| Plan Review Stops For Permit 05061379 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2005-08-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-08-02 |
Time |
10:54 |
Rev Time |
0.25 |
| Received By |
alange |
Date |
2005-08-02 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2005-08-02 00:00:00 | PROCESSED, OK BY LUIS M. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-09-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-08 |
Time |
08:31 |
Rev Time |
0.40 |
| Received By |
dpalmer |
Date |
2005-09-08 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2005-09-08 00:00:00 | ******* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE APPLICATION VALUE | | | NEEDS TO BE INCREASED FOR ALL LABOR AND | | | MATERIALS. PLEASE SEE FBC 104.6.5 CITY | | | WIDE ADMINSTRATIVE CODE. | | | VALUE TO INCLUDE ALL LABOR AND MATERIALS | | | EVEN IF OWNER SUPPLIED. | | | THIS WOULD INCLUDE GENERATOR, ATS ETC. | | | PLEASE SEE VALUE IS SHOWN AS $900 AND | | | THE MIN OF UNIT ON SPECS SUBMITTED IS | | | $3600.00 | | | | | | 2)NOTE: PLEASE PROVIDE RISER DIAGRAM | | | WHICH IS TO SHOW INSTALLATION OF NEW | | | EQUIPMENT INTO EXSITNG SERVICE. | | | PLEASE PROVIDE, LOCATIONS OF EXISTING | | | MAIN(S). | | | PLEASE PROVIDE LOADS AND ITEMS INTENDED | | | FOR CONNECTION INTO NEW PANEL. | | | 220.31,702.5, 215.5 | | | | | | 3)NOTE: PLEASE PROVIDE MEANS OF | | | DSICONNECT GROUPED WITH EXISTING MAINS | | | AS REQUIRED UDNER 225.31, 225.34. PLEASE | | | BE SURE DISCONNECTING MEANS IS RATED AS | | | "SERVICE EQUIPMENT". 225.36 | | | | | | 4)NOTE: PLEASE INDICATE ON SITE PLAN THE | | | LOCATION AND DIMENSIONS FROM HOUSEAND | | | ANY WINDOW/DOOR OR ATTIC OPEINGS. PLEASE | | | SEE THIS IS A MECHANICAL CODE | | | REQUIREMENT OF A MIN OF 10' FROM THE | | | ABOVE LISTED OPENINGS TO A DWELLING | | | UNIT. | | | | | | 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | FOR TIE DOWN OF UNIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-27 |
Time |
11:38 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-07-27 |
Time |
11:38 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-13 |
Time |
13:42 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-07-13 |
Time |
13:34 |
Sent To |
M |
|
| Notes |
| 2005-07-13 00:00:00 | | | | PLANS AND SPECIFICATIONS FOR EQUIPMENT | | | REQUIRED. ELECTRICAL CONTRACTOR SIGNED | | | ON SO PLANS MUST BE PROVIDED WITH THIS | | | APPLICATION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-07-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-05 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-05 |
Time |
10:14 |
Sent To |
E |
|
| Notes |
| 2005-07-05 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2005-07-26 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2005-06-22 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2005-06-22 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-07-13 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-07-13 |
Time |
16:33 |
Sent To |
G |
|
| Notes |
| 2005-07-13 00:00:00 | -----------------PROVISO---------------- | | | GENERATOR EXHAUST TERMINATION TO BE | | | LOCATED MIN. 10' FROM OPENINGS INTO | | | BUILDING STRUCTURE (DOORS,WINDOWS) AND | | | IN COMPLIANCE WITH FBC,M 804.3 | | | | | | RONALD J REGUEIRO | | | 561-805-6734 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-08-01 |
Time |
10:54 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2005-08-01 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2005-08-01 00:00:00 | GAS PERMIT REQUIRED BE FORE FINAL | | | INSPECTION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-07-18 |
Time |
09:43 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-07-18 |
Time |
09:43 |
Sent To |
B |
|
| Notes |
| 2005-07-18 00:00:00 | DENIED; | | | GAS GENERATOR APPLICATION PACKAGE SHALL | | | HAVE A GAS APPLICATION AND PLAN. NOT | | | ENOUGH INFORMATION TO APPROVE RES-GEN | | | APPLICATION. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-07-27 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-07-27 |
Time |
09:35 |
Sent To |
B |
|
| Notes |
| 2005-07-27 00:00:00 | IN LUIS MARTINEZ OFFICE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-01 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-07-01 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-07-01 |
Time |
14:18 |
Sent To |
I |
|
| Notes |
| 2005-07-01 00:00:00 | DENIED, | | | 1. MUST PROVIDE THE DIMENSION OF | | | GENERATOR (FROM STRUCTURE AND PROPERTY | | | LINE). | | | 2. INFORMATION MUST BE PROVIDED ON TWO | | | COPY OF SURVEY PROVIDING INFORMATION | | | NEED TO REVIEW. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|