 |
Plan Review Details - Permit 05061381
| Plan Review Stops For Permit 05061381 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-02-07 |
Time |
12:52 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-02-07 |
Time |
12:52 |
Sent To |
PC |
|
| Notes |
| 2006-02-07 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05061381 | | | ADD: 31150 45TH ST | | | CONT:FRANCHISE PROPERTIES SERVICES | | | INC | | | TEL: (316)304-8749 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT 3A)FROM THE PREVIOUS REVIEW, | | | PLANS DO NOT INDICATE WHICH ARE NEW | | | OPENINGS & WHICH ARE EXISTING, PROVIDE | | | ADDITIONAL INFORMATION FOR WINDOWS AND | | | DOORS. | | | ARCHITECTURAL ELEVATIONS INDICATE | | | WINDOWS AND MULLION TO REMAIN BUT THE | | | STRUCTURAL PLANS S0.1 WIND LOAD NOTES | | | WINDOWS, DOORS AND MECHANICAL LOUVERS | | | TO WITHSTAND WIND LOADS AND LARGE MISSLE | | | IMPACT TESTING.S1 SHOWS DETAIL 9 ON S3.1 | | | | | | NEWLY FRAMED WALL WITH STEEL COLUMNS. | | | THE NEWLY FRAMED WALLS DO NOT SHOW ANY | | | STRAPPING HOLDING TO THE STEEL COLUMN/ | | | EXPLAIN HOW STRUCTURAL STATEMENT OF | | | WINDOWS, DOORS & LOUVER TO MEET THE WIND | | | LOADS & IMPACT STANDARD WITH THE OLD | | | GLAZING UNITS? | | | 1606.2.4 MAIN WIND FORCE RESISTING | | | SYSTEM (MWFRS). ALL ELEMENTS AND | | | CONNECTIONS OF THE MWFRS SHALL BE | | | DESIGNED FOR VERTICAL AND HORIZONTAL | | | LOADS BASED ON THE COMBINED LEEWARD AND | | | WINDWARD WALL PRESSURES AND ROOF | | | PRESSURES DETERMINED FROM TABLE 1606.2A. | | | PRESSURES SHALL BE APPLIED IN | | | ACCORDANCE WITH THE LOADING DIAGRAMS | | | SHOWN IN FIGURE 1606.2A TO THE END | | | ZONE AND INTERIOR ZONE AS SHOWN IN | | | FIGURE 1606.2B.THE BUILDING SHALL | | | BE DESIGNED FOR ALL WIND DIRECTIONS. | | | FOR BUILDINGS HAVING FLAT ROOFS, A | | | RIDGE LINE NORMAL TO THE WIND DIRECTION | | | SHALL BE ASSUMED AT THE MID-LENGTH | | | DIMENSION OF THE ROOF FOR ALL DIRECTIONS | | | CONSIDERED.EACH CORNER SHALLBE | | | CONSIDERED IN TURN AS THE WINDWARD | | | CORNER. | | | 1606.1.4(1) IN WIND BORNE DEBRIS | | | REGIONS, EXTERIOR GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IN BUILDINGS SHALL BE | | | ASSUMED TO BE OPENINGS UNLESS SUCH | | | GLAZING IS IMPACT RESISTANT OR PROTECTED | | | WITH AN IMPACT RESISTANT COVERING MEET- | | | ING THE REQUIREMENTS OF SSTD 12, ASTM | | | E 1886 AND ASTM E 1996 OR MIAMI-DADE. | | | GLAZED OPENINGS LOCATED WITHIN 30 FT OF | | | GRADE SHALL MEET THE REQUIREMENTS OF | | | LARGE MISSLE TEST. | | | | | | | | | | | | 2) COMMENT3B) FROM THE PREVIOUS REVIEW | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS | | | B) DOORS | | | C)SIDING EFIS | | | D) LOUVERS | | | E) ROOFING ASSEMBLIES | | | | | | 4) PLANS INDICATE REWORK OF ROOF AND NEW | | | PARAPET AND FLASHING, PROVIDE PRODUCT | | | TESTING REPORTS FOR ROOFING ASSEMBLIES. | | | | | | 5) PLANS DO NOT PROVIDE WHAT MINIMUM | | | TYPE BUILDING DESIGN THIS PLAN WAS | | | DESIGNED TO? 601.2.1, 601.2.2. | | | | | | 6) PROVIDE A SITE PLAN WITH DIMENSIONS | | | TO THE PROPERTY LINE, TABLE 600 THERE | | | MAY BE OPENING ISSUES. | | | TODAY I WAS IN A MEETING WITH THE | | | CONTRACTOR WHO IS GOING TO BRING IN A | | | SURVEY SO TABLE 600 ISSUES MAY BE | | | ADDRESSED. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-07-24 |
Time |
11:21 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-07-24 |
Time |
11:21 |
Sent To |
PC |
|
| Notes |
| 2005-07-24 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05061381 | | | ADD: 31150 45TH ST | | | CONT:FRANCHISE PROPERTIES SERVICES | | | INC | | | TEL: (316)304-8749 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 3A)PLANS DO NOT INDICATE WHICH ARE NEW | | | OPENINGS & WHICH ARE EXISTING, PROVIDE | | | ADDITIONAL INFORMATION FOR WINDOWS AND | | | DOORS. | | | | | | 3B) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3C)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | D) WINDOWS | | | E) DOORS | | | F) SIDING EFIS | | | G) ROOFING ASSEMBLIES | | | | | | 4) S)0.1 WIND DESIGN LOADS, INDICATES A | | | 130 MPH WIND ZONE SEE FIGURE 1606, WEST | | | PALM BEACH IS IN A 140 MPH WIND ZONE. | | | S0.2 PRESSURES ARE FOR A 130 NOT 140 | | | WIND ZONE CORRECT. | | | | | | 5) PLANS DO NOT PROVIDE WHAT MINIMUM | | | TYPE BUILDING DESIGN THIS PLAN WAS | | | DESIGNED TO? 601.2.1, 601.2.2. | | | | | | 6) PROVIDE A SITE PLAN WITH DIMENSIONS | | | TO THE PROPERTY LINE, TABLE 600 THERE | | | MAY BE OPENING ISSUES. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-21 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-21 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2005-12-21 00:00:00 | REDLINED PLANS** | | | | | | | | | 250.6, 250.24 FOR EQUIPMENT GROUNDS OR | | | BONDS, | | | | | | 230.70 , NO MORE THAN SIX SPACES | | | PERMITTED IN DP, OR A MCB WILL BE | | | REQUIRED. | | | 230.70 | | | | | | ALL KITCHEN RECEPTS MEETING THE | | | REQUIREMENTS OF 210.8B3 SHALL BE GFI | | | PROTECTED. | | | THIS IS ABOVE THE ALREADY IDENTIFIED | | | "SQUARE" GFI SHOWN. | | | PLEASE SEE SOME ARE MISSING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-06 |
Time |
07:08 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2005-07-05 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2005-07-06 00:00:00 | ********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE ALL SHEETS IN BOTH | | | SET OF PLANS SUBMITTED ARE PHOTOCOPIES | | | OF SIGNED AND SEALED DRAWINGS. PLEASE | | | ALL PLANS MUST BE ORIGINAL SIGNED, DATED | | | AND SEALED WITH RAISED SEAL PER FS | | | 481.221 AND FS 471.025. | | | PLEASE SEE MISSING TITLE BLOCK | | | INFORMATION ON "A"- SHEETS ETC AS | | | REQUIRED UNDER FAC 61G1-16.004 FS | | | 481.219. | | | THE ABOVE IS REQUIRED FOR ALL SHEETS AND | | | FOR ALL TRADES WHEATHER OR NOT COMMENT | | | IS MADE BY OTHER REVIEWER(S). | | | | | | 2)NOTE: PLEASE SEE 250.50 : COLD WATER | | | PIPE TO BE PART OF THE GROUNDING | | | ELECTRODE SYSTEM. | | | | | | 3)NOTE: PLEASE SEE 250.6,250.24 AND | | | EQUIPMENT GROUNDING CONDUCTOR SHALL NOT | | | BE INSTALLED UNTIL AFTER THE FIRST MEANS | | | OF DISCONNECT. | | | | | | 4)NOTE: PLEASE SEE FEEDERS INDICATED ON | | | SCHEDULE. MENTIONS GRNDS FOR NEUTRAL? | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE 210.8B3 2002 NEC, | | | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT | | | RECEPTACLES IN NONDWELLING-TYPE KITCHENS | | | TO BE GFCI PROTECTED. THIS REQUIREMENT | | | APPLIES TO EACH AND EVERY 15- AND | | | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, | | | WHETHER OR NOT THE RECEPTACLE SERVES | | | COUNTERTOP APPLIANCES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-12-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-12-19 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-12-19 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2005-12-19 00:00:00 | 1. BUILDING ADDRESS COULD NOT BE LOCATED | | | ON ELEVATION DRAWINGS. A MINIMUM OF AT | | | LEAST 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 2. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-07-11 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-07-11 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2005-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH | | | NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. EXITS SHALL REMAIN CLEAR AND | | | UNOBSTRUCTED DURING WORK. | | | | | | 4. NO GASOLINE POWERED EQUIPMENT SHALL | | | BE USED INDOORS TO PREVENT CARBON | | | MONOXIDE ACCUMULATIONS WITHIN IT. | | | | | | 5. BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. A MINIMUM OF AT | | | LEAST 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 7. PLANS APPEAR TO HAVE BEEN COPIED. | | | | | | 8. PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND | | | CEILINGS. | | | | | | 9. PLEASE PROVIDE DETAILS ON PROPOSED | | | FIRE WRAP NOTED IN M1.1. | | | | | | 10.SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY HOOD, DUCT, AND SUPPRESSION | | | SYSTEM MODIFICATIONS. | | | | | | 11. OCCUPANT LOAD TO BE DETERMINED BY | | | FIRE RESCUE OFFICIALS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 835-2910 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-01-31 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-01-31 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 13. SHT P4.0 GAS RISER DIAGRAM: THE | | | FOLLOWING INFORMATION IS REQUIRED FOR | | | THE GAS PERMIT: | | | B. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). - PLEASE INDICATE IF THE PIZZA | | | OVEN HAS 454,000 BTU TO EACH SECTION OF | | | THE PIZZA OVEN. IF NOT PLEASE INDICATE | | | HOW MANY BTU'S TO EACH SECTION OF THE | | | PIZZA OVEN. | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. - TO | | | BE SUBMITTED FOR PLAN REVIEW TO VERIFY | | | LISTING OF PRODUCT AND TO VERIFY BTU | | | LOAD ON THE SYSTEM. | | | E. SUBMIT MANUF. SPECIFICATIONS SHEETS | | | FOR REQUIRED 2LB TO 1/2 LB REGULATORS. | | | THE MANUF. SHEETS ARE REQUIRED AT THE | | | TIME OF THE PLAN REVIEW. PLEASE SUBMIT. | | | F. SHOW THE LOCATION OF THE REGULATORS | | | ON THE GAS RISER DIAGRAM. SECTION | | | 104.2.1. - IF THE SECONDARY REGULATOR IS | | | TO BE INSTALLED ON THE DROP TO THE PIZZA | | | OVEN, A SHUT OFF VALVE IS REQUIRED | | | UPSTREAM OF THE REGULATOR. IF THIS | | | REGULATOR IS INSTALLED, THE THREE | | | REGULATORS AT THE PIZZA OVEN WILL NOT BE | | | REQUIRED. ONLY THE SHUT OFF VALVES FOR | | | THE APPLIANCES WILL BE REQUIRED AT THE | | | PIZZA OVENS. IF USING THE THREE | | | REGULATORS AT THE OVENS, THE REGULATOR | | | ON THE DROP WILL NOT BE REQUIRED. PLEASE | | | CLARIFY. | | | | | | COMMENTS FROM PLUMBING REVIEW | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-11-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-29 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-29 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2005-12-14 00:00:00 | TO "COMM" BD#28 | | 2005-11-29 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-07-24 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2005-06-23 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2005-06-27 00:00:00 | TO "COMM" BD#4 | | 2005-06-23 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-09 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-09 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2006-01-09 00:00:00 | PROVISO: | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPPRESSION AND WALK-IN COOLERS. | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL | | | DATA WITH MECHANICAL PERMIT APPLICATION. | | | | | | TERMINATION OF EXHAUST FROM THE TYPE I | | | HOOD SHALL COMPLY WITH 2001 FMC | | | 506.3.14.3 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-01-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-21 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-07-21 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2005-07-21 00:00:00 | DENIED: | | | PLEASE NOTE, ADDITIONAL PERMITS REQUIRED | | | FOR HOOD, FIRE SUPPRESSION & WALK-IN | | | COOLERS.PLEASE PROVIDE PLANS AND | | | MANUFACTURERS SUBMITTAL DATA WITH PERMIT | | | APPLICATION. | | | | | | 1.PLANS MUST BE SIGNED, SEALED & DATED | | | BY THE ARCHITECT & ENGINEER IN | | | ACCORDANCE WITH FS 471.025 & 481.221. | | | STAMPS ARE NOT ACCEPTABLE.PRINTED | | | NAME, ADDRESS & LICENSE # OR TITLE BLOCK | | | IS ALSO REQUIRED PER FAC 61G1-16.004 & | | | 61G15-23.002 (2). | | | | | | 2.PLEASE CLARIFY WALL TYPES INDICATED | | | ON PLAN SHEET A1.1.IT APPEARS ALL | | | INTERIOR WALLS ARE "FIRE RATED".PLEASE | | | CLARIFY, DOES THIS "RATING" END AT THE | | | CEILING?DUCTS PENETRATING "RATED" | | | PARTITIONS ARE REQUIRED TO HAVE FIRE | | | DAMPERS AT THE PENETRATION OR COMPLY | | | WITH 2001 FBC(M) EXCEPTION 3 ITEMS 1 | | | THROUGH 4. | | | | | | 3.PLAN SHEET M2.1 DETAIL #5 & 10 DO | | | NOT INDICATE THE HEIGHT FOR THE ROOF | | | CURBS.PER 2001 FBC 1511.7, CURBS SHALL | | | BE A MINIMUM OF 8" ABOVE THE ROOF | | | SURFACE. | | | | | | 4.PLAN SHEET M2.1 KITCHEN EXHAUST FAN | | | DETAIL #2, THE FAN SHALL BE A HINGED | | | UPBLAST TYPE PER NFPA 96. | | | | | | 5.PLEASE PROVIDE OUTSIDE AIR | | | CALUCALTIONS PER 2001 FBC(M) TABLE | | | 403.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-01-31 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-01-31 |
Time |
17:38 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | A. FROM PREVIOUS REVIEW. COMMENT NUMBER | | | WILL STAY THE SAME AS FIRST REVIEW: | | | | | | 4. SHTS A1.2, A1.3, & A1.4 REFERENCE | | | EQUIPMENT LAYOUT PLAN, AND EQUIPMENT | | | SCHEDULES. IF THE EQUIPMENT IN THE | | | RESTURANT IS BEING ALTERED, MOVED, | | | ADDED, OR DELETED, PLANS SHALL BE ROUTED | | | TO DBPR DIVISION OF HOTELS & RESTURANTS | | | FOR REVIEW. PLANS WILL BE STAMPED BY | | | DBPR REVIEWERS AND 2 PAGE "WORKSHEETS" | | | WILL BE ATTACHED TO EACH SET OF PLANS | | | RESUBMITTED TO CITY OF WPB FOR REVIEW. | | | SECTION 101.4.7 - PLEASE INDICATE IF THE | | | FOOD PREP/KITCHEN AREA WILL BE CHANGED | | | OR IF ALL EQUIPMENT WILL BE REINSTALLED | | | IN THE SAME LOCATION. SECTION 104.2.1. - | | | ATTACH THE STAMPED SHEET FROM DBPR AND | | | THE TWO SECTION "SPECIFICATION | | | WORKSHEETS" TO EACH SET OF PLANS | | | SUBMITTED FOR APPROVAL. | | | 5. SHT A8.3 RESTROOM ELEVATIONS. SHOW | | | THE FOLLOWING: | | | (FOR THE URINAL) | | | C. 11-4.18.3 CLEAR FLOOR SPACE - NOT | | | SHOWN. | | | (FOR THE LAVS) | | | E. 11-4.19.3 CLEAR FLOOR SPACE - LAV IN | | | MEN'S TOILET ROOM SHALL BE ACCESSIBLE | | | ALSO FOR USE BY PERSONS USING ACCESSIBLE | | | URINAL. - NOT SHOWN. | | | F. 11-4.19.5 FAUCETS - NOT ADDRESSED. | | | 6. SHT A1.2 TURNING AREA REQUIRED IN | | | SECTION 11-4.22.3 SHALL BE IN THE TOILET | | | ROOM, NOT THE STALL. - NOT ADDRESSED. | | | 9. SHT P1.1 NEW GREASE INTECEPTORS ARE | | | INDICATED. PLEASE CONTACT LYNN MASSON | | | ENVIRONMENTAL COMPLIANCE FOR SIZING. | | | PLEASE CONTACT HER AT (561) 822-2271, | | | FAX (561) 822-2279, OR E-MAIL | | | [email protected]. SUBMIT DETERMINATION | | | SHEET WITH EACH SET OF PLANS WHEN | | | RESUBMITTING. WASTE ORD. #3434. PLEASE | | | SUBMIT APPROVAL SHEET FROM ENVIRONMENTAL | | | COMPLIANCE MANAGER. | | | 11. SHT P3.0 WATER FILTER SYSTEM SHALL | | | COMPLY WITH NSF 42. SECTION 611.1 | | | PROVIDE MANUF. SPECIFICATION SHEETS. - | | | MANUF. SPECIFICATION SHEETS NOT | | | SUBMITTED. | | | 13. SHT P4.0 GAS RISER DIAGRAM: THE | | | FOLLOWING INFORMATION IS REQUIRED FOR | | | THE GAS PERMIT: | | | B. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). - PLEASE INDICATE IF THE PIZZA | | | OVEN HAS 454,000 BTU TO EACH SECTION OF | | | THE PIZZA OVEN. IF NOT PLEASE INDICATE | | | HOW MANY BTU'S TO EACH SECTION OF THE | | | PIZZA OVEN. | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. - TO | | | BE SUBMITTED FOR PLAN REVIEW TO VERIFY | | | LISTING OF PRODUCT AND TO VERIFY BTU | | | LOAD ON THE SYSTEM. | | | E. SUBMIT MANUF. SPECIFICATIONS SHEETS | | | FOR REQUIRED 2LB TO 1/2 LB REGULATORS. | | | THE MANUF. SHEETS ARE REQUIRED AT THE | | | TIME OF THE PLAN REVIEW. PLEASE SUBMIT. | | | F. SHOW THE LOCATION OF THE REGULATORS | | | ON THE GAS RISER DIAGRAM. SECTION | | | 104.2.1. - IF THE SECONDARY REGULATOR IS | | | TO BE INSTALLED ON THE DROP TO THE PIZZA | | | OVEN, A SHUT OFF VALVE IS REQUIRED | | | UPSTREAM OF THE REGULATOR. IF THIS | | | REGULATOR IS INSTALLED, THE THREE | | | REGULATORS AT THE PIZZA OVEN WILL NOT BE | | | REQUIRED. ONLY THE SHUT OFF VALVES FOR | | | THE APPLIANCES WILL BE REQUIRED AT THE | | | PIZZA OVENS. IF USING THE THREE | | | REGULATORS AT THE OVENS, THE REGULATOR | | | ON THE DROP WILL NOT BE REQUIRED. PLEASE | | | CLARIFY. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-16 |
Time |
11:20 |
Rev Time |
3.00 |
| Received By |
kstevens |
Date |
2005-07-16 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2005-07-16 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | | | | | | | 1. ALL ARCHITECTURAL SHEETS REQUIRE A | | | RAISED SEAL AND "WET SIGNATURE". ALL | | | SHEETS APPEAR TO BE PHOTO COPIES OF | | | SIGNED, SEALED PLANS. FAC 61G1-61.003 & | | | FS 481.2055. | | | 2. ALL SHEETS SIGNED, SEALED, & DATED BY | | | THE ARCHITECT SHALL CONTAIN A TITLE | | | BLOCK WITH ALL INFORMATION REQUIRED BY | | | FAC 61G1-16.004. | | | 3. ALL MEP SHEETS REQUIRE A RAISED SEAL, | | | AND A "WET SIGNATURE". ALL MEP SHEET | | | APPEAR TO BE PHOTO COPIES OF SIGNED, | | | SEALED PLANS. FAC 61G15-23.002(1)(2) AND | | | FS 471.025. | | | 4. SHTS A1.2, A1.3, & A1.4 REFERENCE | | | EQUIPMENT LAYOUT PLAN, AND EQUIPMENT | | | SCHEDULES. IF THE EQUIPMENT IN THE | | | RESTURANT IS BEING ALTERED, MOVED, | | | ADDED, OR DELETED, PLANS SHALL BE ROUTED | | | TO DBPR DIVISION OF HOTELS & RESTURANTS | | | FOR REVIEW. PLANS WILL BE STAMPED BY | | | DBPR REVIEWERS AND 2 PAGE "WORKSHEETS" | | | WILL BE ATTACHED TO EACH SET OF PLANS | | | RESUBMITTED TO CITY OF WPB FOR REVIEW. | | | SECTION 101.4.7 - PLEASE INDICATE IF THE | | | FOOD PREP/KITCHEN AREA WILL BE CHANGED | | | OR IF ALL EQUIPMENT WILL BE REINSTALLED | | | IN THE SAME LOCATION. SECTION 104.2.1. | | | 5. SHT A8.3 RESTROOM ELEVATIONS. SHOW | | | THE FOLLOWING: | | | (FOR THE URINAL) | | | B. 11-4.18.2 HEIGHT | | | C. 11-4.18.3 CLEAR FLOOR SPACE | | | D. 11-4.18.4 FLUSH CONTROLS | | | (FOR THE LAVS) | | | E. 11-4.19.3 CLEAR FLOOR SPACE - LAV IN | | | MEN'S TOILET ROOM SHALL BE ACCESSIBLE | | | ALSO FOR USE BY PERSONS USING ACCESSIBLE | | | URINAL. | | | F. 11-4.19.5 FAUCETS | | | 6. SHT A1.2 TURNING AREA REQUIRED IN | | | SECTION 11-4.22.3 SHALL BE IN THE TOILET | | | ROOM, NOT THE STALL. | | | 7. SHT P1.1 ALL FLOOR DRAINS AND KITCHEN | | | EQUIPMENT SHALL CONNECT TO THE GREASE | | | SYSTEM. | | | 8. SHT P1.1 THE DISHWASHER SHALL CONNECT | | | TO THE SANITARY SYSTEM. UTILTIY | | | REQUIREMENT. | | | 9. SHT P1.1 NEW GREASE INTECEPTORS ARE | | | INDICATED. PLEASE CONTACT LYNN MASSON | | | ENVIRONMENTAL COMPLIANCE FOR SIZING. | | | PLEASE CONTACT HER AT (561) 822-2271, | | | FAX (561) 822-2279, OR E-MAIL | | | [email protected]. SUBMIT DETERMINATION | | | SHEET WITH EACH SET OF PLANS WHEN | | | RESUBMITTING. WASTE ORD. #3434. | | | 10. SHT P1.1 SHOWS THE CONDENSATE FROM | | | THE A/C UNITS DRAINING INTO THE | | | SANITARY. THIS IS NOT APPROVED PER CITY | | | CODE SECTION 90-125(5). CONDENSATE SHALL | | | DRAIN SEPARATELY FROM THE BUILDING AND | | | CONNECT INTO THE STORM LINE, CATCH | | | BASIN, DRYWELL, OR PLANTED AREA MINIMUM | | | 1 FOOT FROM THE STRUCTURAL SIDE WALLS. | | | 11. SHT P3.0 WATER FILTER SYSTEM SHALL | | | COMPLY WITH NSF 42. SECTION 611.1 | | | PROVIDE MANUF. SPECIFICATION SHEETS. | | | 12. SHT P4.0 SANT. & GREASE RISER | | | DIAGRAMS. SEE COMMENTS 7 AND 8. RISER | | | DIAGRAMS SHALL REFLECT CHANGES REQUIRED | | | BY THESE COMMENTS. SECTION 104.2.1. | | | 13. SHT P4.0 GAS RISER DIAGRAM: THE | | | FOLLOWING INFORMATION IS REQUIRED FOR | | | THE GAS PERMIT: | | | A. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | B. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | E. SUBMIT MANUF. SPECIFICATIONS SHEETS | | | FOR REQUIRED 2LB TO 1/2 LB REGULATORS. | | | F. SHOW THE LOCATION OF THE REGULATORS | | | ON THE GAS RISER DIAGRAM. SECTION | | | 104.2.1. | | | 14. SUBMIT A WATER RISER DIAGRAM SHOWING | | | ALL PIPE SIZES, VALVES, WATER HAMMER | | | ARRESTORS, (REQD BY SECTION 604.9 AND | | | LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING PER | | | PDI-WH 201). ECT. SECTION 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-01-24 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-01-24 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-01-24 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2006-01-24 00:00:00 | DENIED, RESUB | | | 1. MUST PROVIDE THE UNITY OF TITLE FOR | | | THE PARCEL (PROPERTY). | | | 2. MUST PROVIDE A COMPLETE SITEPLAN OF | | | THE PROPERTY, SHOWING THE ADDRESS AND | | | SETBACKS OF EXISTING BUILDING. | | | 3. THE PROPOSED WORK MUST BE IDENTIFY ON | | | THE SITEPLAN WITH SETBACKS. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-07-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-07-08 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-07-08 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |