Plan Review Details - Permit 05061562
Plan Review Stops For Permit 05061562
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By alange Date 2006-01-23 Time 08:49 Rev Time 3.00
Received By alange Date 2006-01-23 Time 08:20 Sent To  
Notes
2006-01-23 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW CONSTRUCTION TYPE ON PLANS.
  
 4. W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5.ENERGY CALCS SUBMITTED SHALL FOR THE
 2004 FBC.
  
 6.ONCE CONSTRUCTION TYPE HAS BEEN
 SELECTED THE PERMIT VALUATION WILL BE
 ADJUSTED ACCORDING TO ICC BUILDING
 VALUATION DATA.ADDITIONAL PERMIT FEES
 WILL BE DUE.
  
 7.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS. 2004 FBC R-807
  
 8.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.
  
 9.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10.PRODUCT APPROVALS SUBMITTED IS FOR
 A SGD SLIDING GLASS DOOR YET PLANS SHOW
 A FRENCH DOOR.
  
 11.ORIGONAL PERMIT APPLICATION IS
 REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-27 Time 16:48 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 16:48 Sent To M
Notes
2005-12-29 00:00:00PLANS ROUTED TO PLUMB.
2005-12-27 00:00:00********** UNSAT **********
  
  
 1)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 CODE 106.3.4.3 WHICH REQUIRES PLANS TO
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR SAID
 PLANS/ DESIGN FOR SAID PLANS AND DESIGN.
  
 2)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12 WHICH REQUIRES ELECTRICAL OUTLETS
 IN BEDRMS TO BE PROTECTED. PLEASE KNOW
 THIS MEANS SD'S, RECEPTS, FANS, LTS ETC.
  
 3)NOTE: PLEASE SEE REDLINED PLANS FOR
 SOME RECEPTS MISSING PER 210.52.
  
 4)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 COUNTERSPACE GFI(S) REQUIRED. SEE AREA
 OF DISHWASHER. SEE REDLINED PLANS.
  
 PLEASE REVMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 11:01 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 11:01 Sent To E
Notes
2005-12-27 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-23 Cont ID  
Sent By alange Date 2006-01-23 Time 08:54 Rev Time 0.00
Received By alange Date 2005-12-12 Time 17:56 Sent To  
Notes
2005-12-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By tgordon Date 2005-12-28 Time 10:23 Rev Time 0.30
Received By tgordon Date 2005-12-28 Time 10:23 Sent To E
Notes
2005-12-28 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) NEED JOB ADDRESS ON MECHANICAL PLANS.
  
 3) MECHANICAL PLANS NEED TO BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN, PER FBC
 104.2.1 .
  
 4) CHECK CLEARANCE ON CONDENSER UNIT.
 NEED 30" OF CLEARANCE IN FRONT OF
 CONTROL SIDE, PER 2004 FBC/R M1305.1 .
  
 5) NEED TO FILE A NOTICE OF
 COMMENCEMENT, PER F.S. 713.13 .
  
 6) RETURN AIR TRANSFER DUCT TO MASTER
 SUITE IS TO SMALL, SEE NOTE #7.
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By jleech Date 2005-12-29 Time 09:03 Rev Time 0.50
Received By jleech Date 2005-12-29 Time 09:03 Sent To B
Notes
2005-12-29 00:00:00DENIED;
 1.PLANS NEED TO BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONIBLE FOR
 THE DRAWINGS.
 2.SANITARY RISER DIAGRAM DOES NOT MATCH
 FLOOR PLAN.
 3.W/M DRAIN TO BE 3" TO HORIZONTAL
 BRANCH. SEC.406.3.
 4.BACK BATHROOM IS SHOWER NOT TUB.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-22 Cont ID  
Sent By mmclean Date 2005-12-22 Time 16:23 Rev Time 0.00
Received By mmclean Date 2005-12-22 Time 16:23 Sent To I
Notes
***NONE***