| Plan Review Stops For Permit 05061696 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2009-07-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-27 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-27 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2009-07-27 16:27:57 | REVISION TO CHANGE PRODUCT APPROVALS IS DENIED. | | | | | | 1) SUBMIT TWO COPIES OF AN EXTERIOR DOOR AND WINDOW | | | SCHEDULE THAT IS COORDINATED WITH THE NUMBERING SYSTEM | | | USED ON THE PLANS. SPECIFY THE DOOR SIZES AND SWINGS, | | | AS WELL AS, THE WINDOW TYPES AND SIZES ON THE SCHEDULE. | | | | | | 2) CIRCLE THE APPROPRIATE WINDOW SIZES, GLASS TYPE AND | | | DESIGN PRESSURES ON THE PRODUCT APPROVALS FOR THE | | | WINDOWS THAT WILL BE INSTALLED. | | | | | | 3) CIRCLE THE DOOR TYPES, GLASS TYPE AND DESIGN | | | PRESSURES FOR THE DOORS THAT WILL BE INSTALLED. | | | | | | 4) CIRCLE THE MULLION SPANS, THE WIDTH AND DESIGN | | | PRESSURE FOR THE MULLIONS THAT WILL BE INSTALLED. | | | | | | 5) SOME OF THE PRODUCT APPROVAL DESIGN PRESSURES ARE | | | LOWER THAN THE REQUIRED OPENING PRESSURES SPECIFIED ON | | | THE PLANS. PROVIDE PRODUCT APPROVALS FOR COMPONENTS | | | WITH ADEQUATE DESIGN PRESSURES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2009-01-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-01-28 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-01-28 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2009-01-28 09:05:19 | NOTE: ALTHOUGH THE LOADS ON THE ROOF FRAMING PLAN ON | | | S-103 ARE LOW FOR SOME OF THE TRUSSES, THE CONNECTORS | | | SPECIFIED IN THE SCHEDULE ON S-601 ARE ADEQUATE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-10-24 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-10-24 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2008-10-24 09:59:12 | APPROVED FLOOR REVISION SUBMITTAL OK LM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-05-16 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-05-16 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2008-05-16 10:22:24 | CANNOT APPROVE NEW STRUCTURAL ENGINEERS SUBMITTAL. RAS | | | IS THE ENGINEER OF RECORD. | | | | | | | | | | | | | | | L.MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-02-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-02-21 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-02-21 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2007-01-16 13:43:44 | NEW SHEETS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-05 |
Time |
14:05 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2006-07-05 |
Time |
11:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-10-12 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-12 |
Time |
13:39 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2005-10-12 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2005-10-12 00:00:00 | PLAN REVIEW: | | | | | | ITEMS REQUIRED TO SUBMIT PLANS FOR | | | PERMITTING: | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3. WEATHERSHIELD PRODUCT APPROVALS | | | SUBMITTED WITH THIS APPLICATION REQUIRE | | | THE FOLLOWING STATE PRODUCT APPROVALS. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-08-03 |
Time |
09:58 |
Rev Time |
4.50 |
| Received By |
alange |
Date |
2005-08-02 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2005-08-03 00:00:00 | PLAN REVIEW: | | | | | | ITEMS REQUIRED TO SUBMIT PLANS FOR | | | PERMITTING: | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE REQUIRED FOR THE FOLLOWING. | | | ROOFING PRODUCTS, EXTERIOR DOORS, | | | WINDOWS, IMPACT PROTECTION, LINTELS AND | | | STRAPS AND TIE-DOWNS. | | | ALL PRODUCT APPROVALS SUBMITTED SHALL | | | HAVE THE FOLLOWING STATE PRODUCT | | | APPROVAL ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4.SLAB WITH GENERATOR, A/C AND POOL | | | EQUIPTMENT SHALL BE AT 7'6" NGVD. | | | | | | 5.SUBSURFACE EXPLORATION REPORT | | | RECOMMENDS A 10 MIL VAPOR BARRIER | | | SYSTEM.PLANS SHOW 6MIL. | | | | | | 6.SUBMIT A SPIRAL STAIR DETAIL SHOWING | | | COMPLIANCE WITH FBC 1007.8.2.1 | | | | | | 7.PAGE A-7.1 DOOR AND WINDOW SSCHEDULE | | | IS MISSING. | | | | | | 8.BUILDING SPECIFICATIONS SHOW A TYPE | | | IV UNPROTECTED BUILDING.ACCORDING TO | | | TABLE 500 THE MAX. ALLOWABLE HEIGHT WITH | | | OUT SPRINKLERS IS 2 STORIES. | | | SHOW HOW COMPLIANCE WITH THIS SECTION | | | WILL BE MADE. | | | | | | 9.SHOW WINDOW AND DOOR PRESSURES IN | | | ACCORDANCE WITH FBC CHAPTER16. | | | | | | NOTE:NEW CODE CYCLE CHANGE STARTS | | | OCTOBER 1, 2005.APPLICATION FOR | | | PERMITTING SHOULD BE SUBMITTED BEFORE | | | THEN TO BE ON THE 2001 FBC. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-22 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-22 |
Time |
10:34 |
Sent To |
PC |
|
| Notes |
| 2007-02-22 11:40:37 | **REDLINED/REVISION NEEDED ** | | | | | | ** PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE AIC | | | RATING OF THE EQUIPMENT BEING INSTALLED. PLEASE SEE A | | | NOTE ON PLANS NOW MENTIONS 42K AND THE ELECTRICAL | | | CONTRACTOR TO VERIFY WITH FPL ETC BEFORE ORDERING. THIS | | | INFORMATION IS SOMETHING THAT IS REQUIRED TO BE | | | VERIFIED AT THIS TIME. CONTACT SHOULD BE MADE TO THE | | | SERVICE PLANNER FOR THE AREA AND THE INFORMATION CAN BE | | | EASILY FOUND OUT. | | | PLEASE SEE THAT THE RATINGS ON THE PLANS CALL FOR 42K | | | MAIN AND 22K RATED MAINS ON THE LOAD SIDE OF THE HOUSE | | | SERVICE MAIN AND 22K RATED BRANCH BREAKERS. ALL OF | | | THESE RATINGS ARE PERMITTED AND ARE OK; HOWEVER PLEASE | | | KNOW IF THESE RATINGS ARE SHOWN, THEN THIS IS WHAT | | | WOULD BE REQUIRED TO BE INSTALLED. PLEASE VERIFY THIS, | | | AS THIS IS ONLY BEING NOTED. CONSIDERATION TO THE COST | | | OF THE RATED EQUIPMENT AND INSTALLATION OF 22K RATED | | | BRANCH BREAKERS ETC MAY WANT TO BE TAKEN INTO | | | CONSIDERATION. | | | 110.9. | | | | | | **PLEASE KNOW THAT SINCE THE LAST REVIEW OF THIS | | | PROJECT, A MEETING WAS HELD AT THE SOUTHERN SECTION | | | MEETING IN OCT 06 WHERE WE WERE DIRECTLY INFORMED BY | | | NFPA THAT THE USE OF "SD" FOR SMOKE DETECTORS ON PLANS | | | FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN THESE | | | DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS OF | | | SMOKE ALARMS WHICH WOULD BE SHOWN AS "SA"/SMOKE | | | ALARMS". | | | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE | | | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY | | | THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE | | | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL | | | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY | | | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF | | | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS | | | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS | | | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS | | | FOR OTHER NEW HOMES; HOWEVER THIS WAS NOT A COMMENT | | | FROM THIS AHJ OR REVIEWER BEFORE AS THIS INFORMATION | | | WAS MADE AWARE TO ALL OF THE JURISDICTIONS PRESENT, | | | MOST OF WHICH HAD ALSO ALWAYS ACCEPTED SD AND THE | | | STATED SMOKE DETECTORS. | | | | | | | | | THESE ITEMS ALONG WITH ANY OTHER REVISIONS ARE TO BE | | | CORRECTED, SUBMITTED, REVIEWED AND STAMPED FOR JOBSITE | | | BEFORE ANY ROUGH ELECTRICAL INPSECTION IS CALLED IN. | | | | | | IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-17 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-16 |
Time |
12:47 |
Sent To |
P |
|
| Notes |
| 2007-01-17 07:40:38 | ** UNSAT** | | | | | | ** PLEASE SEE SOME COMMENTS FOR COORDINATION AND | | | CHANGES ON PLANS NEED TO BE ADDRESSED. | | | PLEASE ALSO SEE NEW COMMENT #4. | | | | | | | | | 1) NOTE: PLEASE SEE ON THE PREVIOUS REVIEW IT WAS | | | REQUESTED TO SUBMIT THE MANUFACTURE'S SPEC/CUT SHEETS | | | FOR THE LIGHTING HOME AUTOMATION SYSTEM WHICH WAS GOING | | | TO BE INSTALLED. A COVER LETTER MENTIONS ONE SYSTEM | | | WHICH WOULD BE THE LUTRONWHICH MAY BE DONE WITH FOUR | | | OR FIVE PANELS AND ONE SYSTEM WHICH COULD BE DONE WITH | | | THREE PANELS. | | | PLEASE SEE TWO COMPLETELY DIFFERENT PACKAGES FOR THESE | | | SYSTEMS WERE SUBMITTED WITH ONLY ONE CONTAINING THE | | | LISTING FROM A NRTL. PLEASE SEE THE PACKAGE FOR SYSTEM | | | WHICH IS BEING CALLED A CRESTRON DID NOT SEEM IT | | | CONTAINED ANY LISTINGS WHICH COULD BE READILY LOCATED | | | ON SHEETS PROVIDED. | | | ** PLEASE SEE ON THE OTHER HAND THE PLANS SHOWS 4 | | | LIGHTING CONTROL PANELS WHICH WOULD NOT CORRELATE WITH | | | THE STATEMENT ON THE COVER SHEETS WHICH MENTIONS ONLY | | | THREE PANELS ARE BEING USED (CRESTRON). | | | PLEASE CORRELATE PLANS AND SUBMITTALS AND ONLY SUBMIT | | | THE SYSTEM BEING PROPOSED. | | | 110.3, 90.7 | | | FBC 106.1.2 ADMIN SECTION. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE | | | MANUFACTURE'S SPEC/CUT SHEETS FOR THE NEW PROPOSED ATS | | | BEING INSTALLED. PLEASE SEE THIS WAS DONE, HOWEVER | | | SPECS FOR AN ATS WERE SUBMITTED. PLEASE SEE THE PLANS | | | NOW CONTAIN WHAT IS BEING SHOWN AS A MTS, WHICH IS | | | BEING DONE? | | | PLEASE CORRELATE THESE ALSO. | | | 90.7, 110.3, FBC 106.1.2 ADMIN SECTION. | | | | | | 3) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE | | | AIC RATING OF THE EQUIPMENT BEING INSTALLED. PLEASE SEE | | | A NOTE ON PLANS NOW MENTIONS 42K AND THE ELECTRICAL | | | CONTRACTOR TO VERIFY WITH FPL ETC BEFORE ORDERING. THIS | | | INFORMATION IS SOMETHING THAT IS REQUIRED TO BE | | | VERIFIED AT THIS TIME. CONTACT SHOULD BE MADE TO THE | | | SERVICE PLANNER FOR THE AREA AND THE INFORMATION CAN BE | | | EASILY FOUND OUT. | | | PLEASE SEE THAT THE RATINGS ON THE PLANS CALL FOR 42K | | | MAIN AND 22K RATED MAINS ON THE LOAD SIDE OF THE HOUSE | | | SERVICE MAIN AND 22K RATED BRANCH BREAKERS. ALL OF | | | THESE RATINGS ARE PERMITTED AND ARE OK; HOWEVER PLEASE | | | KNOW IF THESE RATINGS ARE SHOWN, THEN THIS IS WHAT | | | WOULD BE REQUIRED TO BE INSTALLED. PLEASE VERIFY THIS, | | | AS THIS IS ONLY BEING NOTED. CONSIDERATION TO THE COST | | | OF THE RATED EQUIPMENT AND INSTALLATION OF 22K RATED | | | BRANCH BREAKERS ETC MAY WANT TO BE TAKEN INTO | | | CONSIDERATION. | | | 110.9. | | | | | | 4) NOTE:PLEASE KNOW THAT SINCE THE LAST REVIEW OF | | | THIS PROJECT, A MEETING WAS HELD AT THE SOUTHERN | | | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY | | | INFORMED BY NFPA THAT THE USE OF "SD" FOR SMOKE | | | DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT | | | ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER | | | THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS | | | "SA"/SMOKE ALARMS". | | | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE | | | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY | | | THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE | | | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL | | | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY | | | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF | | | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS | | | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS | | | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS | | | FOR OTHER NEW HOMES; HOWEVER THIS WAS NOT A COMMENT | | | FROM THIS AHJ OR REVIEWER BEFORE AS THIS INFORMATION | | | WAS MADE AWARE TO ALL OF THE JURISDICTIONS PRESENT, | | | MOST OF WHICH HAD ALSO ALWAYS ACCEPTED SD AND THE | | | STATED SMOKE DETECTORS. | | | IF THE ONLY COMMENT ON THE PLANS WAS THIS, THE PLANS | | | WOULD HAVE BEEN REDLINED FOR THE CORRECTIONS AND WOULD | | | BE ISSUED WITH REVISIONS TO FOLLOW. | | | PLEASE MAKE ADJUSTMENTS FOR THESE AS PLANS ARE COMING | | | BACK FOR ZONING COMMENTS AND NOTES ABOVE. | | | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC | | | RESIDENTIAL CODE/ FBC AND IN NFPA-72. | | | 11.5.1.1, 11.8.3 | | | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-01-17 07:02:33 | 2007-01-17 07:02:33 | | | IN PROGRESS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-22 |
Time |
18:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-21 |
Time |
21:03 |
Sent To |
Z |
|
| Notes |
| 2006-06-22 00:00:00 | ******* UNSAT 3RD REVIEW ************* | | | | | | ** PLEASE SEE THERE ARE COMMENTS FROM | | | PREVIOUS REVIEW WHICH STILL NEED TO BE | | | ADDRESSED AND SOME NEW COMMENTS DUE TO | | | PLAN CHANGES. | | | | | | ** PLEASE SEE NOTES BELOW ARE TAKEN | | | DIRECTLY FROM THE PREVIOUS REVIEW AND | | | ANY NEW NOTES ARE ADDED AT THE BOTTOM. | | | | | | ************* UNSAT ****************** | | | | | | 1)NOTE: NOTE #1 NO, PLEASE SE A4.2 STILL | | | SHOWS THE SAME AS BEFORE. | | | | | | ** PREVIOUS NOTES** | | | PLEASE SEE MAX HEIGHT FOR | | | ELECTRICLA METERCAN PER SECTION 6 OF FPL | | | SERVICE INSTALLATIONS GUIDELINES SHALL | | | BE 6' TO THE CENTER OF METER. | | | PLEASE SEE ELEVATION PLANS A4.2 CLEARLY | | | SHOW THIS HIGHER. | | | | | | 2)NOTE: NOTE #2 SMAE NOTE, ALSO AS | | | ABOVE. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE MAX HEIGHT OF | | | DISCONNECTING EQUIPMENT/SWITCHES SHALL | | | BE 6'7" WITH OUT RESORTING TO LADDERS | | | ETC. | | | 440.11, 100 (DEFINITIONS) ACCESSIBLE | | | READILY)404.8 | | | PLEASE SEE THIS COMMENT IS FOR ALL | | | ELECTRICAL EQUIPMENT ON ELEV ON A4.2 | | | | | | 3)NOTE: NOTE #3 NO, PLEASE SEE GENERATOR | | | LOCATION IS NOT OK. AS OF THIS REVIEW | | | PLEASE SEE OTHER NOTES AS EQUIPMENT | | | LOCATION CAN NOT BE VERIFIED AS MOST | | | GEN'S REQUIRED A MIN OF 3' CLEARENCE ON | | | ALL SIDES AND SOME REQUIRE MORE. THERE | | | ARE VERY FEW WHICH REQUIRE LESS. | | | UNABLE TO VERIFY. | | | A/C DISC'S APPEAR TO BE OK AS SHOWN. | | | | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SEE MIN CLEARENCES | | | REQUIRED ON SAME ELEVATION FOR ALL A/C | | | DISC'S,GENERATOR, METER, ETC.? | | | 110.26. | | | | | | 4)NOTE: OK. | | | | | | 5)NOTE: OK. | | | | | | 6)NOTE: OK. | | | | | | 7)NOTE: OK. | | | | | | 8)NOTE: OK, HOWEVER SEE NEW NOTES | | | PERTAINING TO SD NOTES. | | | | | | 9)NOTE: NOTE #9 NO, PLEASE SEE THAT SOME | | | LTS ARE PERMITTED AS LONG AS ON A GFI | | | PROTECTED CIRCUIT, HOWEVER PLEASE SEE | | | AREAS ALOWWED FOR EXISTING AND NEW. | | | PLEASE SEE THE HOUSE IS NEW AND MUST | | | MEET ANY REQUIREMENTS FOR NEW | | | CONSTRUCTION EVEN IF POOL IS EXISTING. | | | PLEASE SEE RECEPTS MAY NOT BE WITHIN | | | 10FT OF POOL. (NO EXCEPTIONS!) | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SEE 680.22,680.22B ETC | | | FOR MIN CLEARENCES FOR ELECTRICAL | | | EQUIPMENT, DEVICES/RECEPTS AND LT | | | FIXTURES FROM POOL IN NEW CONSTRUCTION. | | | PLEASE SEE POOL HEATER, LTS ETC REDLINED | | | ON PLANS. | | | PLEASE SEE MIN 10' FOR RECEPTS. | | | PLEASE ALSO SEE NOTES FOR LOADS ETC OF | | | POOL EQUIPMENT. | | | PLEASE NOTE: LT FIXTURES W/IN 5' SHALL | | | BE 12' UP.(PLEASE SEE BACK PORCH)? | | | | | | 10)NOTE: OK. | | | | | | 11)NOTE; OK. | | | | | | 12)NOTE: NOTE #12 NO. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SUBMIT COMPLETE | | | SPECS/CUT SHEETS FOR LIGHTING CONTROL | | | PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE | | | SCHEDULING FOR THESE. | | | ALL SYSTEMS SHALL BE LISTED BY A NRTL. | | | PLEASE ALSO SEE COMMENT PERTAINIG TO | | | GEN. LOAD(S). | | | | | | 13)NOTE: OK. | | | | | | 14)NOTE: OK, STILL SHOWS A 24 CIRUCIT | | | PANEL YET THIS IS SHOWN AS 200A'S?? | | | | | | 15)NOTE: OK. | | | | | | 16)NOTE: OK. | | | | | | 17)NOTE: NOTE #17 NO. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND.**NUMBER OF FIX EXCEED GEN LT** | | | | | | 18)NOTE: OK. | | | | | | 19)NOTE: OK. | | | | | | 20)NOTE: OK. | | | | | | 21)NOTE: OK. | | | | | | 22)NOTE: OK. | | | | | | 23)NOTE: OK. | | | | | | 24)NOTE: OK. | | | | | | 25)NOTE: NOTE #25 NO? COULD NOT LOCATE | | | THE REQUIRED DISCONNECT. APPEARS TO SHOW | | | AN OUTLET/RECEPT ONLY?? | | | | | | * PREVIOUS REVIEW NOTE ** | | | PLEASE SEE MISSING REQUIRED | | | EMERGENCY DISCONNETC SWICTH TO BE | | | LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT | | | NO FURTHER THAN 50'. | | | PLEASE SEE 680.41 | | | | | | 26)NOTE: OK. | | | | | | 27)NOTE: OK. | | | | | | 28)NOTE: NOTE #28 NO. | | | ** PLEASE ALSO KNOW, "K" SWITCH IS NOT | | | ACCEPTABLE IN LEIU OF THE REQUIRED | | | DISCONNECTING MEANS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT COMPLETE | | | MANUFACTURE SPECS/CUT SHEETS FOR | | | GENERATOR , ATS . | | | PLEASE KNOW, GENERATOR CAN BE SUBMITTED | | | UNDER SEPARATE PERMIT AT A LATER DATE | | | WITH SEPARATE, SURVEY, PLANS, SPECS, | | | FEES ETC., HOWEVER, SPECS FOR ATS ARE | | | REQUIRED AT THIS TIME FOR REVIEW. | | | PLEASE SEE PLANS AND RISER INDICATE THIS | | | UNIT AS CONTAINING THE MAIN 1OF 1?? | | | PLEASE SEE230.76,230.79, 230.91, | | | 225.31-225.39 ETC | | | WHICH REQUIRES THE MANUAL MEANS OF | | | DISCONNECT TO BE LOCATED ON THE OUTSIDE | | | AND RATED FOR THE LOAD SERVED ETC. | | | UNABLE TO VERIFY CODE COMPLIANCE AT THIS | | | TIME. | | | (THIS WAS REQUESTED ON PREVIOUS REVIEW | | | ALSO). | | | PLEASE VERIFY IF ATS DOES CONTAIN THE | | | MAIN OR DOES NOT AS THIS WILL AFFECT THE | | | FOLLOWING. | | | | | | 29)NOTE: OK. | | | | | | 30)NOTE: OK, HOWEVER VERIFY THE #3 BEING | | | SHOWN. SEE NEW COMMENTS WITH RESPECT TO | | | CONDUIT FILL. | | | | | | 31)NOTE: NOTE #31 NO,PLEASE SEE LOADS | | | FOR GEN ON GEN LOAD SUMMARY DO NOT | | | INDICATE AN AIR CONDITIONING LOADS?? | | | PLEASE SEE NOTE MENTIONS TO SHEDD LOADS | | | BUT NO DETAIL WAS SUBMITED OR SHOWN. | | | PLEASE VERIFY NO A/C LOADS AS THE LOAD | | | SHOWN FOR GEN IS SHOWN AT 97A'S. | | | PLEASE ALSO VERY HOW THE THE ENTIRE | | | SERVICE IS BEING FED YET NOT ALL | | | ELECTRICAL WHICH IS BEING SHOWN PANEL | | | SCHEDULES ARE ON THE LOAD SUMMARY FOR | | | THE GEN?? | | | 215.5 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT COMPLETE LOAD | | | SHEDDING DETAILS FOR AUTOMATION SYSTEM | | | AS RISER DIAGRAM NOTES GENERATOR SHALL | | | BE ADEQUATE FOR THE LOAD TO BE SERVED. | | | 702.5 | | | THIS IS REQUIRED AT THIS TIME, UNLESS | | | GEN IS NOT PERMITTED AT THIS TIME. | | | SEE PREVIOUS NOTES. | | | | | | 32)NOTE: OK. | | | | | | 33)NOTE: OK. | | | | | | 34)NOTE: OK. | | | | | | 35)NOTE: OK. | | | | | | ***** NEW NOTES ***** | | | | | | 36) NOTE: PLEASE SEE SD'S SHALL BE | | | INSTALLED PER NFPA-72 | | | 11.5.1.1,11.8.3.5,11.8.3 | | | PLEASE SEE NOTES MENITONS 12" FROM AIR | | | SUPPLIES AND RETURNS. PLEASE SEE NFPA AS | | | NOTED ABOVE WHERE NO SD'S AARE PERMITTED | | | WITHIN 3' FROM SUPPLIES AND MIN 5' FROM | | | RA BASED ON MANUFACTURES SPEC'S. | | | PLEASE ADJUST ALL NOTES. | | | | | | 37) NOTE: PLEASE SEE PLANS NOTES IN MANY | | | LOCATIONS WITH REFERENCE TO THE "LATEST | | | EDITION" OF THE CODE. THIS IS NOT | | | PERMITTED AS THE LATEST EDITION WOULD BE | | | THE 2004 FBC AND THE LATEST EDITION OF | | | THE NEC HAS NOT BEEN ADOPTED BY THE | | | STATE OF FLORIDA AS OF YET. | | | PLEASE SEE THE FOLLOWING CODES SHALL BE | | | REFLECTED ON PLANS AT A MIN ON | | | ELECTRICAL SHEETS. | | | IF REMAINING UNDER THE 2001 FBC THEN | | | THE ELECTRICAL PLANS SHALL REFLECT THE | | | 2001 FBC, 2002 NFPA-70 (NEC), 2002 | | | NFPA-72, NFPA-101 2003 AT A MIN. | | | PLEASE SEE OTHER REVIEWER(S) AND CODES | | | TO APPLY. | | | | | | 38) NOTE: PLEASE SEE A PREVIOUS NOTE | | | MENTIONED THAT NOW THE "EQUIPMENT | | | GROUNDING CONDUCTORS" ARE NOW SHOWN | | | HOWEVER ARE SIZED AT #3'S?? PLEASE KNOW, | | | THIS IS OK, ALTHOUGH THEY ARE ONLY | | | REQUIRED TO BE SIZED PER 250.122 , BUT | | | IF SHOWN ON PLANS THIS SIZE, THEN THIS | | | IS WHAT WILL BE REQUIRED. | | | ** PLEASE ALSO KNOW, BASED ON FEEDERS | | | SHOWNA DN THE EQUIPMENT GROUNDING | | | CONDUCTORS NOW SHOWN , PLEASE SEE MAX | | | CONDUIT FILL PER TABLES 9, SCH 80. | | | PLEASE ADJUST CONDUIT SIZES AS NEEDED. | | | 215.5 | | | | | | 39) NOTE: PLEASE SEE MISSING E-1 ON ONE | | | SET OF ELECTRICAL PLANS. | | | | | | 40) NOTE: PLEASE ALSO SEE ONE SET IS | | | ALSO MISSING THE "RAISED" SEAL ON SOME | | | "S" SHEETS. | | | PLEASE KNOW, AS OF DEC 31ST, 2005 IT IS | | | NO LONGER ACCEPTABLE USE ENGINEER'S | | | SEALS WITH THE WORDING OF "CERTIFICATE". | | | PLEASE SEE RULING AS PASSED BY THE | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS | | | IN FEB 04 WHICH REQUIRES ALL ENGINEERS | | | TO OBTAIN A NEW SEAL CONTAINING THE | | | WORDING OF "LICENSE". AN EXTENSION WAS | | | GIVEN TO DEC 31ST, 2005. | | | SEE BUILDING REVIEW NOTES, THIS IS ONLY | | | NOTED IN ELECTRICAL REVIEW FOR | | | INFORMATIONAL PURPOSE AS AN FYI. | | | | | | 41) NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO REPEAT | | | COMMENTS FOR CODE COMPLIANCE. | | | PLEASE SEE THAT ALL COMMENTS FROM | | | PREVIOUS REVIEWS MUST BE ADDRESSED. | | | | | | 42) NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT, SEE NEW MAINS NOW | | | ADDED WHICH DO NOT INDICATERATINGS. | | | 110.9,215.5 | | | | | | **PLEASE SEE ANY OTHER POSSIBLE COMMENTS | | | FROM OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE REMOVE ANY/ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | PLEASE SUBMIT ONE COPY OF OLD SHEETS | | | FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | 2006-06-21 00:00:00 | IN ELEC FOR REVIEW. | | 2006-06-16 00:00:00 | | | | | | | | | | SHEET E1 IS MISSING FROM ONE SET OF | | | PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-10-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-07 |
Time |
20:39 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-10-07 |
Time |
19:01 |
Sent To |
M |
|
| Notes |
| 2005-10-07 00:00:00 | ************* UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE MAX HEIGHT FOR | | | ELECTRICLA METERCAN PER SECTION 6 OF FPL | | | SERVICE INSTALLATIONS GUIDELINES SHALL | | | BE 6' TO THE CENTER OF METER. | | | PLEASE SEE ELEVATION PLANS A4.2 CLEARLY | | | SHOW THIS HIGHER. | | | | | | 2)NOTE: PLEASE SEE MAX HEIGHT OF | | | DISCONNECTING EQUIPMENT/SWITCHES SHALL | | | BE 6'7" WITH OUT RESORTING TO LADDERS | | | ETC. | | | 440.11, 100 (DEFINITIONS) ACCESSIBLE | | | READILY)404.8 | | | PLEASE SEE THIS COMMENT IS FOR ALL | | | ELECTRICAL EQUIPMENT ON ELEV ON A4.2 | | | | | | 3)NOTE: PLEASE SEE MIN CLEARENCES | | | REQUIRED ON SAME ELEVATION FOR ALL A/C | | | DISC'S,GENERATOR, METER, ETC.? | | | 110.26. | | | | | | 4)NOTE: PLEASE SEE MISSING DISC'S FOR | | | POOL EQUIPMENT ON THAT SIDE OF HOUSE. | | | PLANS MENTIONS POOL EXISTING? PLEASE | | | ALSO SEE LOAD CALCULATIONS MENTIONS EST | | | LOAD? IF EXISTING, LOADS SHOULD BE | | | KNOWN. | | | | | | 5)NOTE: PLEASE SEE CABANA BLDG IS NOT | | | PART OF MAIN HOUSE AND IS REQUIRED TO | | | HAVE DISCONNECTING MEANS PER 225.31. | | | PLEASE ALSO SEE GROUPING PER 225.34, | | | PLEASE KNOW, IF MORE THAN 6 INDIVIDUAL | | | CIRCUITS AT THIS DETACHED BLDG, A PANEL | | | WILL BE REQUIRED AND A DISCONNECT OR MCB | | | PANEL WILL BE REQUIRED. | | | PLEASE ADJUST RISER DIAGRAM AND SEE NEXT | | | NOTE. | | | | | | 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING | | | ELECTRODE SYSTEM AT DETACHED BLDG. | | | | | | 7)NOTE: PLEASE SEE MISSING SW AND LT AT | | | CABANA BATH PER 210.70 | | | | | | 8)NOTE: PLEASE SEE SD'S WILL BE REQUIRED | | | AT CABANA AT FIRST AND SECOND FLRS. | | | FIRST FLR IS CONSIDERED AN ADAPTABLE | | | SLEEPING RM WITH BATH RM. | | | PLEASE ALSO SEE SD'S REQUIRED ON ALL | | | LEVELS OF A MULTI-LEVEL BLDG. | | | NFPA-72 11.5.1.1 | | | | | | 9)NOTE: PLEASE SEE 680.22,680.22B ETC | | | FOR MIN CLEARENCES FOR ELECTRICAL | | | EQUIPMENT, DEVICES/RECEPTS AND LT | | | FIXTURES FROM POOL IN NEW CONSTRUCTION. | | | PLEASE SEE POOL HEATER, LTS ETC REDLINED | | | ON PLANS. | | | PLEASE SEE MIN 10' FOR RECEPTS. | | | PLEASE ALSO SEE NOTES FOR LOADS ETC OF | | | POOL EQUIPMENT. | | | PLEASE NOTE: LT FIXTURES W/IN 5' SHALL | | | BE 12' UP.(PLEASE SEE BACK PORCH)? | | | | | | 10)NOTE: PLEASE SEE PANEL SCHEDULE "C" | | | INDICATES "POOL EQUIPMENT" AS 14.2KW, | | | HOWEVER PLEASE SEE THAT ALL CONTINUOUS | | | LOADS ARE FIGURED AT 125%. | | | PLEASE SEE THIS APPEARS TO ONLY FEED ONE | | | PIECE OF EQUIPMENT? COOULD NOT LOCATE | | | POOL PUMP, LT ETC. IS THERE A POOL PANEL | | | AND THE 2P 70A A SUB-FEED? | | | PLEASE SEE IF THIS IS NOT ALREADY FIGURE | | | AT CONTINUOUS LOAD, 70A OCP WOULD NOT BE | | | LARGE ENOUGH. 215.3,230.42,680.9 ETC. | | | | | | 11)NOTE; PLEASE SEE BLDG PLANS INDICATE | | | A "WASHER AND DRYER" IN GARAGE AS | | | FUTURE, HOWEVER ELECTRICAL PLANS SEEM TO | | | SHOW THESE , BUT NOT NOTED FOR FUTURE, | | | NOW ? NO ELECTRICAL DEVICES SHOWN. | | | IF THESE UNITS ARE NOT GOING TO BE | | | INSTALLED, PLEASE REMOVE FROM PLANS. | | | | | | 12)NOTE: PLEASE SUBMIT COMPLETE | | | SPECS/CUT SHEETS FOR LIGHTING CONTROL | | | PANELS(AUTOMATION SYSTEM) PLEASE PROVIDE | | | SCHEDULING FOR THESE. | | | ALL SYSTEMS SHALL BE LISTED BY A NRTL. | | | PLEASE ALSO SEE COMMENT PERTAINIG TO | | | GEN. LOAD(S). | | | | | | 13)NOTE: PLEASE SEE PLANS CALL FOR | | | CIRCUITING OF WHAT APPEARS TO BE THE | | | ELEVATOR ON PANEL C-25, 27, HOWEVER | | | PLEASE SEE PANEL "C" IS BEING SHOWN WITH | | | ONLY 24 CIRCUITS?? | | | PLEASE SEE PANEL "D" SEEMS TO SHOW THIS. | | | (MISPRINT). | | | | | | 14)NOTE: PLEASE VERIFY CIRCUITING SHOWN | | | FOR PANEL "C" AS BEING A 24 CIRCUIT | | | PANEL AND ALSO BEING 200A? | | | 215.5 | | | | | | 15)NOTE: PLEASE SEE MISSING EGRESS | | | LIGHTING CONTROL FROM GARAGE TO FRONT | | | PORCH AREA. 210.70 (3-WAY?) | | | | | | 16)NOTE: PLEASE CLARIFY CABANA LTS WHICH | | | SEEM TO BE SHOWN AS "RECESSED LT" | | | FIXTURES. PLEASE SEE PLANS CALL FOR A | | | "WOOD DECK" ABOVE WHICH DOES SEEM TO | | | DETAIL WHEATHER PROTECTION. AN OUTDOOR | | | WP RECESSED IS NOT KNOWN OF AT THIS | | | TIME. PLEASE ALSO VEIFY FAN LOCATION. | | | IF THESE ARE OUTDOOR RAINTIGHT FIXTURES, | | | PLEASE PROVIDE INFORMATION. | | | 90.7,110.3 | | | | | | 17)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND.**NUMBER OF FIX EXCEED GEN LT** | | | | | | 18)NOTE: PLEASE SEE MISSING RECEPT ON | | | 2ND FLR PASSAGE/HALLWAY. 210.52H | | | REDLINED ON PLANS. | | | | | | 19)NOTE: PLEASE CLARIFY RECEPT (B-7) | | | LAUNDRY RECEPT SHOWN BEHIND DRYER? | | | THIS IS ONLY A NOTE. | | | | | | 20)NOTE: PLEASE SEE 2ND FLR, ROOM | | | LOCATED OUTSIDE "DUMB WAITER", ON A3.2 | | | THIS SHOWS A "BAR RM" WITH A FRIG ETC, | | | HOWEVER ELECTRICAL PLANS DO NOT IDENTIFY | | | THIS ROOM AND NO RECEPT IS SHOWN FOR | | | FRIG? PLEASE ADJUST , PANEL | | | SCHEDULE,LOADS ETC. | | | 215.5 | | | | | | 21)NOTE: PLEASE INDICATE CIRCUIT FOR | | | "JACUZZI TUB" LOCATED IN MASTER BATH RM. | | | 215.5 | | | PLEASE ADJUST LOAD CALCS, PANEL SCHEDULE | | | ETC AS A JACUZZI RECEPT IS SHOWN ON | | | PANEL "D" TO ROOF UNIT> | | | | | | 22)NOTE: PLEASE SEE RECEPT SHOWN AT BAR | | | ON 3RD FLR IS REQUIRED TO BE GFI LOCATED | | | WITH IN 6' OF WET BAR SINK. 210.8A7 | | | | | | 23)NOTE: PLEASE IDENTIFY A DISCONNECT | | | SWITCH BEING SHOWN AT 3RD LEVEL, TILED | | | TERRACE AREA? | | | NO CIRCUITING , ?? | | | | | | 24)NOTE: PLEASE SEE MIN CLEARENCES | | | REQUIRED FOR LIGHTING FIXTURE(SHOWN AS | | | FUTURE) (J-BOXES) CIRCUITING TO D-6 AT | | | 3RD FLR AREA. PLEASE SEE TWO BOXES WITH | | | IN ZONE OF JACUZZI/HOT TUB. | | | 680.40 | | | | | | 25)NOTE: PLEASE SEE MISSING REQUIRED | | | EMERGENCY DISCONNETC SWICTH TO BE | | | LOCATED ATLEAST 5' FROM SPA/HOT TUB BUT | | | NO FURTHER THAN 50'. | | | PLEASE SEE 680.41 | | | | | | 26)NOTE: PLEASE CORRELATE PLANS, PANEL | | | CIRCUITING FOR WHAT APPEARS TO BE A A/C | | | UNIT AT 3RD FLR?? | | | PLEASE SEE PLANS SHOWS A "D-7" , HOWEVER | | | PANEL SCHEDULE SHOWS CIRCUIT "D-7,9"?? | | | FOR AN A/C UNIT?? | | | 215.5 | | | IS THIS A WALL UNIT? PLUG-IN? DISC? | | | 440.11 | | | | | | 27)NOTE: PLEASE SEE A MEANS OF EGRESS | | | LTIGHTING CONTROL SWITCH IS REQUIRED AT | | | (4TH) LEVEL ROOF TILED AREA DOWN TO 3RD | | | LEVEL. PLEASE SHOW AS WP.210.70 | | | (3-WAY)?? | | | | | | 28)NOTE: PLEASE SUBMIT COMPLETE | | | MANUFACTURE SPECS/CUT SHEETS FOR | | | GENERATOR , ATS . | | | PLEASE KNOW, GENERATOR CAN BE SUBMITTED | | | UNDER SEPARATE PERMIT AT A LATER DATE | | | WITH SEPARATE, SURVEY, PLANS, SPECS, | | | FEES ETC., HOWEVER, SPECS FOR ATS ARE | | | REQUIRED AT THIS TIME FOR REVIEW. | | | PLEASE SEE PLANS AND RISER INDICATE THIS | | | UNIT AS CONTAINING THE MAIN 1OF 1?? | | | PLEASE SEE230.76,230.79, 230.91 ETC | | | WHICH REQUIRES THE MANUAL MEANS OF | | | DISCONNECT TO BE LOCATED ON THE OUTSIDE | | | AND RATED FOR THE LOAD SERVED ETC. | | | UNABLE TO VERIFY CODE COMPLIANCE AT THIS | | | TIME. | | | (THIS WAS REQUESTED ON PREVIOUS REVIEW | | | ALSO). | | | PLEASE VERIFY IF ATS DOES CONTAIN THE | | | MAIN OR DOES NOT AS THIS WILL AFFECT THE | | | FOLLOWING. | | | | | | 29)NOTE: PLEASE SEE 250.24 FOR THE | | | LOCATION PERMITTED FOR THE GROUNDING | | | ELECTRODE SYSTEM. | | | (IF THERE IS ANY QUESTION, GROUNDING | | | ELECTRODE CONDUCTOR MAY BE LOCATED AT | | | METER. | | | | | | 30)NOTE: PLEASE ALSO SEE MISSING | | | EQUIPMENT GROUNDING CONDUCTOR BETWEEN | | | THE FIRST MEANS OF DISCONNECT(?) AND | | | GUTTER. | | | 250.110,250.122,250.24 | | | | | | 31)NOTE: PLEASE SUBMIT COMPLETE LOAD | | | SHEDDING DETAILS FOR AUTOMATION SYSTEM | | | AS RISER DIAGRAM NOTES GENERATOR SHALL | | | BE ADEQUATE FOR THE LOAD TO BE SERVED. | | | 702.5 | | | THIS IS REQUIRED AT THIS TIME, UNLESS | | | GEN IS NOT PERMITTED AT THIS TIME. | | | SEE PREVIOUS NOTES. | | | | | | 32)NOTE: PLEASE SEE PANEL SCHEDULE "D", | | | CIRCUITS 10/12 WHICH SHOWS A FEED TO A | | | "SPA" , HOWEVER THIS COULD NOT BE LCATED | | | ON PLANS?? | | | 215.5 | | | | | | 33)NOTE: PLEASE SEE LOAD CALCULATIONS | | | WHICH INDICATE 10,000 SQ FT FIGURED FOR | | | HOUSE , YET APPLICATION AND BLDG PLANS | | | DO NOT CORRELATE WITH THIS NUMBER?? | | | 215.5 | | | | | | 34)NOTE: PLEASE BE SURE ALL DEDICATE | | | ITEMS ON PANEL SCHEDULES ARE FIGURED | | | INTO LOAD CALCAULTIONS. SEE PREVIOUS | | | NOTES WITH RESPECT TO FRIG, POOL | | | EQUIPMENT ETC. | | | PLEASE SEE A DEDICATED LAUNDRY | | | LOAD/CIRCUIT IS SHOWN ON PANEL "B", | | | HOWEVER THIS NOT FIGURED INTO LOAD | | | CALCULATIONS FOR MAIN HOUSE. | | | PLEASE SEE EXTERIOR LTS ON PANEL "D" IS | | | SHOWNAT 6.3 KW WHICH IS ABOVE 3 WATTS | | | PER SQ FT ALREADY FIGURED?? | | | 215.5 | | | | | | 35)NOTE: PLEASE SEE LOCATION OF TVSS | | | SHOWN AT LOCATION WHICH APPEARS TO BE | | | TAPPED INTO THE PIPE LOCATED BETWEEN | | | GUTTER AND ATS?? | | | PLEASE SEE 285.21 FOR LOCATIONS | | | PERMITTED. | | | | | | **PLEASE SEE ANY OTHER POSSIBLE COMMENTS | | | FROM OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE REMOVE ANY/ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | PLEASE SUBMIT ONE COPY OF OLD SHEETS | | | FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-14 |
Time |
17:41 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2005-07-13 |
Time |
12:48 |
Sent To |
M |
|
| Notes |
| 2005-07-14 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SUBMIT MANUFACTURERS SPECIFICATIONS | | | FOR THE GENERATOR AND THE TRANSFER | | | SWITCH. PLEASE NOTE THE TRANSFER SWITCH | | | MUST BE SERVICE RATED(225.36) AND MUST | | | BE CAPABLE OF DISCONNECTING ALL CIRCUITS | | | SIMULTANEOUSLY, 230.71. | | | | | | 2} WHAT IS THE BOX BEING FED WITH 500MCM | | | (ON THE RISER) FROM THE BOTTOM OF THE | | | TRANSFER SWITCH? | | | | | | 3} THE WASHER, DRYER, HOT TUB/SPA, | | | ELEVATOR,POOL PUMP AND POOL HEATER, ARE | | | NOT IN THE LOAD CALCS. | | | | | | 4} PLEASE INDICATE THE FEEDER TAP | | | CONDUCTOR SIZES(LEAVING THE GUTTER). | | | | | | 5} THE SMOKE DETECTORS ARE REQUIRED TO | | | BE INTERCONNECTED PER 905.2.1 FBC. THEY | | | ARE SHOWN ON TWO DIFFERENT CIRCUITS ON | | | THE PLAN. ALSO PLEASE NOTE THEY MUST BE | | | ARC FAULT PROTECTED PER 210.12. THIS | | | DOES NOT MEAN THEY MUST BE ON A BEDROOM | | | CIRCUIT NECESSARILY. | | | | | | 6} THE ELEVATOR RECEPTACLE AND LIGHT | | | MUST BE ON A SEPERATE BRANCH CIRCUIT PER | | | 620.23, SEE A-8 CIRCUIT ALSO FEEDS | | | DINING ROOM LIGHTING. | | | | | | 7} THE CONDENSING UNIT DISCONNECTS AND | | | ELECTRIC METER DO NOT APPEAR TO HAVE | | | CLEARANCE PER 110.26. SHOW THE LOCATION | | | OF THE REST OF THE SERVICE AND GENERATOR | | | EQUIPMENT ONPLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2008-01-18 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-01-18 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-01-18 |
Time |
15:50 |
Sent To |
PC |
|
| Notes |
| 2008-01-18 16:46:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | GAS PLAN REVIEW: | | | REVISION DENIED: | | | | | | 1. NOTE: AS OF 2/6/07 GAS RISER DIAGRAMS WERE REMOVED | | | FROM PLANS. PLEASE REFERENCE THE PERMIT INFORMATION | | | ATTACHED TO THESE COMMENTS INDICATING THIS. A GAS | | | PERMIT APPLICATION IS REQUIRED FOR THE PROPOSED GAS | | | SYSTEM. ALICENSED GAS OR PLUMBING CONTRACTOR SHALL | | | SUBMIT PLANS WITH PERMIT APPLICATION. PLEASE ONLY | | | SUBMIT PLAN SHEETS PERTAINING TO THE PROPOSED GAS | | | SYSTEM. TWO COMPLETE SETS OF PLANS ARE NOT REQUIRED FOR | | | GAS PLANS. PER CHAPTER 1, CITY AMENDMENTS SECTION | | | *105.1 REQUIRED. | | | | | | 2. SHEETS A3.1, A3.2, AND A3.3 FLOOR PLANS HAVE TITLE | | | BLOCKS WITH COPIED SIGNATURES OF A DESIGN PROFESSIONAL | | | AND ARE NOT SEALED. PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE | | | AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | | DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | FL ADMIN CODE 61G16.003 ARCHITECTS | | | | | | 3. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. **THE SUBMITTED PLANS DO NOT HAVE ALL | | | CUT SECTIONS OF PIPE WITH CORRESPONDING LENGTHS | | | INDICATED. THIS IS REQUIRED TO VERIFY THE NEXT | | | COMMENT. | | | | | | 4. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). **PLEASE CLEARLY INDICATE | | | THE GAS SYSTEMS LONGEST LENGTH. PER FBC FUEL GAS | | | SECTION *401.1 SCOPE. | | | | | | 5. CLEARLY INDICATE THE LOCATION OF THE REQUIRED MP | | | REGULATORS ON THE GAS ISOMETRIC RISER DIAGRAM. PER FBC | | | FUEL GAS SECTION *401.1 SCOPE. | | | | | | 6. PROVIDE TWO COPIES OF MANUFACTURER'S SPECFICATION | | | OF THE MP REGULATORS INDICATING THE MAKE, MODEL NUMBER, | | | AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING | | | LABORATORY. | | | | | | 7. NOTE: GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES | | | (FUTURE) SHALL BE CLEARLY INDICATED AS BEINGCAPPED | | | GAS TIGHT ON PLANS. IF GAS DELIVERY PRESSURE IS 2 PSI | | | OR GREATER MP REGULATORE SHALL BE INSTALLED PRIOR TO | | | FINAL INSPECTION. PER FBC FUEL GAS SECTION *404.12 | | | OUTLET CLOSERS ANS SECTION *401.1 SCOPE. | | | | | | 8. GAS PLANS ARE INDICATING A FUTURE GENERATOR PLEASE | | | BE AWARE THAT FUTURE GENERATOR GAS PIPING AT OWN RISK, | | | AND A SEPERATE RESIDENTIAL GENERATOR PERMIT IS REQUIRED | | | WITH ZONING APPROVAL OF GENERATOR PLACEMENT. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-02-06 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-02-06 |
Time |
15:09 |
Sent To |
B |
|
| Notes |
| 2007-02-06 15:11:37 | GAS RISER DIAGRAM REMOVED FROM PLANS. GAS PLANS WILL BE | | | SUBMITED BY GAS CONTRACTOR. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2006-07-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-03 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-03 |
Time |
08:30 |
Sent To |
P |
|
| Notes |
| 2006-07-03 00:00:00 | | | | DENIED; | | | THIRD REQUEST; | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | 2.SUBMIT MANUFACTURE SPEC SHEETS FOR GAS | | | LIGHTS AND GENERATOR. | | | 3. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-10-11 |
Time |
08:54 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-10-11 |
Time |
08:54 |
Sent To |
M |
|
| Notes |
| 2005-10-11 00:00:00 | DENIED; | | | 1.PLEASE SIZE ALL CUT OFF PIPE. (SECOND | | | REQUEST) | | | 2.SHOW FUTURE WATER HEATER ON RISER | | | DIAGRAM. PIPE SHOULD BE INSTALLED WITH | | | SHUTOFFVALVE AND PLUG IF NOT USED. | | | 3.PLESE SUBMIT MANUFACTORS CUT SHEETS | | | FOR GAS LAMPS AND GENERATOR. | | | 4.MOST BLACK IRON INSTALLATIONS ARE | | | WELDED 2" AND LARGER, UNDER 2" IS SCREW | | | PIPE. IS ALL PIPE TO BE WELDED? | | | 5. PLEASE ADD TO GAS NOTES, WELDER | | | CERTIFICTIONS ARE REQUIRED WHEN GAS | | | PERMIT IS APPLYIED FOR. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2009-07-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-22 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-22 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2009-07-22 16:12:49 | REVISION TO RM DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2009-01-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-21 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-21 |
Time |
16:44 |
Sent To |
B |
|
| Notes |
| 2009-01-21 16:45:04 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-10-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-16 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-16 |
Time |
09:46 |
Sent To |
B |
|
| Notes |
| 2008-10-16 09:47:13 | TO "LMARTINEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-10-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-16 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-16 |
Time |
09:42 |
Sent To |
B |
|
| Notes |
| 2008-10-16 09:43:18 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-06 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-06 |
Time |
15:42 |
Sent To |
B |
|
| Notes |
| 2008-05-06 15:43:10 | TO "LMARTINEZ" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-15 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-15 |
Time |
15:47 |
Sent To |
G |
|
| Notes |
| 2008-01-15 15:47:39 | TO "G" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-01-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-16 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-16 |
Time |
12:46 |
Sent To |
E |
|
| Notes |
| 2007-01-16 12:47:14 | REMOVED FROM INCOMING AND ROUTED TO ELEC. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-12-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-26 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-26 |
Time |
09:31 |
Sent To |
Z |
|
| Notes |
| 2006-12-26 09:31:59 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-29 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-29 |
Time |
11:57 |
Sent To |
M |
|
| Notes |
| 2006-06-29 00:00:00 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-14 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-14 |
Time |
10:18 |
Sent To |
E |
|
| Notes |
| 2006-06-14 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-10-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-06 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-06 |
Time |
16:36 |
Sent To |
E |
|
| Notes |
| 2005-10-06 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-30 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-30 |
Time |
10:21 |
Sent To |
Z |
|
| Notes |
| 2005-09-30 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-12 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-12 |
Time |
15:05 |
Sent To |
E |
|
| Notes |
| 2005-07-12 00:00:00 | TO "SFR" E |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-28 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-28 |
Time |
14:44 |
Sent To |
Z |
|
| Notes |
| 2005-06-28 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-29 |
Time |
13:58 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-06-29 |
Time |
13:57 |
Sent To |
P |
|
| Notes |
| 2006-06-29 00:00:00 | *** PROVISO *** | | | 1) PROVIDE COMBUSTION AIR FOR GAS | | | CLOTHES DRYER ON SECOND FLOOR LAUNDRY | | | ROOM, PER 2001 FBC/M 701 . | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-10-11 |
Time |
10:43 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-10-11 |
Time |
10:43 |
Sent To |
B |
|
| Notes |
| 2005-10-11 00:00:00 | *** DENIED *** | | | 1) NEED A/C EQUIP. LISTED ON PLANS, | | | MANUFACTURE, MODEL NUMBER, TONS, SEER, | | | FOR EACH UNIT (AIR HANDLERS AND | | | CONDENSER UNITS) . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-19 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-07-19 |
Time |
18:38 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-07-19 |
Time |
17:55 |
Sent To |
P |
|
| Notes |
| 2005-07-19 00:00:00 | PLAN DENIED | | | 1) PLEASE PROVIDE EQUIPMENT SCHEDULE ON | | | PLANS. | | | 2) PLEASE SUBMIT MANUFACTURER | | | INSTALLATION INSTRUCTIONS ON FIRE PLACE | | | AND KITCHEN DOWNDRAFT. | | | 3) PLEASE REFER TO SECTION 307.2.4 | | | AUXILIARY DRAIN PANS | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-01-20 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-01-20 |
Time |
13:48 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-07-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-03 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-03 |
Time |
08:42 |
Sent To |
B |
|
| Notes |
| 2006-07-03 00:00:00 | DENIED; | | | 1.CLEANOUTS ON AUTOMATIC CLOTHES WASHER | | | REQUIRED TO BE INSTALLED AT 48"AFF. | | | 2.SHOW ROOF DRAINS AND SECONDARY | | | (EMERGENCY) DRAINS AND CALCULATIONS PER | | | CHAPTER 11. | | | 3.REMOVE AIR CHAMBER SYMBAL FROM WATER | | | ISOMETRICS. AIR CHAMBERS ARE NOT AN | | | APPROVED PRODUCT. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-10-11 |
Time |
08:27 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2005-10-11 |
Time |
08:27 |
Sent To |
G |
|
| Notes |
| 2005-10-11 00:00:00 | DENIED; | | | 1.SECONDARY DRAIN PROTECTION REQUIRED | | | PER. FBC-2001 PLUMBING SEC. 1107.1. | | | 2.HOT WATER CIRCULATION SYSTEM MUST | | | COMPLY WITH FBC 2001 CHAPTER 13. (ENERGY | | | CODE) SEC. 612.1ABC.4 AND 612.1ABC.5 | | | SHOW HOW PUMP WILL TURN OFF TO SAVE | | | ENERGY. HOT WATER PIPING TO BE INSULATED | | | TO SAME ENERGY. | | | 3.WATER RISER DIAGRAM; SHOW COMPLIANCE | | | WITH SEC. 604.9. PLEASE REMOVE ALL | | | SYMBOLS NOT REQUIRED. (AIR CHAMBERS ARE | | | NOT AN APPROVED PRODUCT. | | | 4.JACUZZI DRAIN SHALL BE A FLOOR SINK | | | INSTALLED 1" ABOVE DECK SURFACE, THIS | | | WILL PREVENT RAIN WATER AND WILL CATCH | | | THE INDIRECT DISCHARGE FROM JACUZZI. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-23 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-07-23 |
Time |
08:44 |
Rev Time |
1.25 |
| Received By |
jleech |
Date |
2005-07-23 |
Time |
08:44 |
Sent To |
B |
|
| Notes |
| 2005-07-23 00:00:00 | DENIED; | | | 1.SANITARY RISER DIAGRAM; | | | A.VENT AND WASTE PIPING SYSTEM IS NOT | | | REQUIRED IN A HOSE SYSTEM. | | | B.FIRST FLOOR BATHROOM NOT TIED TO | | | BUILDING DRAIN. | | | C.WASHING MACHINE ON FIRST FLOOR NOT | | | VENTED. | | | D.ALL SANITARY DRAINAGE PIPING SHALL | | | BE SIZED FOR FUTURE FIXTURES,(3" FLOOR | | | DRAIN FOR JACUZZI) | | | E.2-WAY CLEANOUT REQUIRED FOR CABANA | | | 3' OUTSIDE BUILDING. | | | 2.SHOW SIZE OR ROOF SCUPPERS AND | | | MATERIAL USED. ALSO SHOW TOTAL SQUIRE | | | FOOTAGE CAULKS. PER CHAPTER 11 FBC | | | PLUMBING. | | | GAS; | | | 1.SEE "GAS PERMIT APPLICATION | | | REQUIREMENTS" SHEET. COMPLY WITH ITEMS | | | 1, 3, 4, 7, AND 9. | | | 2.ALL FUTURE GAS EQUIPMENT SHOULD BE | | | ADDED TO CAULCULATIONS SO GAS PIPE | | | SIZEDOES NOT CHANGE WHEN EQUIPMENT IS | | | ADDED. | | | 3.IS GENERATOR NAT. GAS IF SO CAULKS | | | SHOULD BE INCLUDED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2007-01-24 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2007-01-24 |
Time |
10:51 |
Sent To |
B |
|
| Notes |
| 2007-01-24 11:07:45 | PROVISO: COLUMNS/WALL/GATE/FENCEARE NOT APPROVED WITH | | | THE THIS PERMIT. SHALL APPLY FOR A SEPARATE PERMIT AND | | | PROVIDE EASEMENT APPROVAL FROM CITY OF WEST PALM BEACH | | | UTILITY DEPT.MAXIMUM HEIGHT ALLOWED WITHIN FRONT 25FT | | | SETBACK IS 4FT ONLY. PLEASE PROVIDE WALL DETAIL FOR THE | | | COLUMNS, GATE, FENCE, WALL. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
2007-01-12 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2007-01-12 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2007-01-12 |
Time |
14:57 |
Sent To |
M |
|
| Notes |
| 2007-01-12 14:58:23 | DENIED, | | | 1. PLEASE PROVIDE UPDATED SITEPLANS WITH PROPOSED WORK. | | | CANNOT USE DRAINAGE PLANS AND THE VOIDED SITEPLAN | | | (06/09/05). | | | 2. SITEPLAN SHALL PROVIDE THE WIDTH OF THE PROPOSED | | | DRIVEWAY AND SETBACK OF THE PROPOSED STRUCTURES WITH | | | DISTANCE SEPARATION OF THE PROPOSED CABANA AND MAIN | | | STRUCTURE. | | | 3. THE MAXIMUM HEIGHT FOR WALL/COLUMNS/GATES CAN ONLY | | | BE 4FT WITHIN THE 25FT SETBACK. | | | | | | NOTE: SEPARTE PERMIT FOR THE FENCE/WALL/COLUMN WITH | | | EASEMENT APPROVAL FROM THE CITY OF WEST PALM BEACH | | | UTILITY DEPT. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2006-06-28 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-06-28 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-06-28 |
Time |
12:38 |
Sent To |
I |
|
| Notes |
| 2006-06-28 00:00:00 | DENIED. | | | 1. THE COVERED TERRACE MUST SIT BEYOND | | | THE 25FT FRONT SETBACK.SITEPLAN SHOWS | | | IT AT 23.8FT. | | | | | | | | | | | | NOTE: | | | THE PROPOSED A/C UNIT SHALL NOT BE | | | CLOSER THAN 6FT FROMSIDE PROPERTY | | | LINE. | | | | | | NOTE: MUST PULL A SEPERATE PERMIT FOR | | | POOL/SPA/DECK/SCREEN ENCLOSURE AND | | | WALL/GATE/FENCE WITH UTILITY EASEMENT | | | APPROVAL FROM THE CITY OF WEST PALM | | | BEACH UTILITY DEPT. | | | | | | NOTE:THE WALL/COLUMNS/FENCE/GATE CAN | | | ONLY BE A MAXIMUM HEIGHT OF 4FT ONLY | | | WITHIN THE 25FT FRONT SETBACK. | | | | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2006-06-22 00:00:00 | NEW SHEETS, WITH REVISIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-10-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-10-06 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-10-06 |
Time |
16:17 |
Sent To |
I |
|
| Notes |
| 2005-10-06 00:00:00 | NOTE: MUST PULL A SEPERATE PERMIT FOR | | | GATE/WALL/FENCE/COLUMNS WITH EASEMENT | | | APPROVAL FROM THE CITY OF WEST PALM | | | BEACH UTILITIES DEPT. | | | | | | NOTE: FENCE/GATE/WALL/COLUMNS CAN ONLY | | | BE MAXIMUM 4FT WITHIN THE FIRST 25FT | | | FRONT SETBACK.BEYOND THE 25FT FRONT | | | SETBACK MAXIMUM HEIGHT IS 6FT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-07-11 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-07-11 |
Time |
17:09 |
Sent To |
I |
|
| Notes |
| 2005-07-11 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE THE DIMENSION FOR THE | | | DRIVEWAY & WALKWAY (LENGTH & WIDTH). | | | 2. NEED TO APPLY FOR A SEPERATE PERMIT | | | FOR FENCE/GATE/COLUMNS/WALLS WITH THE | | | UTILITY EASEMENT APPROVAL FROM CITY OF | | | WEST PALM BEACH UTILITY DEPT. | | | 3. WALL/GATE/FENCE/COLUMNS CAN ONLY BE A | | | MAX OF 4FT HIGH WITHIN THE FRONT SETBACK | | | (25FT). | | | 4. MAIN STRUCTURE MUST MEET THE HEIGHT | | | REQUIREMENT OF 33FT (30 FOR STRUCTURE | | | AND 10% FOR CHIMNEY). STRUCTURE SHOWS | | | 34+ FEET. | | | 5. MUST HAVE U/C REFRIDGERATOR FOR THE | | | 2ND & 3RD STORY. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|