Plan Review Details - Permit 05061756
Plan Review Stops For Permit 05061756
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-06-29 Cont ID  
Sent By jhiggins Date 2005-06-29 Time 12:38 Rev Time 0.00
Received By jhiggins Date 2005-06-29 Time 12:38 Sent To  
Notes
2005-06-29 00:00:00PARCEL FILE NEEDS PCN UPDATE; ADDRESS IS
 OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-24 Cont ID  
Sent By shill Date 2005-07-24 Time 16:24 Rev Time 1.50
Received By shill Date 2005-07-24 Time 15:14 Sent To  
Notes
2005-07-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)PROVIDE A REASONABLE VALUE FOR THIS
 JOB OR AN ESTIMATE WILL BE DONE FOR YOU
 USING MARSHALL & SWIFT.
  
 4.)DECLARE A BUILDING CONSTRUCTION
 TYPE FBC CHAPTER 6 AND INDICATE THAT
 THIS IS A SPRINKLED BUILDING.
  
 5.)AN OWNER/BUILDER CANNOT DO THE WORK
 WITH A VALUE OF OVER $25,000 FS489.
  
 5.)NO FIRE SPRINKLER INFORMATION WAS
 PROVIDED FBC*104.3.1.1(5).
  
 6.)DECLARE AN OCCUPANCY FBC CHAPTER 3.
  
 7.)THE UPSTAIRS BATHROOM IS TO BE
 ADAPTABLE, FBC11-4.1.3(11).
  
 8.)PROVIDE AREA CALCULATIONS; EXISTING
 SPACE, PROPOSED NEW SPACE.
  
 9.)ENERGY CALCS REQUIRED, FBC13.
  
 10.) TWO MEANS OF EGRESS FROM THE
 MEZZANINE REQUIRED, FBC1005.7.1.
  
 11.)SEE FBC1005.7.3.EGRESS STAIRS
 MAY BE OPEN WHEN ALL CONDITIONS ARE MET.
 ONE OF THE CONDITIONS IS THAT THE SPACE
 BENEATH THE MEZZANINE IS OPEN.THIS IS
 NOT THE CASE DUE TO THE BATHROOM AND
 UTILITY ROOM WALLS PARTIALLY ENCLOSING
 THE SPACE UNDER THE MEZZANINE.
  
 12.)SEE ALSO FBC1005.7.3(4).THE
 MEZZANINE CANNOT BE USED FOR SLEEPING
 PURPOSES.PLEASE CLEARLY NOTE ON THE
 PLAN IF YOU PLAN TO MEET ALL CONDITIONS
 OF FBC1005.7.3.
  
 13.)PROVIDE A FLOOR FRAMING PLAN.
  
 14.)PROVIDE DETAILS FOR THE HANDRAIL
 AND GUARDRAIL, FBC1608.2, FBC1007.2,
 FBC1007.5, FBC1015, FBC11-4.9.THE
 HANDRAIL EXTENSIONS ARE NOT SHOWN AT THE
 BOTTOM OF THE STAIRS ON THE FLOOR PLAN.
  
 15.)THE STAIRS ARE TO COMPLY WITH
 FBC1007 (FBC1005.7.3).THE TREADS ARE
 TO BE A MINIMUM OF 11IN, FBC1007.3.1.
 THEY ARE SHOWN AT 10IN. ON THE
 STRUCTURALS.
  
 16.)SPECIFY FLOOR DESIGN LOAD, FBC16.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 19:09 Rev Time 0.33
Received By dpalmer Date 2005-07-06 Time 19:09 Sent To  
Notes
2005-07-06 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE COMPUTER SYSTEM SHOWS
  
 HALSEY& GRIFFITH INC AS OWNERS OF
 RECORD. OWNER INFORMATION MUST BE
 UPDATED.
 PLEASE SEE FOLLOWING COMMENT TO WHEATHER
 OR NOT AN OWNER/BUILDER MAY BE PULLED
 FOR SCOPE OF WORK AND LOCATED IN A
 COMMERCIAL BLDG.
  
 2)NOTE: PLEASE SEE BLDG VALUATION IS TO
 BE BASED ON ALL LABOR AND MATERIALS AT
 FAIR MARKET VALUE.
 FBC 104.6.5
 PLEASE SEE BLDG REVIEW COMMENTS. IF
 VALUATION IS OVER $25K, THIS MAY NOT BE
 DONE BY O/B.
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE INCLUDE SIZE OF EXISTING OR NEW
 PANEL(S) SERVICE ETC.
 PLEASE INCLUDE LOAD CALCUALTIONS FOR
 ADDED LOAD TO NEW OR EXISTING.
 PLEASE SEE 220.12 FOR TRACK LIGHTING
 LOADS.
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125%.
 220.10,220.11,220.13,215.3,230.42,215.5
 ETC.
  
 4)NOTE: PLEASE SPECIFY USE OF UNIT/
 STORAGE AREA ETC.
 PLANS APPEAR TO SHOW AN OFFICE USE OF
 SOME TYPE ON UPPER LEVEL?
  
 6)NOTE: PLEASE CLARIFY NEW OR EXSITING
 SIGN CIRCUIT? 600.5
  
 7)NOTE: PLEASE SEE PLANS MENTIONS NEW
 "RECESSED LTS" HOWEVER, PLANS FOR AREA
 DO NOT APPEAR TO SHOW NY CEILING
 DETAILS?
  
 8)NOTE: PLEASE SEE MISSING CONTROL OF
 EGRESS LIGHTING FOR STAIRWAY.
 LS 101 5-8, 7-9
 SEE POSSIBLE FIRE REVIEW COMMENTS FOR
 ANY EM/EXT LTS WHICH MAY BE REQUIRED.
 3-WAY SW?
  
 9)NOTE: PLEASE SEE BLDG REVIEW NOTES,
 ADDRESS ON PLANS MENTIONS;
 "OLD" OKEECHOBEE RD". PLEASE KNOW, THIS
 SHOULD READ "OKEECHOBEE RD".
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL/OLD VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 10:44 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 10:29 Sent To  
Notes
2005-07-11 00:00:001. WHAT WILL THE MEZZANINE BE USED FOR.
  
 2. WHAT IS THE PROPOSED OCCUPANT LOAD
 FOR THE MEZZANINE.
  
 3. PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 4. NO EMERGENCY LIGHTING OR EXIT
 SIGNS SHOWN FOR THE MEZZANINE.
  
 5. PLEASE EXPLAIN TEN (10) INCH TREADS
 SHOWN FOR STAIRS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER.
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-06-29 Time 10:23 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#19
2005-06-29 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-05 Cont ID  
Sent By jleech Date 2005-08-05 Time 08:25 Rev Time 0.25
Received By jleech Date 2005-08-05 Time 08:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By kstevens Date 2005-08-04 Time 18:32 Rev Time 1.33
Received By kstevens Date 2005-08-04 Time 17:45 Sent To  
Notes
2005-08-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1. SHT A-1 BATHROOM FOR THE MEZZANINE
 SHALL BE ACCESSIBLE PER SECTION
 11-4.1.3(11). - SUBMIT A DETAIL FOR THE
 BATHROOM SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, 11-4.21,
 11-4.22 AND ALL SUBSECTIONS.
 2. SUBMIT A SANITARY RISER ISOMETRIC
 SHOWING ALL PIPE SIZES, TRAPS, VENTS AND
 POINTS OF CONNECTION AND TERMINATION.
 SECTION 104.3.1.1.
 3. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM SHOWING ALL PIPE SIZES, VALVES
 ECT. SHOW POINT OF CONNECTION. SECTION
 104.3.1.1.
 4. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BUILDING. SECTION
 608.13.2.
 5. PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A SERVICE SINK ARE REQUIRED IN A
 STORAGE OCCUPANCY. PLEASE INDICATE IF
 EXISTING FIXTURES ARE LOCATED IN THE
 BUILDING. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]