Plan Review Details - Permit 05061379
Plan Review Stops For Permit 05061379
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-02 Cont ID  
Sent By alange Date 2005-08-02 Time 10:54 Rev Time 0.25
Received By alange Date 2005-08-02 Time 10:54 Sent To  
Notes
2005-08-02 00:00:00PROCESSED, OK BY LUIS M.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-09-08 Cont ID  
Sent By dpalmer Date 2005-09-08 Time 08:31 Rev Time 0.40
Received By dpalmer Date 2005-09-08 Time 08:31 Sent To  
Notes
2005-09-08 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE APPLICATION VALUE
 NEEDS TO BE INCREASED FOR ALL LABOR AND
 MATERIALS. PLEASE SEE FBC 104.6.5 CITY
 WIDE ADMINSTRATIVE CODE.
 VALUE TO INCLUDE ALL LABOR AND MATERIALS
 EVEN IF OWNER SUPPLIED.
 THIS WOULD INCLUDE GENERATOR, ATS ETC.
 PLEASE SEE VALUE IS SHOWN AS $900 AND
 THE MIN OF UNIT ON SPECS SUBMITTED IS
 $3600.00
  
 2)NOTE: PLEASE PROVIDE RISER DIAGRAM
 WHICH IS TO SHOW INSTALLATION OF NEW
 EQUIPMENT INTO EXSITNG SERVICE.
 PLEASE PROVIDE, LOCATIONS OF EXISTING
 MAIN(S).
 PLEASE PROVIDE LOADS AND ITEMS INTENDED
 FOR CONNECTION INTO NEW PANEL.
 220.31,702.5, 215.5
  
 3)NOTE: PLEASE PROVIDE MEANS OF
 DSICONNECT GROUPED WITH EXISTING MAINS
 AS REQUIRED UDNER 225.31, 225.34. PLEASE
 BE SURE DISCONNECTING MEANS IS RATED AS
 "SERVICE EQUIPMENT". 225.36
  
 4)NOTE: PLEASE INDICATE ON SITE PLAN THE
 LOCATION AND DIMENSIONS FROM HOUSEAND
 ANY WINDOW/DOOR OR ATTIC OPEINGS. PLEASE
 SEE THIS IS A MECHANICAL CODE
 REQUIREMENT OF A MIN OF 10' FROM THE
 ABOVE LISTED OPENINGS TO A DWELLING
 UNIT.
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR TIE DOWN OF UNIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-27 Cont ID  
Sent By btrobaug Date 2005-07-27 Time 11:38 Rev Time 0.50
Received By btrobaug Date 2005-07-27 Time 11:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By btrobaug Date 2005-07-13 Time 13:42 Rev Time 0.33
Received By btrobaug Date 2005-07-13 Time 13:34 Sent To M
Notes
2005-07-13 00:00:00 
 PLANS AND SPECIFICATIONS FOR EQUIPMENT
 REQUIRED. ELECTRICAL CONTRACTOR SIGNED
 ON SO PLANS MUST BE PROVIDED WITH THIS
 APPLICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 10:14 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 10:14 Sent To E
Notes
2005-07-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By lmartine Date 2005-07-26 Time 10:04 Rev Time 0.00
Received By lmartine Date 2005-06-22 Time 16:11 Sent To  
Notes
2005-06-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-13 Cont ID  
Sent By rregueir Date 2005-07-13 Time 16:36 Rev Time 0.00
Received By rregueir Date 2005-07-13 Time 16:33 Sent To G
Notes
2005-07-13 00:00:00-----------------PROVISO----------------
 GENERATOR EXHAUST TERMINATION TO BE
 LOCATED MIN. 10' FROM OPENINGS INTO
 BUILDING STRUCTURE (DOORS,WINDOWS) AND
 IN COMPLIANCE WITH FBC,M 804.3
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-08-01 Cont ID  
Sent By jleech Date 2005-08-01 Time 10:54 Rev Time 0.25
Received By jleech Date 2005-08-01 Time 10:54 Sent To  
Notes
2005-08-01 00:00:00GAS PERMIT REQUIRED BE FORE FINAL
 INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-18 Cont ID  
Sent By jleech Date 2005-07-18 Time 09:43 Rev Time 0.33
Received By jleech Date 2005-07-18 Time 09:43 Sent To B
Notes
2005-07-18 00:00:00DENIED;
 GAS GENERATOR APPLICATION PACKAGE SHALL
 HAVE A GAS APPLICATION AND PLAN. NOT
 ENOUGH INFORMATION TO APPROVE RES-GEN
 APPLICATION.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-27 Cont ID  
Sent By mmclean Date 2005-07-27 Time 09:35 Rev Time 0.00
Received By mmclean Date 2005-07-27 Time 09:35 Sent To B
Notes
2005-07-27 00:00:00IN LUIS MARTINEZ OFFICE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By mmclean Date 2005-07-01 Time 14:18 Rev Time 0.00
Received By mmclean Date 2005-07-01 Time 14:18 Sent To I
Notes
2005-07-01 00:00:00DENIED,
 1. MUST PROVIDE THE DIMENSION OF
 GENERATOR (FROM STRUCTURE AND PROPERTY
 LINE).
 2. INFORMATION MUST BE PROVIDED ON TWO
 COPY OF SURVEY PROVIDING INFORMATION
 NEED TO REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720