Plan Review Details - Permit 05061662
Plan Review Stops For Permit 05061662
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-25 Cont ID  
Sent By alange Date 2006-01-25 Time 08:02 Rev Time 1.00
Received By alange Date 2006-01-25 Time 08:02 Sent To  
Notes
2006-01-25 00:00:00DENIED
  
 4.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR THE
 FOLLOWING:EXTERIOR DOORS AND WINDOWS,
 IMPACT PROTECTION, ROOFING STRAPS AND
 TIE DOWNS AND SUNROOM COMPONENTS AND
 SKYLIGHTS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE APPROVALS
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By alange Date 2005-07-28 Time 10:42 Rev Time 1.50
Received By alange Date 2005-07-28 Time 10:20 Sent To  
Notes
2005-07-28 00:00:00DENIED
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. FBC104.2.1 REQUIREMENTS. AS REQUIRED
 BY FBC104.3.1.1 OF THE CODE, TWO OR
 MORE COPIES OF SPECIFICATIONS, AND OF
 DRAWINGS DRAWN TO SCALE WITH
 SUFFICIENT CLARITY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK, SHALL ACCOMPANY THE APPLICATION
 FOR A PERMIT.SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR
 SHALL THE TERM "LEGAL" OR ITS EQUIVALENT
 BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 *ONE SET OF PLANS TOO SMALL, SUNROOM
 DOCUMENTS NOT READABLE AND SIGNED AND
 SEALED. WHITE OUT USED ON PLANS*
  
 4.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR THE
 FOLLOWING:EXTERIOR DOORS AND WINDOWS,
 IMPACT PROTECTION, ROOFING STRAPS AND
 TIE DOWNS AND SUNROOM COMPONENTS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE APPROVALS
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.INSUFFICIENT INFORMATION SUBMITTED
 FOR SUNROOM.INCLUDE NEW DRAWINGS
 SIGNED AND SEAL SHOWING HOW STRUCTURE
 WILL COMPLY WITH THE 2001 FBC SECTIONS,
 1610.1, 1604.6 AND SECTION 1606.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-22 Cont ID  
Sent By jleahy Date 2006-01-22 Time 12:12 Rev Time 0.45
Received By jleahy Date 2006-01-22 Time 12:12 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-18 Cont ID  
Sent By jleahy Date 2005-07-18 Time 06:44 Rev Time 0.30
Received By jleahy Date 2005-07-18 Time 06:44 Sent To M
Notes
2005-07-19 00:00:00NEED LOAD CALCULATION FOR ADDITION.
  
 SHOW PANEL SCHEDULE FOR NEW CIRCUITS.
  
 PLANS NEED TO INDICATE IF AC IS NEW OR
 EXISTING.IF NEW NEED TO SHOW SIZE OF
 WIRE AND BREAKER.
  
 SAME FOR THE DRYER, WASHER, AND
 REFRIGERATOR.
  
 QUESTIONS CALLJAKE LEAHY644-7291

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 09:26 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 09:26 Sent To E
Notes
2006-01-19 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-30 Cont ID  
Sent By mmclean Date 2006-01-18 Time 16:52 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 10:44 Sent To Z
Notes
2005-12-30 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 14:45 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 14:45 Sent To E
Notes
2005-07-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-28 Cont ID  
Sent By alange Date 2005-07-28 Time 10:43 Rev Time 0.00
Received By alange Date 2005-06-28 Time 08:37 Sent To  
Notes
2005-06-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-24 Cont ID  
Sent By tgordon Date 2006-01-24 Time 11:31 Rev Time 0.25
Received By tgordon Date 2006-01-24 Time 11:31 Sent To B
Notes
2006-01-24 00:00:00*** PROVISO ***
 1) MECHANICAL PERMIT IS FOR INSTALLING A
 NEW DUCTLESS A/C SYSTEM A.H.U. M#
 AUU18RC COND. UNIT M# AOU18RC, AND DRYRE
 VENT.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-19 Cont ID  
Sent By rregueir Date 2005-07-19 Time 17:48 Rev Time 0.00
Received By rregueir Date 2005-07-19 Time 17:48 Sent To P
Notes
2005-07-19 00:00:00-----------------DENIED-----------------
 1)NO INFORMATION PROVIDED RELATING TO
 A/C WORK.IS AHU #1 SHOWN ON PLAN NEW
 OR EXISTING?
  
 2)ONLY ONE COPY OF PLANS SUBMITTED.
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-24 Cont ID  
Sent By jleech Date 2006-01-24 Time 10:18 Rev Time 0.25
Received By jleech Date 2006-01-24 Time 10:18 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By jleech Date 2005-07-20 Time 14:58 Rev Time 0.25
Received By jleech Date 2005-07-20 Time 14:58 Sent To B
Notes
2005-07-20 00:00:00DENIED
 TWO SETS OF PLANS REQUIRED FOR PLAN
 REVIEW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-18 Cont ID  
Sent By mmclean Date 2006-01-18 Time 13:05 Rev Time 0.00
Received By mmclean Date 2006-01-18 Time 13:05 Sent To I
Notes
2006-01-18 00:00:00DENIED,
 1. NEED TO SHOW THE ADDITION ON TWO COPY
 OF CURRENT SURVEY WITH SETBACKS.
 2. SITEPLAN PROVIDED DOES NOT MATCH THE
 SURVEY WITH SETBACKS AND PROVIDE A
 COMPLETE INFORMATION FOR REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
 1/18/06 SURVEY PROIDED WITH PROPOSED
 ADDITION WITH SETBACKS.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE, GATE, WALL WITH EASEMENT APPROVAL
 FROM CITY OF WEST PALM BEACH UTILITY
 DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mmclean Date 2005-07-11 Time 12:03 Rev Time 0.00
Received By mmclean Date 2005-07-11 Time 12:03 Sent To I
Notes
2005-07-11 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF PLANS
 (COMPLETE).
 2. FLOOR PLANS MUST SHOW ACCESS FROM THE
 MAIN STRUCTURE TO NEW ADDITION.
 3. MUST REMOVE/CHANGE REFRIDGERATOR TO A
 U/C REGRIDGERATOR.
 4. MUST PULL SEPERATE PERMIT FOR
 FENCE/GATE/WALL WITH UTILITY EASMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.
 5. MUST HAVE HISTORIC APPROVAL BEFORE
 ZONING COMPLETES THEIR REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720