Plan Review Details - Permit 05061381
Plan Review Stops For Permit 05061381
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-07 Cont ID  
Sent By jwitmer Date 2006-02-07 Time 12:52 Rev Time 2.22
Received By jwitmer Date 2006-02-07 Time 12:52 Sent To PC
Notes
2006-02-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061381
 ADD: 31150 45TH ST
 CONT:FRANCHISE PROPERTIES SERVICES
 INC
 TEL: (316)304-8749
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT 3A)FROM THE PREVIOUS REVIEW,
 PLANS DO NOT INDICATE WHICH ARE NEW
 OPENINGS & WHICH ARE EXISTING, PROVIDE
 ADDITIONAL INFORMATION FOR WINDOWS AND
 DOORS.
 ARCHITECTURAL ELEVATIONS INDICATE
 WINDOWS AND MULLION TO REMAIN BUT THE
 STRUCTURAL PLANS S0.1 WIND LOAD NOTES
 WINDOWS, DOORS AND MECHANICAL LOUVERS
 TO WITHSTAND WIND LOADS AND LARGE MISSLE
 IMPACT TESTING.S1 SHOWS DETAIL 9 ON S3.1
  
 NEWLY FRAMED WALL WITH STEEL COLUMNS.
 THE NEWLY FRAMED WALLS DO NOT SHOW ANY
 STRAPPING HOLDING TO THE STEEL COLUMN/
 EXPLAIN HOW STRUCTURAL STATEMENT OF
 WINDOWS, DOORS & LOUVER TO MEET THE WIND
 LOADS & IMPACT STANDARD WITH THE OLD
 GLAZING UNITS?
 1606.2.4 MAIN WIND FORCE RESISTING
 SYSTEM (MWFRS). ALL ELEMENTS AND
 CONNECTIONS OF THE MWFRS SHALL BE
 DESIGNED FOR VERTICAL AND HORIZONTAL
 LOADS BASED ON THE COMBINED LEEWARD AND
 WINDWARD WALL PRESSURES AND ROOF
 PRESSURES DETERMINED FROM TABLE 1606.2A.
 PRESSURES SHALL BE APPLIED IN
 ACCORDANCE WITH THE LOADING DIAGRAMS
 SHOWN IN FIGURE 1606.2A TO THE END
 ZONE AND INTERIOR ZONE AS SHOWN IN
 FIGURE 1606.2B.THE BUILDING SHALL
 BE DESIGNED FOR ALL WIND DIRECTIONS.
 FOR BUILDINGS HAVING FLAT ROOFS, A
 RIDGE LINE NORMAL TO THE WIND DIRECTION
 SHALL BE ASSUMED AT THE MID-LENGTH
 DIMENSION OF THE ROOF FOR ALL DIRECTIONS
 CONSIDERED.EACH CORNER SHALLBE
 CONSIDERED IN TURN AS THE WINDWARD
 CORNER.
 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 GLAZED OPENINGS LOCATED WITHIN 30 FT OF
 GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
  
  
 2) COMMENT3B) FROM THE PREVIOUS REVIEW
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) DOORS
 C)SIDING EFIS
 D) LOUVERS
 E) ROOFING ASSEMBLIES
  
 4) PLANS INDICATE REWORK OF ROOF AND NEW
 PARAPET AND FLASHING, PROVIDE PRODUCT
 TESTING REPORTS FOR ROOFING ASSEMBLIES.
  
 5) PLANS DO NOT PROVIDE WHAT MINIMUM
 TYPE BUILDING DESIGN THIS PLAN WAS
 DESIGNED TO? 601.2.1, 601.2.2.
  
 6) PROVIDE A SITE PLAN WITH DIMENSIONS
 TO THE PROPERTY LINE, TABLE 600 THERE
 MAY BE OPENING ISSUES.
 TODAY I WAS IN A MEETING WITH THE
 CONTRACTOR WHO IS GOING TO BRING IN A
 SURVEY SO TABLE 600 ISSUES MAY BE
 ADDRESSED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 11:21 Rev Time 2.22
Received By jwitmer Date 2005-07-24 Time 11:21 Sent To PC
Notes
2005-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061381
 ADD: 31150 45TH ST
 CONT:FRANCHISE PROPERTIES SERVICES
 INC
 TEL: (316)304-8749
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 3A)PLANS DO NOT INDICATE WHICH ARE NEW
 OPENINGS & WHICH ARE EXISTING, PROVIDE
 ADDITIONAL INFORMATION FOR WINDOWS AND
 DOORS.
  
 3B) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3C)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 D) WINDOWS
 E) DOORS
 F) SIDING EFIS
 G) ROOFING ASSEMBLIES
  
 4) S)0.1 WIND DESIGN LOADS, INDICATES A
 130 MPH WIND ZONE SEE FIGURE 1606, WEST
 PALM BEACH IS IN A 140 MPH WIND ZONE.
 S0.2 PRESSURES ARE FOR A 130 NOT 140
 WIND ZONE CORRECT.
  
 5) PLANS DO NOT PROVIDE WHAT MINIMUM
 TYPE BUILDING DESIGN THIS PLAN WAS
 DESIGNED TO? 601.2.1, 601.2.2.
  
 6) PROVIDE A SITE PLAN WITH DIMENSIONS
 TO THE PROPERTY LINE, TABLE 600 THERE
 MAY BE OPENING ISSUES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 16:42 Sent To  
Notes
2005-12-21 00:00:00REDLINED PLANS**
  
  
 250.6, 250.24 FOR EQUIPMENT GROUNDS OR
 BONDS,
  
 230.70 , NO MORE THAN SIX SPACES
 PERMITTED IN DP, OR A MCB WILL BE
 REQUIRED.
 230.70
  
 ALL KITCHEN RECEPTS MEETING THE
 REQUIREMENTS OF 210.8B3 SHALL BE GFI
 PROTECTED.
 THIS IS ABOVE THE ALREADY IDENTIFIED
 "SQUARE" GFI SHOWN.
 PLEASE SEE SOME ARE MISSING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 07:08 Rev Time 1.50
Received By dpalmer Date 2005-07-05 Time 15:35 Sent To  
Notes
2005-07-06 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE ALL SHEETS IN BOTH
 SET OF PLANS SUBMITTED ARE PHOTOCOPIES
 OF SIGNED AND SEALED DRAWINGS. PLEASE
 ALL PLANS MUST BE ORIGINAL SIGNED, DATED
 AND SEALED WITH RAISED SEAL PER FS
 481.221 AND FS 471.025.
 PLEASE SEE MISSING TITLE BLOCK
 INFORMATION ON "A"- SHEETS ETC AS
 REQUIRED UNDER FAC 61G1-16.004 FS
 481.219.
 THE ABOVE IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE 250.50 : COLD WATER
 PIPE TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 3)NOTE: PLEASE SEE 250.6,250.24 AND
 EQUIPMENT GROUNDING CONDUCTOR SHALL NOT
 BE INSTALLED UNTIL AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 4)NOTE: PLEASE SEE FEEDERS INDICATED ON
 SCHEDULE. MENTIONS GRNDS FOR NEUTRAL?
 215.5
  
 5)NOTE: PLEASE SEE 210.8B3 2002 NEC,
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-19 Cont ID  
Sent By mcarsill Date 2005-12-19 Time 10:15 Rev Time 0.00
Received By mcarsill Date 2005-12-19 Time 10:15 Sent To  
Notes
2005-12-19 00:00:001. BUILDING ADDRESS COULD NOT BE LOCATED
 ON ELEVATION DRAWINGS. A MINIMUM OF AT
 LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 2. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 12:36 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 12:36 Sent To  
Notes
2005-07-11 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. EXITS SHALL REMAIN CLEAR AND
 UNOBSTRUCTED DURING WORK.
  
 4. NO GASOLINE POWERED EQUIPMENT SHALL
 BE USED INDOORS TO PREVENT CARBON
 MONOXIDE ACCUMULATIONS WITHIN IT.
  
 5. BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. A MINIMUM OF AT
 LEAST 6" HIGH NUMBERS ARE REQUIRED.
  
 7. PLANS APPEAR TO HAVE BEEN COPIED.
  
 8. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 9. PLEASE PROVIDE DETAILS ON PROPOSED
 FIRE WRAP NOTED IN M1.1.
  
 10.SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD, DUCT, AND SUPPRESSION
 SYSTEM MODIFICATIONS.
  
 11. OCCUPANT LOAD TO BE DETERMINED BY
 FIRE RESCUE OFFICIALS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-31 Cont ID  
Sent By kstevens Date 2006-01-31 Time 18:01 Rev Time 0.00
Received By kstevens Date 2006-01-31 Time 18:01 Sent To  
Notes
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 13. SHT P4.0 GAS RISER DIAGRAM: THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 THE GAS PERMIT:
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - PLEASE INDICATE IF THE PIZZA
 OVEN HAS 454,000 BTU TO EACH SECTION OF
 THE PIZZA OVEN. IF NOT PLEASE INDICATE
 HOW MANY BTU'S TO EACH SECTION OF THE
 PIZZA OVEN.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - TO
 BE SUBMITTED FOR PLAN REVIEW TO VERIFY
 LISTING OF PRODUCT AND TO VERIFY BTU
 LOAD ON THE SYSTEM.
 E. SUBMIT MANUF. SPECIFICATIONS SHEETS
 FOR REQUIRED 2LB TO 1/2 LB REGULATORS.
 THE MANUF. SHEETS ARE REQUIRED AT THE
 TIME OF THE PLAN REVIEW. PLEASE SUBMIT.
 F. SHOW THE LOCATION OF THE REGULATORS
 ON THE GAS RISER DIAGRAM. SECTION
 104.2.1. - IF THE SECONDARY REGULATOR IS
 TO BE INSTALLED ON THE DROP TO THE PIZZA
 OVEN, A SHUT OFF VALVE IS REQUIRED
 UPSTREAM OF THE REGULATOR. IF THIS
 REGULATOR IS INSTALLED, THE THREE
 REGULATORS AT THE PIZZA OVEN WILL NOT BE
 REQUIRED. ONLY THE SHUT OFF VALVES FOR
 THE APPLIANCES WILL BE REQUIRED AT THE
 PIZZA OVENS. IF USING THE THREE
 REGULATORS AT THE OVENS, THE REGULATOR
 ON THE DROP WILL NOT BE REQUIRED. PLEASE
 CLARIFY.
  
 COMMENTS FROM PLUMBING REVIEW
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-29 Cont ID  
Sent By adarroug Date 2005-11-29 Time 13:34 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 13:34 Sent To  
Notes
2005-12-14 00:00:00TO "COMM" BD#28
2005-11-29 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 11:20 Rev Time 0.00
Received By jwitmer Date 2005-06-23 Time 16:42 Sent To  
Notes
2005-06-27 00:00:00TO "COMM" BD#4
2005-06-23 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-09 Cont ID  
Sent By pkrauss Date 2006-01-09 Time 12:55 Rev Time 0.00
Received By pkrauss Date 2006-01-09 Time 10:31 Sent To  
Notes
2006-01-09 00:00:00PROVISO:
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION AND WALK-IN COOLERS.
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA WITH MECHANICAL PERMIT APPLICATION.
  
 TERMINATION OF EXHAUST FROM THE TYPE I
 HOOD SHALL COMPLY WITH 2001 FMC
 506.3.14.3
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-09 Cont ID  
Sent By pkrauss Date 2005-07-21 Time 06:53 Rev Time 0.00
Received By pkrauss Date 2005-07-21 Time 06:53 Sent To  
Notes
2005-07-21 00:00:00DENIED:
 PLEASE NOTE, ADDITIONAL PERMITS REQUIRED
 FOR HOOD, FIRE SUPPRESSION & WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURERS SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 1.PLANS MUST BE SIGNED, SEALED & DATED
 BY THE ARCHITECT & ENGINEER IN
 ACCORDANCE WITH FS 471.025 & 481.221.
 STAMPS ARE NOT ACCEPTABLE.PRINTED
 NAME, ADDRESS & LICENSE # OR TITLE BLOCK
 IS ALSO REQUIRED PER FAC 61G1-16.004 &
 61G15-23.002 (2).
  
 2.PLEASE CLARIFY WALL TYPES INDICATED
 ON PLAN SHEET A1.1.IT APPEARS ALL
 INTERIOR WALLS ARE "FIRE RATED".PLEASE
 CLARIFY, DOES THIS "RATING" END AT THE
 CEILING?DUCTS PENETRATING "RATED"
 PARTITIONS ARE REQUIRED TO HAVE FIRE
 DAMPERS AT THE PENETRATION OR COMPLY
 WITH 2001 FBC(M) EXCEPTION 3 ITEMS 1
 THROUGH 4.
  
 3.PLAN SHEET M2.1 DETAIL #5 & 10 DO
 NOT INDICATE THE HEIGHT FOR THE ROOF
 CURBS.PER 2001 FBC 1511.7, CURBS SHALL
 BE A MINIMUM OF 8" ABOVE THE ROOF
 SURFACE.
  
 4.PLAN SHEET M2.1 KITCHEN EXHAUST FAN
 DETAIL #2, THE FAN SHALL BE A HINGED
 UPBLAST TYPE PER NFPA 96.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALUCALTIONS PER 2001 FBC(M) TABLE
 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-31 Cont ID  
Sent By kstevens Date 2006-01-31 Time 17:38 Rev Time 0.00
Received By kstevens Date 2006-01-31 Time 17:38 Sent To  
Notes
2006-01-31 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A. FROM PREVIOUS REVIEW. COMMENT NUMBER
 WILL STAY THE SAME AS FIRST REVIEW:
  
 4. SHTS A1.2, A1.3, & A1.4 REFERENCE
 EQUIPMENT LAYOUT PLAN, AND EQUIPMENT
 SCHEDULES. IF THE EQUIPMENT IN THE
 RESTURANT IS BEING ALTERED, MOVED,
 ADDED, OR DELETED, PLANS SHALL BE ROUTED
 TO DBPR DIVISION OF HOTELS & RESTURANTS
 FOR REVIEW. PLANS WILL BE STAMPED BY
 DBPR REVIEWERS AND 2 PAGE "WORKSHEETS"
 WILL BE ATTACHED TO EACH SET OF PLANS
 RESUBMITTED TO CITY OF WPB FOR REVIEW.
 SECTION 101.4.7 - PLEASE INDICATE IF THE
 FOOD PREP/KITCHEN AREA WILL BE CHANGED
 OR IF ALL EQUIPMENT WILL BE REINSTALLED
 IN THE SAME LOCATION. SECTION 104.2.1. -
 ATTACH THE STAMPED SHEET FROM DBPR AND
 THE TWO SECTION "SPECIFICATION
 WORKSHEETS" TO EACH SET OF PLANS
 SUBMITTED FOR APPROVAL.
 5. SHT A8.3 RESTROOM ELEVATIONS. SHOW
 THE FOLLOWING:
 (FOR THE URINAL)
 C. 11-4.18.3 CLEAR FLOOR SPACE - NOT
 SHOWN.
 (FOR THE LAVS)
 E. 11-4.19.3 CLEAR FLOOR SPACE - LAV IN
 MEN'S TOILET ROOM SHALL BE ACCESSIBLE
 ALSO FOR USE BY PERSONS USING ACCESSIBLE
 URINAL. - NOT SHOWN.
 F. 11-4.19.5 FAUCETS - NOT ADDRESSED.
 6. SHT A1.2 TURNING AREA REQUIRED IN
 SECTION 11-4.22.3 SHALL BE IN THE TOILET
 ROOM, NOT THE STALL. - NOT ADDRESSED.
 9. SHT P1.1 NEW GREASE INTECEPTORS ARE
 INDICATED. PLEASE CONTACT LYNN MASSON
 ENVIRONMENTAL COMPLIANCE FOR SIZING.
 PLEASE CONTACT HER AT (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected]. SUBMIT DETERMINATION
 SHEET WITH EACH SET OF PLANS WHEN
 RESUBMITTING. WASTE ORD. #3434. PLEASE
 SUBMIT APPROVAL SHEET FROM ENVIRONMENTAL
 COMPLIANCE MANAGER.
 11. SHT P3.0 WATER FILTER SYSTEM SHALL
 COMPLY WITH NSF 42. SECTION 611.1
 PROVIDE MANUF. SPECIFICATION SHEETS. -
 MANUF. SPECIFICATION SHEETS NOT
 SUBMITTED.
 13. SHT P4.0 GAS RISER DIAGRAM: THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 THE GAS PERMIT:
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - PLEASE INDICATE IF THE PIZZA
 OVEN HAS 454,000 BTU TO EACH SECTION OF
 THE PIZZA OVEN. IF NOT PLEASE INDICATE
 HOW MANY BTU'S TO EACH SECTION OF THE
 PIZZA OVEN.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - TO
 BE SUBMITTED FOR PLAN REVIEW TO VERIFY
 LISTING OF PRODUCT AND TO VERIFY BTU
 LOAD ON THE SYSTEM.
 E. SUBMIT MANUF. SPECIFICATIONS SHEETS
 FOR REQUIRED 2LB TO 1/2 LB REGULATORS.
 THE MANUF. SHEETS ARE REQUIRED AT THE
 TIME OF THE PLAN REVIEW. PLEASE SUBMIT.
 F. SHOW THE LOCATION OF THE REGULATORS
 ON THE GAS RISER DIAGRAM. SECTION
 104.2.1. - IF THE SECONDARY REGULATOR IS
 TO BE INSTALLED ON THE DROP TO THE PIZZA
 OVEN, A SHUT OFF VALVE IS REQUIRED
 UPSTREAM OF THE REGULATOR. IF THIS
 REGULATOR IS INSTALLED, THE THREE
 REGULATORS AT THE PIZZA OVEN WILL NOT BE
 REQUIRED. ONLY THE SHUT OFF VALVES FOR
 THE APPLIANCES WILL BE REQUIRED AT THE
 PIZZA OVENS. IF USING THE THREE
 REGULATORS AT THE OVENS, THE REGULATOR
 ON THE DROP WILL NOT BE REQUIRED. PLEASE
 CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-16 Cont ID  
Sent By kstevens Date 2005-07-16 Time 11:20 Rev Time 3.00
Received By kstevens Date 2005-07-16 Time 11:20 Sent To  
Notes
2005-07-16 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
  
 1. ALL ARCHITECTURAL SHEETS REQUIRE A
 RAISED SEAL AND "WET SIGNATURE". ALL
 SHEETS APPEAR TO BE PHOTO COPIES OF
 SIGNED, SEALED PLANS. FAC 61G1-61.003 &
 FS 481.2055.
 2. ALL SHEETS SIGNED, SEALED, & DATED BY
 THE ARCHITECT SHALL CONTAIN A TITLE
 BLOCK WITH ALL INFORMATION REQUIRED BY
 FAC 61G1-16.004.
 3. ALL MEP SHEETS REQUIRE A RAISED SEAL,
 AND A "WET SIGNATURE". ALL MEP SHEET
 APPEAR TO BE PHOTO COPIES OF SIGNED,
 SEALED PLANS. FAC 61G15-23.002(1)(2) AND
 FS 471.025.
 4. SHTS A1.2, A1.3, & A1.4 REFERENCE
 EQUIPMENT LAYOUT PLAN, AND EQUIPMENT
 SCHEDULES. IF THE EQUIPMENT IN THE
 RESTURANT IS BEING ALTERED, MOVED,
 ADDED, OR DELETED, PLANS SHALL BE ROUTED
 TO DBPR DIVISION OF HOTELS & RESTURANTS
 FOR REVIEW. PLANS WILL BE STAMPED BY
 DBPR REVIEWERS AND 2 PAGE "WORKSHEETS"
 WILL BE ATTACHED TO EACH SET OF PLANS
 RESUBMITTED TO CITY OF WPB FOR REVIEW.
 SECTION 101.4.7 - PLEASE INDICATE IF THE
 FOOD PREP/KITCHEN AREA WILL BE CHANGED
 OR IF ALL EQUIPMENT WILL BE REINSTALLED
 IN THE SAME LOCATION. SECTION 104.2.1.
 5. SHT A8.3 RESTROOM ELEVATIONS. SHOW
 THE FOLLOWING:
 (FOR THE URINAL)
 B. 11-4.18.2 HEIGHT
 C. 11-4.18.3 CLEAR FLOOR SPACE
 D. 11-4.18.4 FLUSH CONTROLS
 (FOR THE LAVS)
 E. 11-4.19.3 CLEAR FLOOR SPACE - LAV IN
 MEN'S TOILET ROOM SHALL BE ACCESSIBLE
 ALSO FOR USE BY PERSONS USING ACCESSIBLE
 URINAL.
 F. 11-4.19.5 FAUCETS
 6. SHT A1.2 TURNING AREA REQUIRED IN
 SECTION 11-4.22.3 SHALL BE IN THE TOILET
 ROOM, NOT THE STALL.
 7. SHT P1.1 ALL FLOOR DRAINS AND KITCHEN
 EQUIPMENT SHALL CONNECT TO THE GREASE
 SYSTEM.
 8. SHT P1.1 THE DISHWASHER SHALL CONNECT
 TO THE SANITARY SYSTEM. UTILTIY
 REQUIREMENT.
 9. SHT P1.1 NEW GREASE INTECEPTORS ARE
 INDICATED. PLEASE CONTACT LYNN MASSON
 ENVIRONMENTAL COMPLIANCE FOR SIZING.
 PLEASE CONTACT HER AT (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected]. SUBMIT DETERMINATION
 SHEET WITH EACH SET OF PLANS WHEN
 RESUBMITTING. WASTE ORD. #3434.
 10. SHT P1.1 SHOWS THE CONDENSATE FROM
 THE A/C UNITS DRAINING INTO THE
 SANITARY. THIS IS NOT APPROVED PER CITY
 CODE SECTION 90-125(5). CONDENSATE SHALL
 DRAIN SEPARATELY FROM THE BUILDING AND
 CONNECT INTO THE STORM LINE, CATCH
 BASIN, DRYWELL, OR PLANTED AREA MINIMUM
 1 FOOT FROM THE STRUCTURAL SIDE WALLS.
 11. SHT P3.0 WATER FILTER SYSTEM SHALL
 COMPLY WITH NSF 42. SECTION 611.1
 PROVIDE MANUF. SPECIFICATION SHEETS.
 12. SHT P4.0 SANT. & GREASE RISER
 DIAGRAMS. SEE COMMENTS 7 AND 8. RISER
 DIAGRAMS SHALL REFLECT CHANGES REQUIRED
 BY THESE COMMENTS. SECTION 104.2.1.
 13. SHT P4.0 GAS RISER DIAGRAM: THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 THE GAS PERMIT:
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 E. SUBMIT MANUF. SPECIFICATIONS SHEETS
 FOR REQUIRED 2LB TO 1/2 LB REGULATORS.
 F. SHOW THE LOCATION OF THE REGULATORS
 ON THE GAS RISER DIAGRAM. SECTION
 104.2.1.
 14. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQD BY SECTION 604.9 AND
 LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING PER
 PDI-WH 201). ECT. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-24 Cont ID  
Sent By mmclean Date 2006-01-24 Time 13:14 Rev Time 0.00
Received By mmclean Date 2006-01-24 Time 13:14 Sent To  
Notes
2006-01-24 00:00:00DENIED, RESUB
 1. MUST PROVIDE THE UNITY OF TITLE FOR
 THE PARCEL (PROPERTY).
 2. MUST PROVIDE A COMPLETE SITEPLAN OF
 THE PROPERTY, SHOWING THE ADDRESS AND
 SETBACKS OF EXISTING BUILDING.
 3. THE PROPOSED WORK MUST BE IDENTIFY ON
 THE SITEPLAN WITH SETBACKS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-08 Cont ID  
Sent By mmclean Date 2005-07-08 Time 11:56 Rev Time 0.00
Received By mmclean Date 2005-07-08 Time 11:56 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved