Plan Review Details - Permit 05061621
Plan Review Stops For Permit 05061621
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2006-12-07 Cont ID  
Sent By shill Date 2006-12-07 Time 12:45 Rev Time 0.00
Received By shill Date 2006-12-07 Time 12:45 Sent To  
Notes
2006-12-07 13:12:10REVISED PLANS BY NEW ARCHITECT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2006-10-23 Cont ID  
Sent By shill Date 2006-10-23 Time 15:09 Rev Time 0.00
Received By shill Date 2006-10-23 Time 15:09 Sent To  
Notes
2006-10-23 15:10:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2001
  
 1.)SIGN THE OWNER/AGENT LINE OF THE ENERGY CALCS.
  
 2.)CLARIFY SQUARE FOOT AREA ON THE ENERGY CALC.THIS
 DOES NOT MATCH ANY OF THE NUMBERS ON THE PLAN, AND NO
 MECHANICAL PLANS SUBMITTED.
  
 3.)THE STEP RAILING DETAIL EXTENSIONS AT THE TOP AND
 BOTTOM DO NOT COMPLY WITH FBC11-4.9.4(2).

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2006-09-29 Cont ID  
Sent By shill Date 2006-09-29 Time 11:11 Rev Time 0.00
Received By shill Date 2006-09-29 Time 11:11 Sent To  
Notes
2006-09-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE GOVERNING CODE AT THE TIME OF
 PERMIT APPLICATION WAS FBC2001, BUT THE
 PLANS STATE THAT IT WAS DESIGNED
 FBC2004.ASCE7-98 IS REFERENCED, WHICH
 IS THE CORRECT ENGINEERING STANDARD FOR
 THE 2001 CODE BUT NOT 2004 CODE.DESIGN
 INTENT IS NOT CLEAR.
  
 EITHER REVISE THE PLAN TO REFLECT
 FBC2001, OR SUBMIT A NEW PERMIT
 APPLICATION AND SUBMIT PLANS IN
 COMPLIANCE WITH FBC2004.
  
 2.)PROVIDE A CODE SUMMARY; GOVERNING
 CODE, BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, OCCUPANCY
 CLASSIFICATION FBC3, SPRINKLED OR
 UNSPRINKLED.
  
 3.)PROVIDE A SITE PLAN AND SHOW THE
 ACCESSIBLE ROUTE FBC11-4.1.2(1).
  
 4.)SEE FBC11-4.13.6 AND FBC11 FIGURE
 25 REGARDING MANEUVERING CLEARANCE, PULL
 SIDE, FOR DOOR 30, MASSAGE ROOM 3.
 PLANS SHOW AN OBSTRUCTION (COVERING OF
 PIPES); WHERE ARE THE PIPES ON THE WALL?
  
  
 5.)THE STAIR IS TO HAVE ACCESSIBLE
 HANDRAILS, FBC 11-4.9.4, PROVIDE A
 DETAIL.
  
 6.)PLEASE ADJUST VALUE, ADDITIONAL
 WORK SHOWN.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-03-28 Cont ID  
Sent By shill Date 2006-03-28 Time 14:51 Rev Time 0.00
Received By shill Date 2006-03-28 Time 14:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-03-27 Cont ID  
Sent By shill Date 2006-03-27 Time 11:59 Rev Time 0.00
Received By shill Date 2006-03-27 Time 11:57 Sent To  
Notes
2006-03-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) THE ACCESSIBLE BATHROOM DOES NOT
 APPEAR TO HAVE THE TURNING SPACE
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-04-12 Cont ID  
Sent By shill Date 2006-02-21 Time 16:39 Rev Time 0.00
Received By lmartine Date 2006-02-21 Time 16:39 Sent To  
Notes
2006-02-21 00:00:00SHUTTER PLAN OK'D BY NMK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-02-16 Cont ID  
Sent By shill Date 2006-02-16 Time 09:07 Rev Time 0.00
Received By shill Date 2006-02-16 Time 09:07 Sent To  
Notes
2006-02-16 00:00:00HURRICANE PROTECTION INSTALLATION PLAN
 SUBMITTAL
  
 1.)PAGE 2, THE SHUTTERS ARE TO BE
 INSTALLED WITHIN 12 HOURS OF AN OFFICIAL
 HURRICANE WATCH NOTIFICATION (PLAN AS
 SUBMITTED STATES "WARNING").
  
  
  
 SAMANTHA M. HILL
 561-805-6724
 BUILDING PLANS EXAMINER
 CORRECTION MADE AND SHEET 2 SUBMITTED
 VIA EMAIL.OK'D BY RB AND ROUTED TO NMK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-22 Cont ID  
Sent By shill Date 2005-12-22 Time 19:38 Rev Time 2.00
Received By shill Date 2005-12-22 Time 19:31 Sent To  
Notes
2005-12-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FROM PREVIOUS TWO REVIEWS, NUMBERING
 REMAINS THE SAME FOR CONSISTENCY:
  
 1.)PROVIDE PRODUCT APPROVALS FOR:
  
 DOORS TO BE REUSED (N/A)
 EXTERIOR DOOR
 STOREFRONT SYSTEM
 GLASS BLOCK (N/A)
 IMPACT PROTECTION
 ROOF TILE (N/A)
 ROOF MODIFIED (N/A)
 SOLARTUBE SKYLIGHTS (N/A)
 7' SKYLIGHTS (N/A)
  
 (THIRD REVIEW) - MIAMIDADE NOAS FOR THE
 EXTERIOR DOOR WERE SUBMITTED AND APPEAR
 COMPLIANT, BUT FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL IS ALSO REQUIRED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 IT APPEARS THAT THE DOORS TO BE REUSED
 WILL NOW BE "STORED FOR FUTURE USE" AND
 ARE NOT BEING REINSTALLED IN THIS
 PROJECT.IT APPEARS THAT THE GLASS
 BLOCK (EXTERIOR) AND THE SKYLIGHTS HAVE
 ALSO BEEN REMOVED FROM THE SCOPE OF
 WORK.IS THIS CORRECT?
  
 ONE ILLEGIBLE NOA FOR A NONIMPACT
 STOREFRONT SYSTEM WAS SUBMITTED.TWO
 LEGIBLE COPIES REQUIRED.
  
 IMPACT PROTECTION REQUIRED, FBC1606.1.4.
 REMOVABLE SHUTTERS MUST BE APPROVED BY
 THE BUILDING OFFICIAL.SEE ITEM #2
 BELOW.THIS MUST BE ADDRESSED PRIOR TO
 PERMIT ISSUANCE.
  
 2.)IS THERE A PLAN FOR INSTALLATION OF
 HURRICANE PROTECTIVE DEVICES FOR THIS
 BUILDING?IF YOU PROPOSE TO USE NON
 IMPACT GLASS ON A COMMERCIAL BUILDING,
 SUBMIT AN INSTALLATION PLAN FOR APPROVAL
 BY THE BUILDING OFFICIAL.SEE ATTACHED
 POLICY, ITEM #13.
  
 NOT ADDRESSED.
  
 9.)IMPACT FEES REQUIRED.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION.233-5025
  
 NOT ADDRESSED.NO CHANGES ARE SHOWN ON
 THE PLAN AND THE OLD SHEETS WERE NOT
 SUBMITTED.I BELIEVE THAT THE OLD
 SHEETS SHOWED A SMALL ADDITION, THIS
 PLAN APPARENTLY DOES NOT SHOW THE
 ADDITION.IS THIS CORRECT?WHEN
 RESUBMITTING, SHOW ALL CHANGES AND
 PROVIDE OLD SHEETS FOR REFERENCE.
  
 10.)ENERGY CALCS REQUIRED FBC13.
  
 NOT ADDRESSED.THIS WAS AN ADDITION; IS
 THIS NOW ONLY AN ALTERATION?
  
 NEW COMMENT -
  
 11.)SHOW MANEUVERING CLEARANCE, PULL
 SIDE, FOR DOORS 6 AND 12, FBC11 FIGURE
 25.
  
 12.)THE NOC IS EXPIRED, MORE THAN 90
 DAYS WITHOUT COMMENCING WORK,
 FS713.13(2).
  
 ****WHEN RESUBMITTING, CLEARLY SHOW ALL
 CHANGES TO THE PLAN WITH CLOUDS AND
 SUBMIT THE OLD SHEETS FOR REFERENCE.A
 RESPONSE LETTER WOULD EXPEDITE PLAN
 REVIEW. ***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-29 Cont ID  
Sent By shill Date 2005-08-29 Time 13:08 Rev Time 1.00
Received By shill Date 2005-08-29 Time 13:08 Sent To  
Notes
2005-08-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FROM PREVIOUS REVIEW, NUMBERING REMAINS
 THE SAME FOR CONSISTENCY:
  
 1.)PROVIDE PRODUCT APPROVALS FOR:
  
 DOORS TO BE REUSED
 STOREFRONT SYSTEM
 GLASS BLOCK
 IMPACT PROTECTION
 ROOF TILE
 ROOF MODIFIED
 SOLARTUBE SKYLIGHTS
 7' SKYLIGHTS
  
 2.)IS THERE A PLAN FOR INSTALLATION OF
 HURRICANE PROTECTIVE DEVICES FOR THIS
 BUILDING?IF YOU PROPOSE TO USE NON
 IMPACT GLASS ON A COMMERCIAL BUILDING,
 SUBMIT AN INSTALLATION PLAN FOR APPROVAL
 BY THE BUILDING OFFICIAL.SEE ATTACHED
 POLICY, ITEM #13.
  
 9.)IMPACT FEES REQUIRED.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION.233-5025
  
 10.)ENERGY CALCS REQUIRED FBC13.
  
 NEW COMMENTS:
  
 11.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING - OCCUPANCY LOAD,
 OCCUPANCY TYPE, BUILDING TYPE (INCLUDE
 PROTECTED OR UNPROTECTED), SPRINKLED OR
 UNSPRINKLED SO THAT TABLE 500 COMPLIANCE
 CAN BE DETERMINED.
  
 12.)THE DOORS AT VESTIBULE 1 AND
 VESTIBULE 2 BLOCK OVER HALF THE REQUIRED
 EGRESS, FBC1012.1.4.
  
 13.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENT #10 IS NOT ADDRESSED A THIRD
 TIME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-07 Cont ID  
Sent By shill Date 2005-07-07 Time 11:40 Rev Time 2.00
Received By shill Date 2005-07-07 Time 11:40 Sent To PC
Notes
2005-07-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 1.)PROVIDE PRODUCT APPROVALS FOR:
  
 DOORS TO BE REUSED
 STOREFRONT SYSTEM
 GLASS BLOCK
 IMPACT PROTECTION
 ROOF TILE
 ROOF MODIFIED
 SOLARTUBE SKYLIGHTS
 7' SKYLIGHTS
  
 2.)IS THERE A PLAN FOR INSTALLATION OF
 HURRICANE PROTECTIVE DEVICES FOR THIS
 BUILDING?IF YOU PROPOSE TO USE NON
 IMPACT GLASS ON A COMMERCIAL BUILDING,
 SUBMIT AN INSTALLATION PLAN FOR APPROVAL
 BY THE BUILDING OFFICIAL.SEE ATTACHED
 POLICY, ITEM #13.
  
 3.)SHOW HALLWAY WIDTH.
  
 4.)THE PLAYROOM BATHROOM, NEW MEN'S
 TOILET AND NEW WOMEN'S TOILET ARE TO BE
 ACCESSIBLE, FBC11-4.1.6(1)(6).PROVIDE
 DETAILS FOR THE SINK, TOILET, TURNING
 SPACE, GRAB BARS.
  
 5.)THE HALL#3 SINK IS TO BE COMPLIANT
 WITH
  
 5.)SHOW COMPLIANCE WITH FBC11-4.13.7,
 FIG. 26 FOR VESTIBULE #1 AND #2 DOORS.
  
 6.)SHOW MANEUVERIENG CLEARANCE FOR
 DOORS, FBC11-4.13.6, FIG 25 FOR THE
 FOLLOWING DOORS (PLEASE NOTE THAT OTHER
 DOORS ENCROACH THE CLEAR FLOOR SPACE):
  
 DOORS AT VEST #1 AND VEST #2
 DOOR AT HALLWAY #1 AND #2
  
 7.)THE WINDOW BUCK IS TO PROVIDE FULL
 SUPPPORT (THE DETAIL ON A5 SHOWS THE
 WINDOW BEARING ON DRYWALL) UNLESS IT WAS
 TESTED THIS WAY, FBC1707.4.4.2.AS
 PRODUCT APPROVALS WERE NOT SUBMITTED FOR
 THE STOREFRONT I CANNOT DETERMINE
 WHETHER OR NOT THIS DETAIL IS CODE
 COMPLIANT.
  
 8.) PROVIDE AREA CALCULATIONS ON THE
 PLAN (EXISTING, PROPOSED NEW, NEW
 TOTAL).
  
 9.)IMPACT FEES REQUIRED.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION.233-5025
  
 10.)ENERGY CALCS REQUIRED FBC13.
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-05-18 Cont ID  
Sent By dpalmer Date 2007-05-18 Time 16:35 Rev Time 0.00
Received By dpalmer Date 2007-05-18 Time 16:35 Sent To PC
Notes
2007-05-18 16:35:48ELEC REV OK, NEW SHEET.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-05-11 Cont ID  
Sent By dpalmer Date 2007-05-11 Time 15:58 Rev Time 0.00
Received By dpalmer Date 2007-05-11 Time 15:47 Sent To PC
Notes
2007-05-11 15:59:08** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE INDICATE CIRCUITING ON PLANS FOR NEW
 ELECTRICAL AND COORDINATE WITH THE PANEL SCHEDULES ON
 RECORD SET OF PLANS.
 PLEASE INCLUDE ANY NEW LOADS TO EQUIPMENT. PLEASE
 CLARIFY IF THIS AREA IS NEW TO THE EXISTING BUILDING OR
 NEW BUILD OUT AREA?
 240.4, 310.16, 408.4.
 FBC 106.3.5.1.2, 106.1.2
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-10-22 Cont ID  
Sent By dpalmer Date 2006-10-22 Time 14:47 Rev Time 0.00
Received By dpalmer Date 2006-10-22 Time 14:32 Sent To  
Notes
2006-10-22 14:47:51REVISED SHEETS FOR NEW DESIGNER OF RECORD OK.
 STAMPED NEW E-1, 2 AND 3.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 11:10 Sent To  
Notes
2006-09-10 00:00:00** UNSAT **
  
 1) NOTE: PLEASE CORRLEATE ADDRESSING FOR
 PROJECT WITH NEW PLANS.
 PLEASE SEE THIS SCOPE OF WORK WAS
 PERMITTED UNDER THE ADDRESS OF 8100
 IBIS, AND REV COVER SHEET MENTIONS 8225
 AND THE PLANS INDICATE 8550. PLEASE
 CORRELATE AND REVISE.
  
 2) NOTE: PLEASE SEE A NOTE IS BEING
 PLACE ON PLANS FOR COMPLIANCE WITH 2004
 FBC 2004 13-415.1ABC.1.1. PLEASE SEE IF
 BRINGING THIS SPACE UP TO CODE FOR THIS,
 PLEASE PROVIDE DETAILS FOR SYSTEM BEING
 PROPOSED. NEED TO SHOW SYSTEM,
 SCHEDULING, OVER RIDES AND OVER RIDES
 LOCATION. PLEASE SEE LOCATION SHALL BE
 LOCATEDFOR INGRESS/EGRESS AREA AND
 BEING ABLE TO SEE THE LIGHTING WHICH IS
 BEING CONTROLLED. PLEASE SEE CONTROLS
 AND OVER RIDES FOR SEPARATE SPACES COULD
 NOT BE LOCATED. PLEASE SEEMAX TIMES FO
 OVER RIDING DEVICES MUST ALOS BE STATED.
 (TIMER TYPE 4HRS MAX, OCCUPANT SENSOR
 TYPE 30MINS MAX).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3
 ** PLEASE SEE PREVIOUS NOTES WHICH
 REQUESTED SUBMITTIAL OFNEW ENGERGY
 CALCULATIONS BEIGN SIGNED, DATED AND
 SEALED BY NEW ARCHITECT OF RECORD.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-08-17 Cont ID  
Sent By dpalmer Date 2006-08-17 Time 07:14 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 07:04 Sent To PC
Notes
2006-08-17 00:00:00**** UNSAT ***
  
 1) NOTE: IF RELEASING THE ARCHITECT OF
 RECORD: MUST SUBMIT TWO COMPLETE SETS
 FOR PROJECT DONE BY THE NEW ARCHITECT OF
 RECORD. WHICH INCLUDES ALL PLANS, ENERGY
 CALCULATIONS ETC WHICH WERE SUBMITTED
 AND DONE BY THE PREVIOUS ARCHITECT.
 MUST SUBMIT A LETTER FROM THE OWNER
 WHICH IS RELAESING THE ARCHITECT OF
 RECORD.
 THIS LETTER MUST BE PROPERLY NOTARIZED
 UNDER FS 117.05.
  
 OPTION #2
  
 2) NOTE: PLEASE SEE THAT A NOTE IS BEING
 PLACE ON PLANS WHICH MENTIONS THE
 EXISTING ARCHITECT IS PERMITTING THE NEW
 DESIGNER TO COMPLETE PROJECT WHICH IS
 FINE, HOWEVER MUST ALSO HAVE A LETTER
 FROM THE EXISTING ARCHITECT THEN
 RELEASING HIMSELF AND PERMITTING THE NEW
 ARCHITECT TO TAKE OVE. THE LETTER MUST
 BE SIGNED, DATED AND SEALED BY THE
 EXISTING ARCHITECT AND PROPERLY
 NOTARIZED UNDER FS 117.05
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-16 Cont ID  
Sent By dpalmer Date 2006-03-16 Time 19:00 Rev Time 0.00
Received By dpalmer Date 2006-03-16 Time 18:44 Sent To  
Notes
2006-03-16 00:00:00PLANS OK.
  
 NEEDS NEW RE-RECORDED NOC AS NOC HAS
 EXPIRED. PLEASE SEE FS 713.13(2) WHICH
 STATES " IF WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING NOC, THE NOC
 SHALL BECOME VOID AND WILL BE REQUIRED
 TO BE RE-RECORDED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-06 Cont ID  
Sent By dpalmer Date 2005-12-06 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2005-12-06 Time 12:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-08-10 Time 19:34 Rev Time 1.00
Received By dpalmer Date 2005-08-10 Time 19:16 Sent To  
Notes
2005-08-10 00:00:00************ UNSAT2ND REVIEW ********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW COMMENTS FOR
 NEW ELECTRICAL INFORMATION SUBMITTED.
  
  
 1)NOTE: NOTE #1 OK.
 PLANS, SIGNED, DATED AND SEALED BY
 ARCHITECT.
  
 2)NOTE: NOTE #2 NO,
 PLEASE SEE RISER NOWS SHOWS ONE NEW
 ELECTRICAL SUB PANEL WITH PANEL
 SCHEDULE, HOWEVER NEW ELECTRICAL SUB
 PANEL DOES NOT INCLUDE OTHER CIRCUITS AS
 SHOWN ON PLANS.
 PLEASE SEE NO PANEL SCHEDULE FOR REVISED
 PANEL "A" WAS SUBMITTED.
 215.5
  
 3)NOTE: NOTE #3 NO, PLEASE SEE NEC
 220.3,220.10,220.11,220.13 ETC FOR LOAD
 CALCUALTIONS. PLEASE SEE GEN LT LOAD MAY
 NOT BE 1VA PER FT IN THIS OCCUPANCY.
 PLEASE ALSO SEE RECEPTS ETC ARE MISSING
 FROM LOAD CALCS.
 PLEASE BE SURE ALL CONTINUOUS LAODS ARE
 SHOWN AT 125% 215.3,230.42 ETC
  
 4)NOTE: NOTE #4 NO, PLEASE SEE THESE
 UNITS/ CIRCUITS FOR GEN UNITS AND
 LOCATIONS ARE STILL NOT SHOWN ON PLANS?
 PLEASE SHOW.
  
 5)NOTE: NOTE #5 NO, NO GFI PROTECTION IS
 INDICATED ON PLANS, PANEL SCHEDULE ETC.
 680.44.680.71
  
 NEW NOTES.
  
 6)NOTE: PLEASE CORRELATE CIRCUITING FOR
 HEATER ON NEW SUB PANEL WITH CONDCUTORS
 SHOWN ON RISER.
 215.5
  
 7)NOTE: PLEASE SEE LOAD CALCULATIONS
 INDICATE PANEL "A" AS 225A EXISITING AND
 RISER SHOWS THIS PANEL "A" AS 200A
 EXISTING?
 PLEASE CORRELATE.
 215.5
  
 8)NOTE: PLEASE SEE OTHER LOADS BESIDES
 NEW SPA LOADS ARE NOT SHOWN IN LOAD
 CALCUALTIONS?
 220,215.5
  
 9)NOTE: PLEASE SEE 680.43A FOR MIN GFI
 RECEPT REQUIRED.
  
 10)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL AND REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 PLEASE SEE ONE COPY OF ELECTRICAL PLANS
 ARE BEING RETAINED FOR FILE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHALL
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 20:45 Rev Time 0.33
Received By dpalmer Date 2005-07-01 Time 20:34 Sent To  
Notes
2005-07-01 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE ALL THREE SETS OF
 PLANS SUBMITTED CONTAIN A "STAMP" FOR
 THE SIGNATURE OF ARCHITECT. PLEASE SEE
 FS 481.221 WHICH REQUIRES THE ARCHITECT
 TO SIGN, DATE AND SEAL ALL PLANS. PLEASE
 SEE THIS SIGNATURE MUST BE AN ORIGINAL
 "WET" SIGNATURE. STAMPS ARE NOT
 ACCEPTABLE.
 PLEASE SEE ONE SET OF PLANS AHVE BEEN
 RETAINED FOR FILE. PLANS MAY BE TURNED
 OVER TO DBPR/ FLORIDA BOARD OF
 ARCHITECTS FOR POSSIBLE REVIEW.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE INCLUDE CIRCUITING ON
 PLANS FOR ALL NEW AND CORRELATE WITH A
 COMPLETE PANEL SCHEDULE TO BE SUBMITTED.
 215.5
  
 3)NOTE: PLEASE INCLUDE LOAD CALCAULTIOSN
 FOR NEW LOADS TO EXISTING LOADS. PLEASE
 INCLUDE SIZE, RATING ETC FOR PANEL. NO
 INFORMATION WAS SHOWN ON PLANS AND GIVEN
 AT THIS TIME.
  
 4)NOTE: PLEASE SEE NEW ELECTRICAL SPA,
 STEAM GEN ETC ARE INDICATED ON PANEL
 SCHEDULE, HOWEVER NONE OF THESE COULD BE
 LOCATED ON PLANS.??
 215.5
  
 5)NOTE: PLEASE INDICATE GFI PROTECTION
 FOR SPA CIRCUIT ETC PER 680.44,680.71
 ETC.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-10-02 Cont ID  
Sent By mawillia Date 2006-10-02 Time 15:28 Rev Time 0.00
Received By mawillia Date 2006-10-02 Time 15:28 Sent To  
Notes
2006-10-02 00:00:00*****APPROVED*****W/REMINDERS
  
  
  
  
  
 1.) VERIFY AND/OR RECTIFY THAT THE
 NUMERICAL ADDRESS ON THE PERMIT IS
 CONSISTENT WITH THAT LISTED ON THE SHOP
 DRAWINGS/PLANS.
  
 2.) AS PER CITY OF WEST PALM BEACH CODE,
 NUMERICAL ADDRESS OF NO LESS THAN 6" IN
 HEIGHT AND 1" IN WIDTH SHALL BE POSTED
 ON THE BUILDING.
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-03-31 Cont ID  
Sent By mwennerg Date 2006-03-31 Time 10:57 Rev Time 0.00
Received By mwennerg Date 2006-03-31 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-02 Cont ID  
Sent By mwennerg Date 2005-09-02 Time 10:31 Rev Time 0.00
Received By mwennerg Date 2005-09-02 Time 10:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-05 Cont ID  
Sent By mwennerg Date 2005-07-05 Time 09:44 Rev Time 0.00
Received By mwennerg Date 2005-07-05 Time 09:44 Sent To  
Notes
2005-07-05 00:00:00******DENIED******
  
 1) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) PLEASE ILLUSTRATE NEW AND OR EXISTING
 LOCATIONS OF FIRE EXTINGUISHERS.
  
 3) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS REQUIREMENT FOR SIGNING,
 DATING AND SEALING ALL DRAWINGS.
  
 4) DRAWINGS SHOW TWO DOORS WITH
 EMERGENCY HARDWARE AND ALARM. PLEASE
 EXPLAIN.
  
 5) PLEASE PROVIDE DETAILS AND CUT SHEETS
 TO ILLUSTRATE ANY FLAME RETARDANT
 INFORMATION OF THE NEW CANVAS AWNINGS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 09:29 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 09:29 Sent To E
Notes
2007-05-17 09:29:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-05-11 Cont ID  
Sent By adarroug Date 2007-05-11 Time 11:06 Rev Time 0.00
Received By adarroug Date 2007-05-11 Time 11:06 Sent To E
Notes
2007-05-11 11:07:07TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 14:46 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 14:46 Sent To M
Notes
2007-01-31 14:47:05TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 14:14 Sent To B
Notes
2006-11-13 14:14:50TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 11:24 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 11:11 Sent To  
Notes
2006-10-20 11:17:52TO "COMM" BD#61
2006-10-10 11:11:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 13:07 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 13:07 Sent To  
Notes
2006-08-31 00:00:00TO "COMM" BD#1
2006-08-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 13:56 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 13:56 Sent To E
Notes
2006-08-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:57 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:57 Sent To  
Notes
2006-03-16 00:00:00TO "COMM" BD#20
2006-02-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:51 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:51 Sent To B
Notes
2006-02-15 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-18 Time 15:05 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 15:04 Sent To  
Notes
2005-12-02 00:00:00TO "COMM" BD#9
2005-11-18 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-08-05 Time 15:51 Rev Time 0.00
Received By adarroug Date 2005-08-05 Time 15:51 Sent To  
Notes
2005-08-05 00:00:00TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-07 Cont ID  
Sent By dpalmer Date 2005-07-07 Time 17:08 Rev Time 0.00
Received By shill Date 2005-06-28 Time 09:16 Sent To  
Notes
2005-06-30 00:00:00TO BLD-OUT BOARD #7
2005-06-28 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-02-01 Cont ID  
Sent By tgordon Date 2007-02-01 Time 15:10 Rev Time 0.40
Received By tgordon Date 2007-02-01 Time 15:10 Sent To  
Notes
2007-02-01 15:13:46MECH. REVISION TO PAGE M-1 TO INCLUDE EXHAUST FANS AND
 VENTS FOR LOCKER ROOM PLUS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-09-27 Cont ID  
Sent By tgordon Date 2006-09-27 Time 14:18 Rev Time 0.15
Received By tgordon Date 2006-09-27 Time 14:18 Sent To  
Notes
2006-09-27 00:00:00RELOCATE CONDENSER UNITS (RE-STAMP)

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-22 Cont ID  
Sent By tgordon Date 2006-05-22 Time 13:55 Rev Time 0.15
Received By tgordon Date 2006-05-22 Time 13:55 Sent To  
Notes
2006-05-22 00:00:00PERMIT FOR RELOCATING CONDENSER UNIT
 ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-08-24 Cont ID  
Sent By pkrauss Date 2005-08-24 Time 11:47 Rev Time 0.30
Received By pkrauss Date 2005-08-24 Time 11:37 Sent To  
Notes
2005-08-24 00:00:00NO MECHANICAL CONTRACTOR OR PLANS
 INDICATED WITH PERMIT APPLICATION.
 PROVIDE PLANS WITH MECHANICAL PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-06 Cont ID  
Sent By pkrauss Date 2005-07-06 Time 10:39 Rev Time 0.30
Received By pkrauss Date 2005-07-06 Time 10:39 Sent To B
Notes
2005-07-06 00:00:00DENIED:
 MECHANICAL CONTRACTOR INDICATED ON THE
 PERMIT APPLICATION.PLEASE PROVIDE
 MECHANICAL PLANS.INDICATE DUCT SIZE,
 MATERIAL, AND LAYOUT.PROVIDE EQUIPMENT
 INFORMATION, NEW OR EXISTING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-11-08 Cont ID  
Sent By kstevens Date 2006-11-08 Time 16:43 Rev Time 0.00
Received By kstevens Date 2006-11-08 Time 16:43 Sent To  
Notes
2006-11-08 16:44:14REVISION OK - SHEET P-1 NEW TOILET ROOMS, SINKS, MOVED
 DRINKING FOUNTAINS ETC.

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-09-13 Cont ID  
Sent By kstevens Date 2006-09-13 Time 07:59 Rev Time 0.00
Received By kstevens Date 2006-09-13 Time 07:59 Sent To  
Notes
2006-09-13 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. THE ADDRESS SHOWN ON THE PLANS AND
 THE ADDRESS ON THE PERMIT ARE NOT THE
 SAME. THE ADDRESS ON THE PLANS SHALL BE
 CORRELATED WITH THE ADDRESS ON THE
 PERMIT AND THE PERMIT APPLICATION.
 SECTION 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-04-13 Cont ID  
Sent By pschmitz Date 2006-04-13 Time 13:52 Rev Time 0.00
Received By pschmitz Date 2006-04-13 Time 13:52 Sent To Z
Notes
2006-04-13 00:00:00PROVISO:
 SHTS A-2, A-3 ,P-1 PER BRAD NEIDER P/M

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-01-31 Cont ID  
Sent By kstevens Date 2006-01-31 Time 07:45 Rev Time 0.00
Received By kstevens Date 2006-01-31 Time 07:44 Sent To  
Notes
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A. FROM FIRST REVIEW: COMMENT NOT
 ADDRESSED.
  
 4. SHT A-1 NEW MENS AND WOMENS TOILET
 ROOMS, AND THE PLAYROOM TOILET ROOM
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND "ALL
 SUBSECTIONS". SECTIONS 11-4.1.6(1)(B)
 AND 11-4.1.1(6).
  
 ***************NEW COMMENTS*************
 NEW SHEETS:
 1B. SHTS A-3 & P-1 SANT. RISER DIAGRAMS
 DO NOT REFLECT THE FLOOR PLAN. RISER FOR
 MASSAGE ROOM #3 DOES NOT SHOW THE FLOOR
 DRAIN. LAV SHALL CONNECT TO THE DRAIN
 LINE DOWNSTREAM OF THE FLOOR DRAIN NOT
 TO THE FLOOR DRAIN. - RISER DIAGRAM FOR
 MASSAGE ROOMS #'S 1 & 2 SHOW 3 TRAPS,
 BUT ONLY 2 SINKS SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE RISERS AND FLOOR
 PLAN. SECTION 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-06 Cont ID  
Sent By pschmitz Date 2005-08-06 Time 07:26 Rev Time 0.00
Received By pschmitz Date 2005-08-06 Time 07:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-05 Cont ID  
Sent By kstevens Date 2005-07-05 Time 13:48 Rev Time 0.98
Received By kstevens Date 2005-08-06 Time 07:23 Sent To  
Notes
2005-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE SIGNED BY THE
 ARCHITECT OF RECORD. STAMPED SIGNATRUES
 ARE NOT APPROVED. FAC 61G116.003 AND FS
 481.2055.
 2. SHT D1 INDICATES THE STEAM GENERATOR
 WILL BE REMOVED, BUT SHT A-1 INDICATES
 TWO STEAM ROOMS. PLEASE CLARIFY. SECTION
 104.2.1. - IF NEW STEAM GENERATORS ARE
 TO BE INSTALLED, DETAILS FOR THE NEW
 GENERATORS ARE REQUIRED. SHOW THE
 LOCATION OF THE STEAM GENERATORS, AS
 WELL AS THE INFORMATION ON THE EMERGENCY
 PAN, THE PAN DRAIN LINES, THE P/T VALVE
 DISCHARGE LINES ECT. SHOW ROUTING OF
 LINES AS WELL AS THE STEAM LINES TO THE
 STEAM ROOMS. INDICATE MATERIAL FOR ALL
 LINES AND EMERGENCY PAN. STEAM UNITS
 SHALL BE LISTED. SUBMIT MANUF.
 SPECIFICATION SHEETS.
 3. SHT A-1 SINK IN HALL #3 SHALL BE
 ACCESSIBLE. PLEASE PROVIDE A DETAIL
 SHOWING COMPLIANCE WITH 11-4.24 AND "ALL
 SUBSECTIONS"
 4. SHT A-1 NEW MENS AND WOMENS TOILET
 ROOMS, AND THE PLAYROOM TOILET ROOM
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND "ALL
 SUBSECTIONS". SECTIONS 11-4.1.6(1)(B)
 AND 11-4.1.1(6).
 5. SHT A-3 SANT. RISER DIAGRAM FOR
 FLAYROOM TOILET ROOM, PIPE SIZE
 INDICATES 2" TO PICK UP TOILET. TABLE
 709.1 FOOTNOTE "D" STATES "TRAP SIZE
 SHALL BE CONSISTENT WITH THE FIXTURE
 OUTLET SIZE". PLEASE SUBMIT MANUF.
 SPECIFICATION FOR TOILET THAT INDICATES
 A 2" OUTLET FOR THE TOILET.
 6. SHT A-3 SANT. RISER DIAGRAM FOR NEW
 SPA AREAS. PLEASE INDICATE WHAT THE LINE
 TO THE RIGHT OF THE DRAIN LINE TO THE
 SPA FLOOR DRAIN LINE DOWNSTREAM OF THE
 FLOOR DRAINS IS DRAINING. SECTION
 104.2.1.
 7. PLEASE SUBMIT A PLUMBING FLOOR PLAN
 SHOWING ALL PIPING AND THE POINT OF
 CONNECTION FOR EACH RISER SHOWN ON SHT
 A-3.
 8. SHT A-3 SANT. RISER DIAGRAMS AND
 WATER RISER DIAGRAMS, SHOW ALL PIPE
 SIZES. SECTION 104.2.1.
 10. SHT A-2 PLUMBING NOTES:
 #1. PIPING SHALL BE PER TABLE 704.1.
 PIPING 2-1/2" OR SMALLER SHALL BE RUN
 WITH A MINIMUM SLOPE OF 1/4" PER FT.
 #8. INDICATE WHERE NEW SHOWER WILL BE
 INSTALLED. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-11-07 Cont ID  
Sent By lfranco Date 2006-11-07 Time 19:15 Rev Time 0.00
Received By lfranco Date 2006-11-07 Time 19:15 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-09-08 Cont ID  
Sent By lfranco Date 2006-09-08 Time 17:49 Rev Time 0.00
Received By lfranco Date 2006-09-08 Time 17:49 Sent To I
Notes
2006-09-08 00:00:00PLANNING AND ZONING: PASSED
  
 INTERIOR RENOVATIONS ONLY. NO ADDITIONAL
 SQUARE FOOTAGE PROPOSED. THE FOOTPRINT
 OF THE EXISTING BUILDING SHALL REMAIN
 THE SAME.OTHERWISE, A MINOR AMENDMENT
 TO THE MASTER PLAN WILL BE REQUIRED
 PRIOR TO SIGN-OFF FROM PLANNING AND
 ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT LINDA MIA FRANCO @
 (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-02 Cont ID  
Sent By lfranco Date 2006-05-02 Time 09:06 Rev Time 0.00
Received By lfranco Date 2006-09-08 Time 17:48 Sent To I
Notes
2006-05-02 00:00:00PLANNING AND ZONING: PASSED
  
 INTERIOR RENOVATIONS ONLY. NO ADDITIONAL
 SQUARE FOOTAGE PROPOSED. THE FOOTPRINT
 OF THE EXISTING BUILDING SHALL REMAIN
 THE SAME.OTHERWISE, A MINOR AMENDMENT
 TO THE MASTER PLAN WILL BE REQUIRED
 PRIOR TO SIGN-OFF FROM PLANNING AND
 ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT LINDA MIA FRANCO @
 (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By mmclean Date 2005-09-01 Time 10:52 Rev Time 0.00
Received By mmclean Date 2005-09-01 Time 10:52 Sent To  
Notes
2005-09-01 00:00:00DENIED,
 1. NEED TO APPLY FOR A MINOR AMENDMENT,
 SPOKE WITH CONTRACTOR, PLANNER GRACE
 JOYCE, 822-1435 MM
2005-08-10 00:00:00NEEDS ZONING, INCREASE OF SQ FT OF BLDG.