Plan Review Details - Permit 05061696
Plan Review Stops For Permit 05061696
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2009-07-27 Cont ID  
Sent By rmcdouga Date 2009-07-27 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2009-07-27 Time 16:01 Sent To  
Notes
2009-07-27 16:27:57REVISION TO CHANGE PRODUCT APPROVALS IS DENIED.
  
 1) SUBMIT TWO COPIES OF AN EXTERIOR DOOR AND WINDOW
 SCHEDULE THAT IS COORDINATED WITH THE NUMBERING SYSTEM
 USED ON THE PLANS. SPECIFY THE DOOR SIZES AND SWINGS,
 AS WELL AS, THE WINDOW TYPES AND SIZES ON THE SCHEDULE.
  
 2) CIRCLE THE APPROPRIATE WINDOW SIZES, GLASS TYPE AND
 DESIGN PRESSURES ON THE PRODUCT APPROVALS FOR THE
 WINDOWS THAT WILL BE INSTALLED.
  
 3) CIRCLE THE DOOR TYPES, GLASS TYPE AND DESIGN
 PRESSURES FOR THE DOORS THAT WILL BE INSTALLED.
  
 4) CIRCLE THE MULLION SPANS, THE WIDTH AND DESIGN
 PRESSURE FOR THE MULLIONS THAT WILL BE INSTALLED.
  
 5) SOME OF THE PRODUCT APPROVAL DESIGN PRESSURES ARE
 LOWER THAN THE REQUIRED OPENING PRESSURES SPECIFIED ON
 THE PLANS. PROVIDE PRODUCT APPROVALS FOR COMPONENTS
 WITH ADEQUATE DESIGN PRESSURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-01-28 Cont ID  
Sent By rmcdouga Date 2009-01-28 Time 07:50 Rev Time 0.00
Received By rmcdouga Date 2009-01-28 Time 06:47 Sent To  
Notes
2009-01-28 09:05:19NOTE: ALTHOUGH THE LOADS ON THE ROOF FRAMING PLAN ON
 S-103 ARE LOW FOR SOME OF THE TRUSSES, THE CONNECTORS
 SPECIFIED IN THE SCHEDULE ON S-601 ARE ADEQUATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-10-24 Cont ID  
Sent By lmartine Date 2008-10-24 Time 09:58 Rev Time 0.00
Received By lmartine Date 2008-10-24 Time 09:58 Sent To  
Notes
2008-10-24 09:59:12APPROVED FLOOR REVISION SUBMITTAL OK LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-05-16 Cont ID  
Sent By lmartine Date 2008-05-16 Time 10:46 Rev Time 0.00
Received By lmartine Date 2008-05-16 Time 10:10 Sent To  
Notes
2008-05-16 10:22:24CANNOT APPROVE NEW STRUCTURAL ENGINEERS SUBMITTAL. RAS
 IS THE ENGINEER OF RECORD.
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-21 Cont ID  
Sent By lmartine Date 2007-02-21 Time 17:25 Rev Time 0.00
Received By lmartine Date 2007-02-21 Time 17:25 Sent To  
Notes
2007-01-16 13:43:44NEW SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-05 Cont ID  
Sent By alange Date 2006-07-05 Time 14:05 Rev Time 2.00
Received By alange Date 2006-07-05 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-12 Cont ID  
Sent By alange Date 2005-10-12 Time 13:39 Rev Time 2.00
Received By alange Date 2005-10-12 Time 11:01 Sent To  
Notes
2005-10-12 00:00:00PLAN REVIEW:
  
 ITEMS REQUIRED TO SUBMIT PLANS FOR
 PERMITTING:
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. WEATHERSHIELD PRODUCT APPROVALS
 SUBMITTED WITH THIS APPLICATION REQUIRE
 THE FOLLOWING STATE PRODUCT APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By alange Date 2005-08-03 Time 09:58 Rev Time 4.50
Received By alange Date 2005-08-02 Time 16:47 Sent To  
Notes
2005-08-03 00:00:00PLAN REVIEW:
  
 ITEMS REQUIRED TO SUBMIT PLANS FOR
 PERMITTING:
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR THE FOLLOWING.
 ROOFING PRODUCTS, EXTERIOR DOORS,
 WINDOWS, IMPACT PROTECTION, LINTELS AND
 STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SLAB WITH GENERATOR, A/C AND POOL
 EQUIPTMENT SHALL BE AT 7'6" NGVD.
  
 5.SUBSURFACE EXPLORATION REPORT
 RECOMMENDS A 10 MIL VAPOR BARRIER
 SYSTEM.PLANS SHOW 6MIL.
  
 6.SUBMIT A SPIRAL STAIR DETAIL SHOWING
 COMPLIANCE WITH FBC 1007.8.2.1
  
 7.PAGE A-7.1 DOOR AND WINDOW SSCHEDULE
 IS MISSING.
  
 8.BUILDING SPECIFICATIONS SHOW A TYPE
 IV UNPROTECTED BUILDING.ACCORDING TO
 TABLE 500 THE MAX. ALLOWABLE HEIGHT WITH
 OUT SPRINKLERS IS 2 STORIES.
 SHOW HOW COMPLIANCE WITH THIS SECTION
 WILL BE MADE.
  
 9.SHOW WINDOW AND DOOR PRESSURES IN
 ACCORDANCE WITH FBC CHAPTER16.
  
 NOTE:NEW CODE CYCLE CHANGE STARTS
 OCTOBER 1, 2005.APPLICATION FOR
 PERMITTING SHOULD BE SUBMITTED BEFORE
 THEN TO BE ON THE 2001 FBC.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-02-22 Cont ID  
Sent By dpalmer Date 2007-02-22 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2007-02-22 Time 10:34 Sent To PC
Notes
2007-02-22 11:40:37**REDLINED/REVISION NEEDED **
  
 ** PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE AIC
 RATING OF THE EQUIPMENT BEING INSTALLED. PLEASE SEE A
 NOTE ON PLANS NOW MENTIONS 42K AND THE ELECTRICAL
 CONTRACTOR TO VERIFY WITH FPL ETC BEFORE ORDERING. THIS
 INFORMATION IS SOMETHING THAT IS REQUIRED TO BE
 VERIFIED AT THIS TIME. CONTACT SHOULD BE MADE TO THE
 SERVICE PLANNER FOR THE AREA AND THE INFORMATION CAN BE
 EASILY FOUND OUT.
 PLEASE SEE THAT THE RATINGS ON THE PLANS CALL FOR 42K
 MAIN AND 22K RATED MAINS ON THE LOAD SIDE OF THE HOUSE
 SERVICE MAIN AND 22K RATED BRANCH BREAKERS. ALL OF
 THESE RATINGS ARE PERMITTED AND ARE OK; HOWEVER PLEASE
 KNOW IF THESE RATINGS ARE SHOWN, THEN THIS IS WHAT
 WOULD BE REQUIRED TO BE INSTALLED. PLEASE VERIFY THIS,
 AS THIS IS ONLY BEING NOTED. CONSIDERATION TO THE COST
 OF THE RATED EQUIPMENT AND INSTALLATION OF 22K RATED
 BRANCH BREAKERS ETC MAY WANT TO BE TAKEN INTO
 CONSIDERATION.
 110.9.
  
 **PLEASE KNOW THAT SINCE THE LAST REVIEW OF THIS
 PROJECT, A MEETING WAS HELD AT THE SOUTHERN SECTION
 MEETING IN OCT 06 WHERE WE WERE DIRECTLY INFORMED BY
 NFPA THAT THE USE OF "SD" FOR SMOKE DETECTORS ON PLANS
 FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN THESE
 DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS OF
 SMOKE ALARMS WHICH WOULD BE SHOWN AS "SA"/SMOKE
 ALARMS".
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES; HOWEVER THIS WAS NOT A COMMENT
 FROM THIS AHJ OR REVIEWER BEFORE AS THIS INFORMATION
 WAS MADE AWARE TO ALL OF THE JURISDICTIONS PRESENT,
 MOST OF WHICH HAD ALSO ALWAYS ACCEPTED SD AND THE
 STATED SMOKE DETECTORS.
  
  
 THESE ITEMS ALONG WITH ANY OTHER REVISIONS ARE TO BE
 CORRECTED, SUBMITTED, REVIEWED AND STAMPED FOR JOBSITE
 BEFORE ANY ROUGH ELECTRICAL INPSECTION IS CALLED IN.
  
 IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-01-17 Cont ID  
Sent By dpalmer Date 2007-01-17 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2007-01-16 Time 12:47 Sent To P
Notes
2007-01-17 07:40:38** UNSAT**
  
 ** PLEASE SEE SOME COMMENTS FOR COORDINATION AND
 CHANGES ON PLANS NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW COMMENT #4.
  
  
 1) NOTE: PLEASE SEE ON THE PREVIOUS REVIEW IT WAS
 REQUESTED TO SUBMIT THE MANUFACTURE'S SPEC/CUT SHEETS
 FOR THE LIGHTING HOME AUTOMATION SYSTEM WHICH WAS GOING
 TO BE INSTALLED. A COVER LETTER MENTIONS ONE SYSTEM
 WHICH WOULD BE THE LUTRONWHICH MAY BE DONE WITH FOUR
 OR FIVE PANELS AND ONE SYSTEM WHICH COULD BE DONE WITH
 THREE PANELS.
 PLEASE SEE TWO COMPLETELY DIFFERENT PACKAGES FOR THESE
 SYSTEMS WERE SUBMITTED WITH ONLY ONE CONTAINING THE
 LISTING FROM A NRTL. PLEASE SEE THE PACKAGE FOR SYSTEM
 WHICH IS BEING CALLED A CRESTRON DID NOT SEEM IT
 CONTAINED ANY LISTINGS WHICH COULD BE READILY LOCATED
 ON SHEETS PROVIDED.
 ** PLEASE SEE ON THE OTHER HAND THE PLANS SHOWS 4
 LIGHTING CONTROL PANELS WHICH WOULD NOT CORRELATE WITH
 THE STATEMENT ON THE COVER SHEETS WHICH MENTIONS ONLY
 THREE PANELS ARE BEING USED (CRESTRON).
 PLEASE CORRELATE PLANS AND SUBMITTALS AND ONLY SUBMIT
 THE SYSTEM BEING PROPOSED.
 110.3, 90.7
 FBC 106.1.2 ADMIN SECTION.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE
 MANUFACTURE'S SPEC/CUT SHEETS FOR THE NEW PROPOSED ATS
 BEING INSTALLED. PLEASE SEE THIS WAS DONE, HOWEVER
 SPECS FOR AN ATS WERE SUBMITTED. PLEASE SEE THE PLANS
 NOW CONTAIN WHAT IS BEING SHOWN AS A MTS, WHICH IS
 BEING DONE?
 PLEASE CORRELATE THESE ALSO.
 90.7, 110.3, FBC 106.1.2 ADMIN SECTION.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE
 AIC RATING OF THE EQUIPMENT BEING INSTALLED. PLEASE SEE
 A NOTE ON PLANS NOW MENTIONS 42K AND THE ELECTRICAL
 CONTRACTOR TO VERIFY WITH FPL ETC BEFORE ORDERING. THIS
 INFORMATION IS SOMETHING THAT IS REQUIRED TO BE
 VERIFIED AT THIS TIME. CONTACT SHOULD BE MADE TO THE
 SERVICE PLANNER FOR THE AREA AND THE INFORMATION CAN BE
 EASILY FOUND OUT.
 PLEASE SEE THAT THE RATINGS ON THE PLANS CALL FOR 42K
 MAIN AND 22K RATED MAINS ON THE LOAD SIDE OF THE HOUSE
 SERVICE MAIN AND 22K RATED BRANCH BREAKERS. ALL OF
 THESE RATINGS ARE PERMITTED AND ARE OK; HOWEVER PLEASE
 KNOW IF THESE RATINGS ARE SHOWN, THEN THIS IS WHAT
 WOULD BE REQUIRED TO BE INSTALLED. PLEASE VERIFY THIS,
 AS THIS IS ONLY BEING NOTED. CONSIDERATION TO THE COST
 OF THE RATED EQUIPMENT AND INSTALLATION OF 22K RATED
 BRANCH BREAKERS ETC MAY WANT TO BE TAKEN INTO
 CONSIDERATION.
 110.9.
  
 4) NOTE:PLEASE KNOW THAT SINCE THE LAST REVIEW OF
 THIS PROJECT, A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF "SD" FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 "SA"/SMOKE ALARMS".
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES; HOWEVER THIS WAS NOT A COMMENT
 FROM THIS AHJ OR REVIEWER BEFORE AS THIS INFORMATION
 WAS MADE AWARE TO ALL OF THE JURISDICTIONS PRESENT,
 MOST OF WHICH HAD ALSO ALWAYS ACCEPTED SD AND THE
 STATED SMOKE DETECTORS.
 IF THE ONLY COMMENT ON THE PLANS WAS THIS, THE PLANS
 WOULD HAVE BEEN REDLINED FOR THE CORRECTIONS AND WOULD
 BE ISSUED WITH REVISIONS TO FOLLOW.
 PLEASE MAKE ADJUSTMENTS FOR THESE AS PLANS ARE COMING
 BACK FOR ZONING COMMENTS AND NOTES ABOVE.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 11.5.1.1, 11.8.3
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-17 07:02:332007-01-17 07:02:33
 IN PROGRESS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-22 Cont ID  
Sent By dpalmer Date 2006-06-22 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2006-06-21 Time 21:03 Sent To Z
Notes
2006-06-22 00:00:00******* UNSAT 3RD REVIEW *************
  
 ** PLEASE SEE THERE ARE COMMENTS FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED AND SOME NEW COMMENTS DUE TO
 PLAN CHANGES.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM THE PREVIOUS REVIEW AND
 ANY NEW NOTES ARE ADDED AT THE BOTTOM.
  
 ************* UNSAT ******************
  
 1)NOTE: NOTE #1 NO, PLEASE SE A4.2 STILL
 SHOWS THE SAME AS BEFORE.
  
 ** PREVIOUS NOTES**
 PLEASE SEE MAX HEIGHT FOR
 ELECTRICLA METERCAN PER SECTION 6 OF FPL
 SERVICE INSTALLATIONS GUIDELINES SHALL
 BE 6' TO THE CENTER OF METER.
 PLEASE SEE ELEVATION PLANS A4.2 CLEARLY
 SHOW THIS HIGHER.
  
 2)NOTE: NOTE #2 SMAE NOTE, ALSO AS
 ABOVE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MAX HEIGHT OF
 DISCONNECTING EQUIPMENT/SWITCHES SHALL
 BE 6'7" WITH OUT RESORTING TO LADDERS
 ETC.
 440.11, 100 (DEFINITIONS) ACCESSIBLE
 READILY)404.8
 PLEASE SEE THIS COMMENT IS FOR ALL
 ELECTRICAL EQUIPMENT ON ELEV ON A4.2
  
 3)NOTE: NOTE #3 NO, PLEASE SEE GENERATOR
 LOCATION IS NOT OK. AS OF THIS REVIEW
 PLEASE SEE OTHER NOTES AS EQUIPMENT
 LOCATION CAN NOT BE VERIFIED AS MOST
 GEN'S REQUIRED A MIN OF 3' CLEARENCE ON
 ALL SIDES AND SOME REQUIRE MORE. THERE
 ARE VERY FEW WHICH REQUIRE LESS.
 UNABLE TO VERIFY.
 A/C DISC'S APPEAR TO BE OK AS SHOWN.
  
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE MIN CLEARENCES
 REQUIRED ON SAME ELEVATION FOR ALL A/C
 DISC'S,GENERATOR, METER, ETC.?
 110.26.
  
 4)NOTE: OK.
  
 5)NOTE: OK.
  
 6)NOTE: OK.
  
 7)NOTE: OK.
  
 8)NOTE: OK, HOWEVER SEE NEW NOTES
 PERTAINING TO SD NOTES.
  
 9)NOTE: NOTE #9 NO, PLEASE SEE THAT SOME
 LTS ARE PERMITTED AS LONG AS ON A GFI
 PROTECTED CIRCUIT, HOWEVER PLEASE SEE
 AREAS ALOWWED FOR EXISTING AND NEW.
 PLEASE SEE THE HOUSE IS NEW AND MUST
 MEET ANY REQUIREMENTS FOR NEW
 CONSTRUCTION EVEN IF POOL IS EXISTING.
 PLEASE SEE RECEPTS MAY NOT BE WITHIN
 10FT OF POOL. (NO EXCEPTIONS!)
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE 680.22,680.22B ETC
 FOR MIN CLEARENCES FOR ELECTRICAL
 EQUIPMENT, DEVICES/RECEPTS AND LT
 FIXTURES FROM POOL IN NEW CONSTRUCTION.
 PLEASE SEE POOL HEATER, LTS ETC REDLINED
 ON PLANS.
 PLEASE SEE MIN 10' FOR RECEPTS.
 PLEASE ALSO SEE NOTES FOR LOADS ETC OF
 POOL EQUIPMENT.
 PLEASE NOTE: LT FIXTURES W/IN 5' SHALL
 BE 12' UP.(PLEASE SEE BACK PORCH)?
  
 10)NOTE: OK.
  
 11)NOTE; OK.
  
 12)NOTE: NOTE #12 NO.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT COMPLETE
 SPECS/CUT SHEETS FOR LIGHTING CONTROL
 PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE
 SCHEDULING FOR THESE.
 ALL SYSTEMS SHALL BE LISTED BY A NRTL.
 PLEASE ALSO SEE COMMENT PERTAINIG TO
 GEN. LOAD(S).
  
 13)NOTE: OK.
  
 14)NOTE: OK, STILL SHOWS A 24 CIRUCIT
 PANEL YET THIS IS SHOWN AS 200A'S??
  
 15)NOTE: OK.
  
 16)NOTE: OK.
  
 17)NOTE: NOTE #17 NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.**NUMBER OF FIX EXCEED GEN LT**
  
 18)NOTE: OK.
  
 19)NOTE: OK.
  
 20)NOTE: OK.
  
 21)NOTE: OK.
  
 22)NOTE: OK.
  
 23)NOTE: OK.
  
 24)NOTE: OK.
  
 25)NOTE: NOTE #25 NO? COULD NOT LOCATE
 THE REQUIRED DISCONNECT. APPEARS TO SHOW
 AN OUTLET/RECEPT ONLY??
  
 * PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 EMERGENCY DISCONNETC SWICTH TO BE
 LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT
 NO FURTHER THAN 50'.
 PLEASE SEE 680.41
  
 26)NOTE: OK.
  
 27)NOTE: OK.
  
 28)NOTE: NOTE #28 NO.
 ** PLEASE ALSO KNOW, "K" SWITCH IS NOT
 ACCEPTABLE IN LEIU OF THE REQUIRED
 DISCONNECTING MEANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE
 MANUFACTURE SPECS/CUT SHEETS FOR
 GENERATOR , ATS .
 PLEASE KNOW, GENERATOR CAN BE SUBMITTED
 UNDER SEPARATE PERMIT AT A LATER DATE
 WITH SEPARATE, SURVEY, PLANS, SPECS,
 FEES ETC., HOWEVER, SPECS FOR ATS ARE
 REQUIRED AT THIS TIME FOR REVIEW.
 PLEASE SEE PLANS AND RISER INDICATE THIS
 UNIT AS CONTAINING THE MAIN 1OF 1??
 PLEASE SEE230.76,230.79, 230.91,
 225.31-225.39 ETC
 WHICH REQUIRES THE MANUAL MEANS OF
 DISCONNECT TO BE LOCATED ON THE OUTSIDE
 AND RATED FOR THE LOAD SERVED ETC.
 UNABLE TO VERIFY CODE COMPLIANCE AT THIS
 TIME.
 (THIS WAS REQUESTED ON PREVIOUS REVIEW
 ALSO).
 PLEASE VERIFY IF ATS DOES CONTAIN THE
 MAIN OR DOES NOT AS THIS WILL AFFECT THE
 FOLLOWING.
  
 29)NOTE: OK.
  
 30)NOTE: OK, HOWEVER VERIFY THE #3 BEING
 SHOWN. SEE NEW COMMENTS WITH RESPECT TO
 CONDUIT FILL.
  
 31)NOTE: NOTE #31 NO,PLEASE SEE LOADS
 FOR GEN ON GEN LOAD SUMMARY DO NOT
 INDICATE AN AIR CONDITIONING LOADS??
 PLEASE SEE NOTE MENTIONS TO SHEDD LOADS
 BUT NO DETAIL WAS SUBMITED OR SHOWN.
 PLEASE VERIFY NO A/C LOADS AS THE LOAD
 SHOWN FOR GEN IS SHOWN AT 97A'S.
 PLEASE ALSO VERY HOW THE THE ENTIRE
 SERVICE IS BEING FED YET NOT ALL
 ELECTRICAL WHICH IS BEING SHOWN PANEL
 SCHEDULES ARE ON THE LOAD SUMMARY FOR
 THE GEN??
 215.5
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 SHEDDING DETAILS FOR AUTOMATION SYSTEM
 AS RISER DIAGRAM NOTES GENERATOR SHALL
 BE ADEQUATE FOR THE LOAD TO BE SERVED.
 702.5
 THIS IS REQUIRED AT THIS TIME, UNLESS
 GEN IS NOT PERMITTED AT THIS TIME.
 SEE PREVIOUS NOTES.
  
 32)NOTE: OK.
  
 33)NOTE: OK.
  
 34)NOTE: OK.
  
 35)NOTE: OK.
  
 ***** NEW NOTES *****
  
 36) NOTE: PLEASE SEE SD'S SHALL BE
 INSTALLED PER NFPA-72
 11.5.1.1,11.8.3.5,11.8.3
 PLEASE SEE NOTES MENITONS 12" FROM AIR
 SUPPLIES AND RETURNS. PLEASE SEE NFPA AS
 NOTED ABOVE WHERE NO SD'S AARE PERMITTED
 WITHIN 3' FROM SUPPLIES AND MIN 5' FROM
 RA BASED ON MANUFACTURES SPEC'S.
 PLEASE ADJUST ALL NOTES.
  
 37) NOTE: PLEASE SEE PLANS NOTES IN MANY
 LOCATIONS WITH REFERENCE TO THE "LATEST
 EDITION" OF THE CODE. THIS IS NOT
 PERMITTED AS THE LATEST EDITION WOULD BE
 THE 2004 FBC AND THE LATEST EDITION OF
 THE NEC HAS NOT BEEN ADOPTED BY THE
 STATE OF FLORIDA AS OF YET.
 PLEASE SEE THE FOLLOWING CODES SHALL BE
 REFLECTED ON PLANS AT A MIN ON
 ELECTRICAL SHEETS.
 IF REMAINING UNDER THE 2001 FBC THEN
 THE ELECTRICAL PLANS SHALL REFLECT THE
 2001 FBC, 2002 NFPA-70 (NEC), 2002
 NFPA-72, NFPA-101 2003 AT A MIN.
 PLEASE SEE OTHER REVIEWER(S) AND CODES
 TO APPLY.
  
 38) NOTE: PLEASE SEE A PREVIOUS NOTE
 MENTIONED THAT NOW THE "EQUIPMENT
 GROUNDING CONDUCTORS" ARE NOW SHOWN
 HOWEVER ARE SIZED AT #3'S?? PLEASE KNOW,
 THIS IS OK, ALTHOUGH THEY ARE ONLY
 REQUIRED TO BE SIZED PER 250.122 , BUT
 IF SHOWN ON PLANS THIS SIZE, THEN THIS
 IS WHAT WILL BE REQUIRED.
 ** PLEASE ALSO KNOW, BASED ON FEEDERS
 SHOWNA DN THE EQUIPMENT GROUNDING
 CONDUCTORS NOW SHOWN , PLEASE SEE MAX
 CONDUIT FILL PER TABLES 9, SCH 80.
 PLEASE ADJUST CONDUIT SIZES AS NEEDED.
 215.5
  
 39) NOTE: PLEASE SEE MISSING E-1 ON ONE
 SET OF ELECTRICAL PLANS.
  
 40) NOTE: PLEASE ALSO SEE ONE SET IS
 ALSO MISSING THE "RAISED" SEAL ON SOME
 "S" SHEETS.
 PLEASE KNOW, AS OF DEC 31ST, 2005 IT IS
 NO LONGER ACCEPTABLE USE ENGINEER'S
 SEALS WITH THE WORDING OF "CERTIFICATE".
 PLEASE SEE RULING AS PASSED BY THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 IN FEB 04 WHICH REQUIRES ALL ENGINEERS
 TO OBTAIN A NEW SEAL CONTAINING THE
 WORDING OF "LICENSE". AN EXTENSION WAS
 GIVEN TO DEC 31ST, 2005.
 SEE BUILDING REVIEW NOTES, THIS IS ONLY
 NOTED IN ELECTRICAL REVIEW FOR
 INFORMATIONAL PURPOSE AS AN FYI.
  
 41) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE THAT ALL COMMENTS FROM
 PREVIOUS REVIEWS MUST BE ADDRESSED.
  
 42) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT, SEE NEW MAINS NOW
 ADDED WHICH DO NOT INDICATERATINGS.
 110.9,215.5
  
 **PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ANY/ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
2006-06-21 00:00:00IN ELEC FOR REVIEW.
2006-06-16 00:00:00 
  
  
 SHEET E1 IS MISSING FROM ONE SET OF
 PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-07 Cont ID  
Sent By dpalmer Date 2005-10-07 Time 20:39 Rev Time 1.00
Received By dpalmer Date 2005-10-07 Time 19:01 Sent To M
Notes
2005-10-07 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE MAX HEIGHT FOR
 ELECTRICLA METERCAN PER SECTION 6 OF FPL
 SERVICE INSTALLATIONS GUIDELINES SHALL
 BE 6' TO THE CENTER OF METER.
 PLEASE SEE ELEVATION PLANS A4.2 CLEARLY
 SHOW THIS HIGHER.
  
 2)NOTE: PLEASE SEE MAX HEIGHT OF
 DISCONNECTING EQUIPMENT/SWITCHES SHALL
 BE 6'7" WITH OUT RESORTING TO LADDERS
 ETC.
 440.11, 100 (DEFINITIONS) ACCESSIBLE
 READILY)404.8
 PLEASE SEE THIS COMMENT IS FOR ALL
 ELECTRICAL EQUIPMENT ON ELEV ON A4.2
  
 3)NOTE: PLEASE SEE MIN CLEARENCES
 REQUIRED ON SAME ELEVATION FOR ALL A/C
 DISC'S,GENERATOR, METER, ETC.?
 110.26.
  
 4)NOTE: PLEASE SEE MISSING DISC'S FOR
 POOL EQUIPMENT ON THAT SIDE OF HOUSE.
 PLANS MENTIONS POOL EXISTING? PLEASE
 ALSO SEE LOAD CALCULATIONS MENTIONS EST
 LOAD? IF EXISTING, LOADS SHOULD BE
 KNOWN.
  
 5)NOTE: PLEASE SEE CABANA BLDG IS NOT
 PART OF MAIN HOUSE AND IS REQUIRED TO
 HAVE DISCONNECTING MEANS PER 225.31.
 PLEASE ALSO SEE GROUPING PER 225.34,
 PLEASE KNOW, IF MORE THAN 6 INDIVIDUAL
 CIRCUITS AT THIS DETACHED BLDG, A PANEL
 WILL BE REQUIRED AND A DISCONNECT OR MCB
 PANEL WILL BE REQUIRED.
 PLEASE ADJUST RISER DIAGRAM AND SEE NEXT
 NOTE.
  
 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDG.
  
 7)NOTE: PLEASE SEE MISSING SW AND LT AT
 CABANA BATH PER 210.70
  
 8)NOTE: PLEASE SEE SD'S WILL BE REQUIRED
 AT CABANA AT FIRST AND SECOND FLRS.
 FIRST FLR IS CONSIDERED AN ADAPTABLE
 SLEEPING RM WITH BATH RM.
 PLEASE ALSO SEE SD'S REQUIRED ON ALL
 LEVELS OF A MULTI-LEVEL BLDG.
 NFPA-72 11.5.1.1
  
 9)NOTE: PLEASE SEE 680.22,680.22B ETC
 FOR MIN CLEARENCES FOR ELECTRICAL
 EQUIPMENT, DEVICES/RECEPTS AND LT
 FIXTURES FROM POOL IN NEW CONSTRUCTION.
 PLEASE SEE POOL HEATER, LTS ETC REDLINED
 ON PLANS.
 PLEASE SEE MIN 10' FOR RECEPTS.
 PLEASE ALSO SEE NOTES FOR LOADS ETC OF
 POOL EQUIPMENT.
 PLEASE NOTE: LT FIXTURES W/IN 5' SHALL
 BE 12' UP.(PLEASE SEE BACK PORCH)?
  
 10)NOTE: PLEASE SEE PANEL SCHEDULE "C"
 INDICATES "POOL EQUIPMENT" AS 14.2KW,
 HOWEVER PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE FIGURED AT 125%.
 PLEASE SEE THIS APPEARS TO ONLY FEED ONE
 PIECE OF EQUIPMENT? COOULD NOT LOCATE
 POOL PUMP, LT ETC. IS THERE A POOL PANEL
 AND THE 2P 70A A SUB-FEED?
 PLEASE SEE IF THIS IS NOT ALREADY FIGURE
 AT CONTINUOUS LOAD, 70A OCP WOULD NOT BE
 LARGE ENOUGH. 215.3,230.42,680.9 ETC.
  
 11)NOTE; PLEASE SEE BLDG PLANS INDICATE
 A "WASHER AND DRYER" IN GARAGE AS
 FUTURE, HOWEVER ELECTRICAL PLANS SEEM TO
 SHOW THESE , BUT NOT NOTED FOR FUTURE,
 NOW ? NO ELECTRICAL DEVICES SHOWN.
 IF THESE UNITS ARE NOT GOING TO BE
 INSTALLED, PLEASE REMOVE FROM PLANS.
  
 12)NOTE: PLEASE SUBMIT COMPLETE
 SPECS/CUT SHEETS FOR LIGHTING CONTROL
 PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE
 SCHEDULING FOR THESE.
 ALL SYSTEMS SHALL BE LISTED BY A NRTL.
 PLEASE ALSO SEE COMMENT PERTAINIG TO
 GEN. LOAD(S).
  
 13)NOTE: PLEASE SEE PLANS CALL FOR
 CIRCUITING OF WHAT APPEARS TO BE THE
 ELEVATOR ON PANEL C-25, 27, HOWEVER
 PLEASE SEE PANEL "C" IS BEING SHOWN WITH
 ONLY 24 CIRCUITS??
 PLEASE SEE PANEL "D" SEEMS TO SHOW THIS.
 (MISPRINT).
  
 14)NOTE: PLEASE VERIFY CIRCUITING SHOWN
 FOR PANEL "C" AS BEING A 24 CIRCUIT
 PANEL AND ALSO BEING 200A?
 215.5
  
 15)NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL FROM GARAGE TO FRONT
 PORCH AREA. 210.70 (3-WAY?)
  
 16)NOTE: PLEASE CLARIFY CABANA LTS WHICH
 SEEM TO BE SHOWN AS "RECESSED LT"
 FIXTURES. PLEASE SEE PLANS CALL FOR A
 "WOOD DECK" ABOVE WHICH DOES SEEM TO
 DETAIL WHEATHER PROTECTION. AN OUTDOOR
 WP RECESSED IS NOT KNOWN OF AT THIS
 TIME. PLEASE ALSO VEIFY FAN LOCATION.
 IF THESE ARE OUTDOOR RAINTIGHT FIXTURES,
 PLEASE PROVIDE INFORMATION.
 90.7,110.3
  
 17)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.**NUMBER OF FIX EXCEED GEN LT**
  
 18)NOTE: PLEASE SEE MISSING RECEPT ON
 2ND FLR PASSAGE/HALLWAY. 210.52H
 REDLINED ON PLANS.
  
 19)NOTE: PLEASE CLARIFY RECEPT (B-7)
 LAUNDRY RECEPT SHOWN BEHIND DRYER?
 THIS IS ONLY A NOTE.
  
 20)NOTE: PLEASE SEE 2ND FLR, ROOM
 LOCATED OUTSIDE "DUMB WAITER", ON A3.2
 THIS SHOWS A "BAR RM" WITH A FRIG ETC,
 HOWEVER ELECTRICAL PLANS DO NOT IDENTIFY
 THIS ROOM AND NO RECEPT IS SHOWN FOR
 FRIG? PLEASE ADJUST , PANEL
 SCHEDULE,LOADS ETC.
 215.5
  
 21)NOTE: PLEASE INDICATE CIRCUIT FOR
 "JACUZZI TUB" LOCATED IN MASTER BATH RM.
 215.5
 PLEASE ADJUST LOAD CALCS, PANEL SCHEDULE
 ETC AS A JACUZZI RECEPT IS SHOWN ON
 PANEL "D" TO ROOF UNIT>
  
 22)NOTE: PLEASE SEE RECEPT SHOWN AT BAR
 ON 3RD FLR IS REQUIRED TO BE GFI LOCATED
 WITH IN 6' OF WET BAR SINK. 210.8A7
  
 23)NOTE: PLEASE IDENTIFY A DISCONNECT
 SWITCH BEING SHOWN AT 3RD LEVEL, TILED
 TERRACE AREA?
 NO CIRCUITING , ??
  
 24)NOTE: PLEASE SEE MIN CLEARENCES
 REQUIRED FOR LIGHTING FIXTURE(SHOWN AS
 FUTURE) (J-BOXES) CIRCUITING TO D-6 AT
 3RD FLR AREA. PLEASE SEE TWO BOXES WITH
 IN ZONE OF JACUZZI/HOT TUB.
 680.40
  
 25)NOTE: PLEASE SEE MISSING REQUIRED
 EMERGENCY DISCONNETC SWICTH TO BE
 LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT
 NO FURTHER THAN 50'.
 PLEASE SEE 680.41
  
 26)NOTE: PLEASE CORRELATE PLANS, PANEL
 CIRCUITING FOR WHAT APPEARS TO BE A A/C
 UNIT AT 3RD FLR??
 PLEASE SEE PLANS SHOWS A "D-7" , HOWEVER
 PANEL SCHEDULE SHOWS CIRCUIT "D-7,9"??
 FOR AN A/C UNIT??
 215.5
 IS THIS A WALL UNIT? PLUG-IN? DISC?
 440.11
  
 27)NOTE: PLEASE SEE A MEANS OF EGRESS
 LTIGHTING CONTROL SWITCH IS REQUIRED AT
 (4TH) LEVEL ROOF TILED AREA DOWN TO 3RD
 LEVEL. PLEASE SHOW AS WP.210.70
 (3-WAY)??
  
 28)NOTE: PLEASE SUBMIT COMPLETE
 MANUFACTURE SPECS/CUT SHEETS FOR
 GENERATOR , ATS .
 PLEASE KNOW, GENERATOR CAN BE SUBMITTED
 UNDER SEPARATE PERMIT AT A LATER DATE
 WITH SEPARATE, SURVEY, PLANS, SPECS,
 FEES ETC., HOWEVER, SPECS FOR ATS ARE
 REQUIRED AT THIS TIME FOR REVIEW.
 PLEASE SEE PLANS AND RISER INDICATE THIS
 UNIT AS CONTAINING THE MAIN 1OF 1??
 PLEASE SEE230.76,230.79, 230.91 ETC
 WHICH REQUIRES THE MANUAL MEANS OF
 DISCONNECT TO BE LOCATED ON THE OUTSIDE
 AND RATED FOR THE LOAD SERVED ETC.
 UNABLE TO VERIFY CODE COMPLIANCE AT THIS
 TIME.
 (THIS WAS REQUESTED ON PREVIOUS REVIEW
 ALSO).
 PLEASE VERIFY IF ATS DOES CONTAIN THE
 MAIN OR DOES NOT AS THIS WILL AFFECT THE
 FOLLOWING.
  
 29)NOTE: PLEASE SEE 250.24 FOR THE
 LOCATION PERMITTED FOR THE GROUNDING
 ELECTRODE SYSTEM.
 (IF THERE IS ANY QUESTION, GROUNDING
 ELECTRODE CONDUCTOR MAY BE LOCATED AT
 METER.
  
 30)NOTE: PLEASE ALSO SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 THE FIRST MEANS OF DISCONNECT(?) AND
 GUTTER.
 250.110,250.122,250.24
  
 31)NOTE: PLEASE SUBMIT COMPLETE LOAD
 SHEDDING DETAILS FOR AUTOMATION SYSTEM
 AS RISER DIAGRAM NOTES GENERATOR SHALL
 BE ADEQUATE FOR THE LOAD TO BE SERVED.
 702.5
 THIS IS REQUIRED AT THIS TIME, UNLESS
 GEN IS NOT PERMITTED AT THIS TIME.
 SEE PREVIOUS NOTES.
  
 32)NOTE: PLEASE SEE PANEL SCHEDULE "D",
 CIRCUITS 10/12 WHICH SHOWS A FEED TO A
 "SPA" , HOWEVER THIS COULD NOT BE LCATED
 ON PLANS??
 215.5
  
 33)NOTE: PLEASE SEE LOAD CALCULATIONS
 WHICH INDICATE 10,000 SQ FT FIGURED FOR
 HOUSE , YET APPLICATION AND BLDG PLANS
 DO NOT CORRELATE WITH THIS NUMBER??
 215.5
  
 34)NOTE: PLEASE BE SURE ALL DEDICATE
 ITEMS ON PANEL SCHEDULES ARE FIGURED
 INTO LOAD CALCAULTIONS. SEE PREVIOUS
 NOTES WITH RESPECT TO FRIG, POOL
 EQUIPMENT ETC.
 PLEASE SEE A DEDICATED LAUNDRY
 LOAD/CIRCUIT IS SHOWN ON PANEL "B",
 HOWEVER THIS NOT FIGURED INTO LOAD
 CALCULATIONS FOR MAIN HOUSE.
 PLEASE SEE EXTERIOR LTS ON PANEL "D" IS
 SHOWNAT 6.3 KW WHICH IS ABOVE 3 WATTS
 PER SQ FT ALREADY FIGURED??
 215.5
  
 35)NOTE: PLEASE SEE LOCATION OF TVSS
 SHOWN AT LOCATION WHICH APPEARS TO BE
 TAPPED INTO THE PIPE LOCATED BETWEEN
 GUTTER AND ATS??
 PLEASE SEE 285.21 FOR LOCATIONS
 PERMITTED.
  
 **PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ANY/ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By btrobaug Date 2005-07-14 Time 17:41 Rev Time 1.00
Received By btrobaug Date 2005-07-13 Time 12:48 Sent To M
Notes
2005-07-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT MANUFACTURERS SPECIFICATIONS
 FOR THE GENERATOR AND THE TRANSFER
 SWITCH. PLEASE NOTE THE TRANSFER SWITCH
 MUST BE SERVICE RATED(225.36) AND MUST
 BE CAPABLE OF DISCONNECTING ALL CIRCUITS
 SIMULTANEOUSLY, 230.71.
  
 2} WHAT IS THE BOX BEING FED WITH 500MCM
 (ON THE RISER) FROM THE BOTTOM OF THE
 TRANSFER SWITCH?
  
 3} THE WASHER, DRYER, HOT TUB/SPA,
 ELEVATOR,POOL PUMP AND POOL HEATER, ARE
 NOT IN THE LOAD CALCS.
  
 4} PLEASE INDICATE THE FEEDER TAP
 CONDUCTOR SIZES(LEAVING THE GUTTER).
  
 5} THE SMOKE DETECTORS ARE REQUIRED TO
 BE INTERCONNECTED PER 905.2.1 FBC. THEY
 ARE SHOWN ON TWO DIFFERENT CIRCUITS ON
 THE PLAN. ALSO PLEASE NOTE THEY MUST BE
 ARC FAULT PROTECTED PER 210.12. THIS
 DOES NOT MEAN THEY MUST BE ON A BEDROOM
 CIRCUIT NECESSARILY.
  
 6} THE ELEVATOR RECEPTACLE AND LIGHT
 MUST BE ON A SEPERATE BRANCH CIRCUIT PER
 620.23, SEE A-8 CIRCUIT ALSO FEEDS
 DINING ROOM LIGHTING.
  
 7} THE CONDENSING UNIT DISCONNECTS AND
 ELECTRIC METER DO NOT APPEAR TO HAVE
 CLEARANCE PER 110.26. SHOW THE LOCATION
 OF THE REST OF THE SERVICE AND GENERATOR
 EQUIPMENT ONPLAN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-01-18 Cont ID  
Sent By mperson Date 2008-01-18 Time 15:50 Rev Time 0.00
Received By mperson Date 2008-01-18 Time 15:50 Sent To PC
Notes
2008-01-18 16:46:55PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 1. NOTE: AS OF 2/6/07 GAS RISER DIAGRAMS WERE REMOVED
 FROM PLANS. PLEASE REFERENCE THE PERMIT INFORMATION
 ATTACHED TO THESE COMMENTS INDICATING THIS. A GAS
 PERMIT APPLICATION IS REQUIRED FOR THE PROPOSED GAS
 SYSTEM. ALICENSED GAS OR PLUMBING CONTRACTOR SHALL
 SUBMIT PLANS WITH PERMIT APPLICATION. PLEASE ONLY
 SUBMIT PLAN SHEETS PERTAINING TO THE PROPOSED GAS
 SYSTEM. TWO COMPLETE SETS OF PLANS ARE NOT REQUIRED FOR
 GAS PLANS. PER CHAPTER 1, CITY AMENDMENTS SECTION
 *105.1 REQUIRED.
  
 2. SHEETS A3.1, A3.2, AND A3.3 FLOOR PLANS HAVE TITLE
 BLOCKS WITH COPIED SIGNATURES OF A DESIGN PROFESSIONAL
 AND ARE NOT SEALED. PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. **THE SUBMITTED PLANS DO NOT HAVE ALL
 CUT SECTIONS OF PIPE WITH CORRESPONDING LENGTHS
 INDICATED. THIS IS REQUIRED TO VERIFY THE NEXT
 COMMENT.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). **PLEASE CLEARLY INDICATE
 THE GAS SYSTEMS LONGEST LENGTH. PER FBC FUEL GAS
 SECTION *401.1 SCOPE.
  
 5. CLEARLY INDICATE THE LOCATION OF THE REQUIRED MP
 REGULATORS ON THE GAS ISOMETRIC RISER DIAGRAM. PER FBC
 FUEL GAS SECTION *401.1 SCOPE.
  
 6. PROVIDE TWO COPIES OF MANUFACTURER'S SPECFICATION
 OF THE MP REGULATORS INDICATING THE MAKE, MODEL NUMBER,
 AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 7. NOTE: GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 (FUTURE) SHALL BE CLEARLY INDICATED AS BEINGCAPPED
 GAS TIGHT ON PLANS. IF GAS DELIVERY PRESSURE IS 2 PSI
 OR GREATER MP REGULATORE SHALL BE INSTALLED PRIOR TO
 FINAL INSPECTION. PER FBC FUEL GAS SECTION *404.12
 OUTLET CLOSERS ANS SECTION *401.1 SCOPE.
  
 8. GAS PLANS ARE INDICATING A FUTURE GENERATOR PLEASE
 BE AWARE THAT FUTURE GENERATOR GAS PIPING AT OWN RISK,
 AND A SEPERATE RESIDENTIAL GENERATOR PERMIT IS REQUIRED
 WITH ZONING APPROVAL OF GENERATOR PLACEMENT.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2007-02-06 Cont ID  
Sent By jleech Date 2007-02-06 Time 15:09 Rev Time 0.00
Received By jleech Date 2007-02-06 Time 15:09 Sent To B
Notes
2007-02-06 15:11:37GAS RISER DIAGRAM REMOVED FROM PLANS. GAS PLANS WILL BE
 SUBMITED BY GAS CONTRACTOR.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-07-03 Cont ID  
Sent By jleech Date 2006-07-03 Time 08:30 Rev Time 0.00
Received By jleech Date 2006-07-03 Time 08:30 Sent To P
Notes
2006-07-03 00:00:00 
 DENIED;
 THIRD REQUEST;
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2.SUBMIT MANUFACTURE SPEC SHEETS FOR GAS
 LIGHTS AND GENERATOR.
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By jleech Date 2005-10-11 Time 08:54 Rev Time 0.50
Received By jleech Date 2005-10-11 Time 08:54 Sent To M
Notes
2005-10-11 00:00:00DENIED;
 1.PLEASE SIZE ALL CUT OFF PIPE. (SECOND
 REQUEST)
 2.SHOW FUTURE WATER HEATER ON RISER
 DIAGRAM. PIPE SHOULD BE INSTALLED WITH
 SHUTOFFVALVE AND PLUG IF NOT USED.
 3.PLESE SUBMIT MANUFACTORS CUT SHEETS
 FOR GAS LAMPS AND GENERATOR.
 4.MOST BLACK IRON INSTALLATIONS ARE
 WELDED 2" AND LARGER, UNDER 2" IS SCREW
 PIPE. IS ALL PIPE TO BE WELDED?
 5. PLEASE ADD TO GAS NOTES, WELDER
 CERTIFICTIONS ARE REQUIRED WHEN GAS
 PERMIT IS APPLYIED FOR.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 16:12 Rev Time 0.00
Received By shill Date 2009-07-22 Time 16:12 Sent To  
Notes
2009-07-22 16:12:49REVISION TO RM DESK

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-01-21 Cont ID  
Sent By adarroug Date 2009-01-21 Time 16:44 Rev Time 0.00
Received By adarroug Date 2009-01-21 Time 16:44 Sent To B
Notes
2009-01-21 16:45:04TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 09:46 Sent To B
Notes
2008-10-16 09:47:13TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 09:42 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 09:42 Sent To B
Notes
2008-10-16 09:43:18TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 15:42 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 15:42 Sent To B
Notes
2008-05-06 15:43:10TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-01-15 Cont ID  
Sent By adarroug Date 2008-01-15 Time 15:47 Rev Time 0.00
Received By adarroug Date 2008-01-15 Time 15:47 Sent To G
Notes
2008-01-15 15:47:39TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-01-16 Cont ID  
Sent By dpalmer Date 2007-01-16 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2007-01-16 Time 12:46 Sent To E
Notes
2007-01-16 12:47:14REMOVED FROM INCOMING AND ROUTED TO ELEC.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 09:31 Sent To Z
Notes
2006-12-26 09:31:59TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 11:57 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 11:57 Sent To M
Notes
2006-06-29 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 10:18 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 10:18 Sent To E
Notes
2006-06-14 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 16:36 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 16:36 Sent To E
Notes
2005-10-06 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 10:21 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 10:21 Sent To Z
Notes
2005-09-30 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 15:05 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 15:05 Sent To E
Notes
2005-07-12 00:00:00TO "SFR" E

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 14:44 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 14:44 Sent To Z
Notes
2005-06-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-06-29 Cont ID  
Sent By tgordon Date 2006-06-29 Time 13:58 Rev Time 0.45
Received By tgordon Date 2006-06-29 Time 13:57 Sent To P
Notes
2006-06-29 00:00:00*** PROVISO ***
 1) PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER ON SECOND FLOOR LAUNDRY
 ROOM, PER 2001 FBC/M 701 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-10-11 Cont ID  
Sent By tgordon Date 2005-10-11 Time 10:43 Rev Time 0.30
Received By tgordon Date 2005-10-11 Time 10:43 Sent To B
Notes
2005-10-11 00:00:00*** DENIED ***
 1) NEED A/C EQUIP. LISTED ON PLANS,
 MANUFACTURE, MODEL NUMBER, TONS, SEER,
 FOR EACH UNIT (AIR HANDLERS AND
 CONDENSER UNITS) .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-19 Cont ID  
Sent By hmoser Date 2005-07-19 Time 18:38 Rev Time 0.00
Received By hmoser Date 2005-07-19 Time 17:55 Sent To P
Notes
2005-07-19 00:00:00PLAN DENIED
 1) PLEASE PROVIDE EQUIPMENT SCHEDULE ON
 PLANS.
 2) PLEASE SUBMIT MANUFACTURER
 INSTALLATION INSTRUCTIONS ON FIRE PLACE
 AND KITCHEN DOWNDRAFT.
 3) PLEASE REFER TO SECTION 307.2.4
 AUXILIARY DRAIN PANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-20 Cont ID  
Sent By jleech Date 2007-01-20 Time 13:48 Rev Time 0.00
Received By jleech Date 2007-01-20 Time 13:48 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-07-03 Cont ID  
Sent By jleech Date 2006-07-03 Time 08:42 Rev Time 0.00
Received By jleech Date 2006-07-03 Time 08:42 Sent To B
Notes
2006-07-03 00:00:00DENIED;
 1.CLEANOUTS ON AUTOMATIC CLOTHES WASHER
 REQUIRED TO BE INSTALLED AT 48"AFF.
 2.SHOW ROOF DRAINS AND SECONDARY
 (EMERGENCY) DRAINS AND CALCULATIONS PER
 CHAPTER 11.
 3.REMOVE AIR CHAMBER SYMBAL FROM WATER
 ISOMETRICS. AIR CHAMBERS ARE NOT AN
 APPROVED PRODUCT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-11 Cont ID  
Sent By jleech Date 2005-10-11 Time 08:27 Rev Time 1.00
Received By jleech Date 2005-10-11 Time 08:27 Sent To G
Notes
2005-10-11 00:00:00DENIED;
 1.SECONDARY DRAIN PROTECTION REQUIRED
 PER. FBC-2001 PLUMBING SEC. 1107.1.
 2.HOT WATER CIRCULATION SYSTEM MUST
 COMPLY WITH FBC 2001 CHAPTER 13. (ENERGY
 CODE) SEC. 612.1ABC.4 AND 612.1ABC.5
 SHOW HOW PUMP WILL TURN OFF TO SAVE
 ENERGY. HOT WATER PIPING TO BE INSULATED
 TO SAME ENERGY.
 3.WATER RISER DIAGRAM; SHOW COMPLIANCE
 WITH SEC. 604.9. PLEASE REMOVE ALL
 SYMBOLS NOT REQUIRED. (AIR CHAMBERS ARE
 NOT AN APPROVED PRODUCT.
 4.JACUZZI DRAIN SHALL BE A FLOOR SINK
 INSTALLED 1" ABOVE DECK SURFACE, THIS
 WILL PREVENT RAIN WATER AND WILL CATCH
 THE INDIRECT DISCHARGE FROM JACUZZI.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 08:44 Rev Time 1.25
Received By jleech Date 2005-07-23 Time 08:44 Sent To B
Notes
2005-07-23 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM;
 A.VENT AND WASTE PIPING SYSTEM IS NOT
 REQUIRED IN A HOSE SYSTEM.
 B.FIRST FLOOR BATHROOM NOT TIED TO
 BUILDING DRAIN.
 C.WASHING MACHINE ON FIRST FLOOR NOT
 VENTED.
 D.ALL SANITARY DRAINAGE PIPING SHALL
 BE SIZED FOR FUTURE FIXTURES,(3" FLOOR
 DRAIN FOR JACUZZI)
 E.2-WAY CLEANOUT REQUIRED FOR CABANA
 3' OUTSIDE BUILDING.
 2.SHOW SIZE OR ROOF SCUPPERS AND
 MATERIAL USED. ALSO SHOW TOTAL SQUIRE
 FOOTAGE CAULKS. PER CHAPTER 11 FBC
 PLUMBING.
 GAS;
 1.SEE "GAS PERMIT APPLICATION
 REQUIREMENTS" SHEET. COMPLY WITH ITEMS
 1, 3, 4, 7, AND 9.
 2.ALL FUTURE GAS EQUIPMENT SHOULD BE
 ADDED TO CAULCULATIONS SO GAS PIPE
 SIZEDOES NOT CHANGE WHEN EQUIPMENT IS
 ADDED.
 3.IS GENERATOR NAT. GAS IF SO CAULKS
 SHOULD BE INCLUDED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2007-01-24 Cont ID  
Sent By mmclean Date 2007-01-24 Time 10:51 Rev Time 0.00
Received By mmclean Date 2007-01-24 Time 10:51 Sent To B
Notes
2007-01-24 11:07:45PROVISO: COLUMNS/WALL/GATE/FENCEARE NOT APPROVED WITH
 THE THIS PERMIT. SHALL APPLY FOR A SEPARATE PERMIT AND
 PROVIDE EASEMENT APPROVAL FROM CITY OF WEST PALM BEACH
 UTILITY DEPT.MAXIMUM HEIGHT ALLOWED WITHIN FRONT 25FT
 SETBACK IS 4FT ONLY. PLEASE PROVIDE WALL DETAIL FOR THE
 COLUMNS, GATE, FENCE, WALL.
  

Review Stop Z ZONING
Rev No 4 Status F Date 2007-01-12 Cont ID  
Sent By mmclean Date 2007-01-12 Time 08:09 Rev Time 0.00
Received By mmclean Date 2007-01-12 Time 14:57 Sent To M
Notes
2007-01-12 14:58:23DENIED,
 1. PLEASE PROVIDE UPDATED SITEPLANS WITH PROPOSED WORK.
 CANNOT USE DRAINAGE PLANS AND THE VOIDED SITEPLAN
 (06/09/05).
 2. SITEPLAN SHALL PROVIDE THE WIDTH OF THE PROPOSED
 DRIVEWAY AND SETBACK OF THE PROPOSED STRUCTURES WITH
 DISTANCE SEPARATION OF THE PROPOSED CABANA AND MAIN
 STRUCTURE.
 3. THE MAXIMUM HEIGHT FOR WALL/COLUMNS/GATES CAN ONLY
 BE 4FT WITHIN THE 25FT SETBACK.
  
 NOTE: SEPARTE PERMIT FOR THE FENCE/WALL/COLUMN WITH
 EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 3 Status F Date 2006-06-28 Cont ID  
Sent By mmclean Date 2006-06-28 Time 12:38 Rev Time 0.00
Received By mmclean Date 2006-06-28 Time 12:38 Sent To I
Notes
2006-06-28 00:00:00DENIED.
 1. THE COVERED TERRACE MUST SIT BEYOND
 THE 25FT FRONT SETBACK.SITEPLAN SHOWS
 IT AT 23.8FT.
  
  
  
 NOTE:
 THE PROPOSED A/C UNIT SHALL NOT BE
 CLOSER THAN 6FT FROMSIDE PROPERTY
 LINE.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE AND
 WALL/GATE/FENCE WITH UTILITY EASEMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.
  
 NOTE:THE WALL/COLUMNS/FENCE/GATE CAN
 ONLY BE A MAXIMUM HEIGHT OF 4FT ONLY
 WITHIN THE 25FT FRONT SETBACK.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2006-06-22 00:00:00NEW SHEETS, WITH REVISIONS.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-10-06 Cont ID  
Sent By mmclean Date 2005-10-06 Time 16:17 Rev Time 0.00
Received By mmclean Date 2005-10-06 Time 16:17 Sent To I
Notes
2005-10-06 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 GATE/WALL/FENCE/COLUMNS WITH EASEMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITIES DEPT.
  
 NOTE: FENCE/GATE/WALL/COLUMNS CAN ONLY
 BE MAXIMUM 4FT WITHIN THE FIRST 25FT
 FRONT SETBACK.BEYOND THE 25FT FRONT
 SETBACK MAXIMUM HEIGHT IS 6FT.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 17:09 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 17:09 Sent To I
Notes
2005-07-11 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION FOR THE
 DRIVEWAY & WALKWAY (LENGTH & WIDTH).
 2. NEED TO APPLY FOR A SEPERATE PERMIT
 FOR FENCE/GATE/COLUMNS/WALLS WITH THE
 UTILITY EASEMENT APPROVAL FROM CITY OF
 WEST PALM BEACH UTILITY DEPT.
 3. WALL/GATE/FENCE/COLUMNS CAN ONLY BE A
 MAX OF 4FT HIGH WITHIN THE FRONT SETBACK
 (25FT).
 4. MAIN STRUCTURE MUST MEET THE HEIGHT
 REQUIREMENT OF 33FT (30 FOR STRUCTURE
 AND 10% FOR CHIMNEY). STRUCTURE SHOWS
 34+ FEET.
 5. MUST HAVE U/C REFRIDGERATOR FOR THE
 2ND & 3RD STORY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved