Plan Review Details - Permit 05061711
Plan Review Stops For Permit 05061711
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By rmcdouga Date 2005-08-03 Time 09:34 Rev Time 0.00
Received By rmcdouga Date 2005-08-03 Time 09:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-07 Cont ID  
Sent By rmcdouga Date 2005-07-07 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2005-07-07 Time 09:37 Sent To  
Notes
2005-07-07 00:00:00DENIED
  
 1) CLARIFY WHAT IS TO BE DONE WHERE THE
 FIRE RATED DOOR AND SECTION OF FIRE
 RATED WALL ARE BEING DEMOED AT THE EXIT
 CORRIDOR.
  
 2) SPECIFY THE RATING OF THE CORRIDOR
 WALL AND IF THE BUILDING HAS AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM.
  
 3) FBC 1004.2 REQUIRES TWO EXITS FROM
 THE TENNANT SPACE BECAUSE THE TRAVEL
 DISTANCE TO THE EXIT ACCESS EXCEEDS 75'.
  
 4)FBC 1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.EXCEPTION
 #2 ALLOWS THIS TO BE REDUCED TO 1/3 OF
 THE LENGTH IF BUILDING HAS AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM. SPECIFY THE
 TRAVEL DISTANCES TO THE EXITS. DOORS
 SHOULD BE RELOCATED TO COMPLY WITH THIS
 SECTION.
  
 5) SPECIFY HOW THE FIRE RATING AND
 CAPACITY OF THE EXIT CORRIDOR WILL
 MAINTAINED DURING CONSTRUCTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By dpalmer Date 2005-08-03 Time 09:42 Rev Time 0.25
Received By dpalmer Date 2005-08-03 Time 09:42 Sent To  
Notes
2005-08-03 00:00:00ELECTRICAL DEMO ONLY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-30 Cont ID  
Sent By dpalmer Date 2005-06-30 Time 19:55 Rev Time 0.10
Received By dpalmer Date 2005-06-30 Time 19:52 Sent To  
Notes
2005-06-30 00:00:00ELECTRICAL DEMO ONLY.
 ELECTRICAL PERMIT REQUIRED.
 STAMPED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By mwennerg Date 2005-08-03 Time 10:30 Rev Time 0.00
Received By mwennerg Date 2005-08-03 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 08:44 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 08:44 Sent To  
Notes
2005-07-11 00:00:001. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 2. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3. SUITABLE EXITS ARE TO BE PROVIDED
 DURING CONSTRUCTION.
  
 4. PLEASE SEE NOTES FROM BUILDING
 PLAN REVIEWER.
  
 5. ALL FIRE AND LIFE SAFETY SYSTEMS OR
 DEVICES SHALL BE MAINTAINED DURING
 DEMOLITION ACTIVITIES.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 11:40 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 11:38 Sent To  
Notes
2005-07-22 00:00:00TO "BOB" #3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-12 Cont ID  
Sent By rmcdouga Date 2005-07-12 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2005-06-29 Time 15:55 Sent To  
Notes
2005-06-29 00:00:00TO "INT REMOD" BD#1
 INT DEMO

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By rmcdouga Date 2005-08-03 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2005-08-03 Time 10:09 Sent To  
Notes
2005-08-03 00:00:00DEMO ONLY. NO DEAD ENDS ALLOWED -
 SECTION 704.5. PLUMBING PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By kstevens Date 2005-07-06 Time 07:16 Rev Time 0.25
Received By kstevens Date 2005-07-06 Time 07:16 Sent To  
Notes
2005-07-06 00:00:00DEMO ONLY - NO DEAD ENDS ALLOWED.
 SECTION 704.5. -PLUMBING PERMIT
 REQUIRED.