
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE ELECTRICAL PLAN INDICATES PHASING OF
 THIS PROJECT, WILL THE PATENTS BE MOVED
 OUT OF THE WORK AREA DURING EACH PHASE?
 IN PHASE II THE COMMON AREAS WILL BE
 REMODELED,WHEREWILL THE TEMPORARY
 COMMON AREAS BE ?
  
 3) PROVIDE A LIFE SAFETY PLAN FOR EACH
 PHASED WORK AREA.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-16 Cont ID  
Sent By dpalmer Date 2006-03-16 Time 17:41 Rev Time 0.00
Received By dpalmer Date 2006-03-16 Time 17:39 Sent To  
Notes
2006-03-16 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE THERE IS NOT ENOUGH
 INFORMATION FOR REVIEW FOR ELECTRICAL.
 PLEASE REVISE AND COMPLETE ELECTRICAL
 REVISIONS TO WHAT NOW APPEARS TO BE AN
 ADDITION.
 215.5
  
 2)NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS ALSO WITH RESPECT TO VALUATION
 OF PROJECT TO BE INCREASED FOR NEW WORK.
 FBC 104.6.5/108.3
  
 3)NOTE: PLEASE SEE NOTES BELOW AS THESE
 ITEMS WERE REDLINED ON PREVIOUS PLANS
 AND NEED TO BE UPDATED AND CORRECTED
 WHEN SUBMITTING NEW REVISED ELECTRICAL
 PLANS.
  
 **************************************
 *** NOTED***
  
 ALL ELECTRICAL SERVICE SHOWN IS EXSITNG,
 INCLUDING GENERATOR.
 REDLINED CONSTRICTION SPEC BOOKS, AS
 GENERATOR IS MENTIONED.
  
 REDLINED NFPA-72, TO BE 2002, 1999
 REFERENCED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-16 Cont ID  
Sent By dpalmer Date 2005-11-16 Time 07:56 Rev Time 1.00
Received By dpalmer Date 2005-11-16 Time 07:14 Sent To  
Notes
2005-11-16 00:00:00*** NOTED***
  
 ALL ELECTRICAL SERVICE SHOWN IS EXSITNG,
 INCLUDING GENERATOR.
 REDLINED CONSTRUCTION SPEC BOOKS, AS
 GENERATOR IS MENTIONED.
  
 REDLINED NFPA-72, TO BE 2002, 1999
 REFERENCED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By dpalmer Date 2005-07-11 Time 19:53 Rev Time 1.75
Received By dpalmer Date 2005-07-11 Time 19:31 Sent To  
Notes
2005-07-11 00:00:00IN ELEC FOR REVIEW, NOTES TO FOLLOW.
 ********** UNSAT ************
  
 1)NOTE: PLEASE SEE IT IS UNCLEAR IF
 SERVICE SHOWN IS TO BE NEW OR EXSITING.
 RISER SEEMS TO INDICATE ALL NEW, HOWEVER
 THE FOUR PANEL SCHEDULES SUBMITTED
 INDICATE AS EXSITING?
 IF NEW, PLEASE SEE THE FOLLOWING.
  
 2)NOTE: PLEASE SEE MDP-2 SHOWN ON PLANS
 BUT NOT ON RISER?
 COULD NOT LOCATE WHAT IS SHOWN AS SECOND
 SERVICE "DP-6" ON PLANS FOR VERIFICATION
 OF GROUPING MAINS?
 230.76,230.79,230.72,215.5 ETC
  
 3)NOTE: PLEASE SEE MDP-2 DOES NOTE SEEM
 TO MEET 110.26
  
 4)NOTE: PLEASE SEE SPECBOOKSSUBMITTED
 SEEM TO INDICATE A NEW ATS, PANELS,
 GENERATOR ETC??
 IF NEW? PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR ATS, GEN , FUEL
 TANKS ETC. PLEASE BE SURE ALL LISTINGS
 ARE INDICATED BY A NRTL.
 110.4, 90.7, 225.31-225.36
 PLEASE SEE RISER DIAGRAM IN UNCLEAR FOR
 FEEDS TO ATS SWITCHES? GUTTERS, TAPS?
 240.21 ETC?
 LOCATION OF GEN , ATS ETC TO BE SHOWN ON
 ALL PLANS, INCLUDING A SITE PLAN TO BE
 SUBMITTED, SEEE ZONING COMMENTS.
  
 5)NOTE: PLEASE SEE NO INFORMATION FOR
 MDP-1 WAS GIVEN TO VERIFY SEC'S? PLEASE
 ALSO SEE 250.66 FOR SIZING OF GROUNDING
 ELECTRODE CONDUCTOR.
 215.5
  
 6)NOTE: PLEASE SEE LIGHTNING PROTECTION
 SYSTEM IS INDICATED IN SPEC BOOK,
 HOWEVER NO PLANS SUBMITTED. IF SYSTEM IS
 TO BE PERMITTED UNDER THIS SCOPE OF
 WORK, PLEASE SUBMIT COMPLETE PLANS FOR
 PROPOSED SYSTEM.
  
 7)NOTE: PLEASE SEE PAGE 16470 OF SPEC
 BOOK WHICH REFERENCES A 2000 NFPA-70
 (NEC)> PLEASE SEE WE ARE UNDER THE 2002
 NEC WHICH WAS ADOPTED JULY 1ST, 2003.
 PLEASE ALSO SEECODES REFERENCED ON
 SOME LOCATION ON PLANS/IN NOTES ARE PER
 1999 NEC. , (384) NOTE #6 GEN NOTES.
  
 8)NOTE: PLEASE SEE "IF NEW", PLEASE
 SUBMIT COMPLETE LOAD CALCULATIONS BASED
 ON MIN AS SETFORTH IN 2002 NEC.
 PLEASE SHOW ALL CONTINOUS LOADS @ 125%
 215.3,230.42 ETC.
  
 9)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQUIRED TO BE ON TITLE
 BLOCK. FS 471.023
 PLEASE ALSO VERIFY ENGINEERING FIRM OF
 RECORD? TWO SHOWN?
 PLEASE ALSO SEE MISSING TITLE BLOCK
 INFORMATION REQUIRED ON TRADE SHEETS FOR
 ARCHITECT/FIRM. FAC 61G1-16.004. PLEASE
 SEE ALL INFORMATION AS SHOWN ON A-SHEETS
 SHOULD ALSO BE SHOWN ON TRADE TITLE
 BLOCKS.
 PLEASE BE SURE ALL SEALS ARE CLEAR AND
 VISABLE WITH ALL INFORMATION AS SETFORTH
 UNDER FS 471.025,AND FS 481.221, PLEASE
 SEE SOME SEALS ARE NOT VER READABLE.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S)>
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERNCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-03-24 Cont ID  
Sent By mwennerg Date 2006-03-24 Time 15:52 Rev Time 0.00
Received By mwennerg Date 2006-03-24 Time 15:52 Sent To  
Notes
2006-03-24 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING INTENDED WORK AND PROVIDE
 CLARIFICATION.
  
 2) ANY CHANGES TO THE ORIGINAL FIRE
 SPRINKLER REMODEL SHALL BE REFLECTED ON
 THE SEPARATE SHOP DRAWINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-11-15 Cont ID  
Sent By mwennerg Date 2005-11-15 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2005-11-15 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By mwennerg Date 2005-07-13 Time 10:06 Rev Time 0.00
Received By mwennerg Date 2005-07-13 Time 10:06 Sent To  
Notes
2005-07-13 00:00:00******DENIED******
  
 1) FIGURE A-4 ILLUSTRATES A PROPOSED
 REMOVAL PLAN. IT IS PRESUMED THAT THIS
 REFERENCES THE SECOND FLOOR. PLEASE SHOW
 THIS ON THE DRAWING.
  
 2) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3) THE SPEC MANUAL REFERENCES A FIRE
 WATCH. A REQUIRED FIRE WATCH MUST BE
 APPROVED BY THE CITY FIRE MARSHAL. THE
 APPROVED FIRE WATCH SHALL BE IN
 ACCORDANCE WITH LOCAL REQUIREMENTS AND A
 WRITTEN POLICY WILL BE AVAILABLE TO
 ASSIST WITH THE PROCESS.
  
 4) THE DRAWINGS DON'T SHOW ANY ENCLOSURE
 RATING FOR ELEVATOR #2 AND ASSOCIATED
 EQUIPMENT ROOM. PLEASE SHOW ALL EXISTING
 VERTICAL ENCLOSURE RATINGS.
  
 5) NEW DUCT SMOKE DETECTORS WHERE
 PROVIDED MUST BE WIRED TO THE FIRE ALARM
 SYSTEM TO INITIATE A GENERAL FIRE ALARM
 IN ADDITION TO FAN SHUT DOWN.
  
 6) PLEASE SHOW THE LOCATIONS OF NEW AND
 OR EXISTING ILLUMINATED EXIT SIGNS AND
 EMERGENCY LIGHTING FACILITIES.
  
 7) WILL THIS WORK IMPACT EXISTING
 BUILDING LIFE SAFETY EQUIPMENT?
  
 8) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE SPRINKLER AND
 FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 09:14 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 09:14 Sent To M
Notes
2007-03-13 09:14:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 13:30 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 13:30 Sent To  
Notes
2006-03-16 00:00:00TO "COMM" BD#27
2006-02-28 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-24 Cont ID  
Sent By adarroug Date 2006-02-24 Time 09:16 Rev Time 0.00
Received By adarroug Date 2006-02-24 Time 09:16 Sent To B
Notes
2006-02-24 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 17:19 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 17:19 Sent To M
Notes
2005-12-05 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-03 Cont ID  
Sent By adarroug Date 2005-10-03 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-10-03 Time 14:06 Sent To  
Notes
2005-10-12 00:00:00TO "COMM" BD#31
2005-10-03 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 13:49 Rev Time 0.00
Received By jwitmer Date 2005-07-01 Time 16:53 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#38

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-04-02 Cont ID  
Sent By hmoser Date 2007-04-02 Time 10:02 Rev Time 0.00
Received By hmoser Date 2007-04-02 Time 10:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-10-31 Cont ID  
Sent By pkrauss Date 2006-10-31 Time 07:35 Rev Time 0.00
Received By pkrauss Date 2006-10-31 Time 07:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-04-03 Cont ID  
Sent By pkrauss Date 2006-04-03 Time 13:21 Rev Time 0.00
Received By pkrauss Date 2006-04-03 Time 13:21 Sent To  
Notes
2006-04-03 00:00:00PROVISO:
 1.AHU CLOSET SHALL COMPLY WITH 2004
 FMC 603.9.
  
 2.MECHANICAL REVISION REQUIRED FOR THE
 RECONFIGURATION OF THE DUCTWORK.
  
 3.OVERFLOW PROTECTION REQUIRED IN
 ACCORDANCE WITH 2001 FMC 307.2.3 &
 307.2.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-13 Cont ID  
Sent By hmoser Date 2005-12-13 Time 07:32 Rev Time 0.00
Received By hmoser Date 2005-12-13 Time 07:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-11-15 Cont ID  
Sent By pkrauss Date 2005-11-15 Time 06:58 Rev Time 0.55
Received By pkrauss Date 2005-11-15 Time 06:58 Sent To  
Notes
2005-11-15 00:00:00DENIED:
 1.IN ACCORDANCE WITH FAC 61G15-23.002
 (2), ENGINEER SHALL HAVE PRINTED NAME &
 LICENSE NUMBER INDICATED ON THE TITLE
 BLOCK.
  
 2.PLAN SHEET M-1; AHU-N102 INDICATES
 THE NEW CONDENSATE TERMINATING INTO A
 HUB DRAIN.PER THE CITY CODE SEC.
 90-125 (B)(5), THE CONDENSATE SHALL NOT
 TERMINATE INTO THE SANITARY DRAIN.
 PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By hmoser Date 2005-07-28 Time 14:58 Rev Time 0.00
Received By hmoser Date 2005-07-28 Time 14:58 Sent To  
Notes
2005-07-28 00:00:00PLAN DENIED
 .1) PLEASE REFER TO SECTION 7.1.3.2.1
 NFPA 101 PENETRATION IN STAIR WELLS.
 2) NEED FIRE DAMPER IN ROOM N103.
 3) PLEASE SUBMIT EQUIPMENT MODEL NUMBER
 AND SEER ON PLAN
 4) PLEASE SUBMIT FRESH AIR CALCULATIONS
 ON PLAN.
 5) PLEASE SUBMIT ENERGY CALCULATIONS
 PLAN REVIEW BY HAROLD MOSER 651-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-08-04 Cont ID  
Sent By pschmitz Date 2005-08-04 Time 19:01 Rev Time 0.00
Received By pschmitz Date 2005-08-04 Time 19:01 Sent To  
Notes
***NONE***