Plan Review Details - Permit 05061374
Plan Review Stops For Permit 05061374
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-10 Cont ID  
Sent By jwitmer Date 2006-02-10 Time 11:53 Rev Time 1.11
Received By jwitmer Date 2006-02-10 Time 11:53 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-30 Cont ID  
Sent By jwitmer Date 2006-01-30 Time 12:58 Rev Time 1.11
Received By jwitmer Date 2006-01-30 Time 12:47 Sent To  
Notes
2006-01-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061374
 ADD: 900 S OLIVE
 CONT: PURDY CONST
 TEL: (561)718-8082
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1)COMMENT# 1 FROM THE PREVIOUS REVIEW,
 PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE WHEN WORK HAS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING NOC IT IS NULL AND
 VOID.FAC 713.13.(2).
  
 2) COMMENT#2 FROM THE PREVIOUS REVIEW:
 DELT WITH THE BUILDING CLASSIFICATION,
 PLANS NOW INDICATEW A TYPE II-A WHICH IS
 A 2004 CLASSIFICATION, THIS PLAN IS A
 2001 PLAN.RE-CLASSIFY TO THE 2001 FBC.
  
 3A)COMMENT # 4 FROM THE PREVIOUS REVIEW,
 DEPENDING ON THE RESULTS OF QUESTION
 NUMBER TWO DETAIL #2 ON S-2 MAY OR MAY
 NOT HAVE COMBUSTIBLE WALLS & ROOF
 FRAMING MEMBERS & SHEATHING. TABLE 600.
 EXTERIOR BEARING WALLS ARE TO BE
 NON-COMBUSTIBLEAND A 3HR FIRE RATING.
 THE ROOF FRAMING IS TO BE FIRE RETARDANT
 TREATED WOOD WHEN THE BUILDING IS NOT
 OVER 2 STORIES WITH A 1 HR FIRE RATING,
 PLANS DO NOT INDICATE COMPLIANCE WITH
 FIRE RATING.
  
 4) COMMENT# 5FROM THE PEVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) COMMENT# 6FROM THE PREVIOUS REVIEW,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOFING ASSEMBLIES
 B) TRUSS STRAPS
 C) EXTERIOR COOLER IF PART OF THIS
 PERMIT!!!!!!!
  
 6) COMMENT# 7 FROM THE PREVIOUS REVIEW,
 STAIRS TO HAVE A HANDRAIL BOTH SIDES
 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
 THE ARCHETECTURAL AND STRUCTURAL PLANS
 NEED TO MATCH. THE A SHEETS INDICATE 4
 RISERS WHILE THE STRUCTURAL INDICATE 5
 RISERS 5X7"= 35" REQUIRING GUARDRAILS
 AND HANDRAILS.
 7) COMMENT# 8 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-18 Cont ID  
Sent By jwitmer Date 2005-11-18 Time 16:36 Rev Time 1.33
Received By lmartine Date 2005-11-18 Time 15:28 Sent To Z
Notes
2005-11-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061374
 ADD: 900 S OLIVE
 CONT: PURDY CONST
 TEL: (561)718-8082
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT#2 FROM THE PREVIOUS REVIEW:
 PLANS DO NOT PROVIDE THE BUILDING
 CLASSIFICATION BY TYPE OF CONSTRUCTION.
  
 3)COMMENT # 4 FROM THE PREVIOUS REVIEW,
 DEPENDING ON THE RESULTS OF QUESTION
 NUMBER TWO DETAIL #2 ON S-2 MAY OR MAY
 NOT HAVE COMBUSTIBLE WALLS & ROOF
 FRAMING MEMBERS & SHEATHING. TABLE 600.
 WHY DOES THE PLYWOOD STOP SHORT OF THE
 TOP PLATE?IF LEFT THIS WAY
 FIREBLOCKING REQUIRED AT THE TOP OF
 PLYWOOD.
  
 4) COMMENT# 5FROM THE PEVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) COMMENT# 6FROM THE PREVIOUS REVIEW,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOFING ASSEMBLIES
 B) TRUSS STRAPS
  
 6) COMMENT# 7 FROM THE PREVIOUS REVIEW,
 STAIRS TO HAVE A HANDRAIL BOTH SIDES
 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
  
 7) COMMENT# 8 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 14:02 Rev Time 1.11
Received By jwitmer Date 2005-07-24 Time 14:02 Sent To PC
Notes
2005-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061374
 ADD: 900 S OLIVE
 CONT: PURDY CONST
 TEL: (561)718-8082
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS DO NOT PROVIDE THE BUILDING
 CLASSIFICATION BY TYPE OF CONSTRUCTION.
  
 3) PLANS INDICATE A LANDING THAT HAS THE
 LANDING DECREASED BY A EXISTING
 CONCREETE CURB. 1007.4.2THE WIDTH OF
 LANDINGS SHALL BE NOT LESS
 THAN THE WIDTH OF STAIRWAYS THEY
 SERVE.
  
 4) DEPENDING ON THE RESULTS OF QUESTION
 NUMBER TWO DETAIL #2 ON S-2 MAY OR MAY
 NOT HAVE COMBUSTIBLE WALLS & ROOF
 FRAMING MEMBERS & SHEATHING. TABLE 600.
 WHY DOES THE PLYWOOD STOP SHORT OF THE
 TPO PLATE?IF LEFT THIS WAY
 FIREBLOCKING REQUIRED AT THE TOP OF
 PLYWOOD.
  
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOFING ASSEMBLIES
 B) TRUSS STRAPS
  
 7) STAIRS TO HAVE A HANDRAIL BOTH SIDES
 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-12-18 Cont ID  
Sent By dpalmer Date 2006-12-18 Time 18:00 Rev Time 0.00
Received By dpalmer Date 2006-12-18 Time 18:00 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-12-05 Cont ID  
Sent By dpalmer Date 2006-12-05 Time 15:46 Rev Time 0.00
Received By dpalmer Date 2006-12-05 Time 15:10 Sent To PC
Notes
2006-12-05 15:37:34*** UNSAT ***
  
 1) NOTE: PLEASE KNOW WHEN SUBMITTING REVISIONS ON PLANS
 WHICH WERE ORIGINALLY DONE UNDER A BUILDING PERMIT
 NUMBER; PLEASE BE SURE WHEN SUBMITTING THE REVISIONS TO
 INDICATE # 05061374
  
 2) NOTE: PLEASE 250.50, THE GROUNDING ELECTRODE
 ATTACHMENT SHOULD BE MORE THAN THE CWP, AS THIS
 BUILDING WOULD HAVE OTHER REQUIRED ATTACHMENT POINTS.
 PLEASE KNOW IF THE CWP AT THE LOCATION OF THE
 TRANSFORMER CONTAIN CPVC ANYWHERE IN THE SYSTEM BEFORE
 IT ACTUALLY ORIGINATES, THEN THE ATTACHMENT WOULD NOT
 PROVIDE A SUFFICIENT RESISTANCE OR BE PART OF THE
 BUILDING?S SYSTEM.
  
 3) NOTE: PLEASE SEE PANEL KPR SEEMS TO INDICATE THE
 TRANSFORMER KVA SIZE AS 15K, WHERE AS THE RISER SHOWS
 50.
 PLEASE KNOW THIS PART CAN NOT BE REVIEWED FOR THE
 CORRECT OCP ETC WITH OUT FIRST KNOWING WHICH SIZE IS
 ACCURATE.
 PLEASE SEE THE LOAD IS BEING SHOWN HIGHER THAN THAT OF
 A 15KVA UNIT.
 240.21, 450.3, 310.16, 240.4, ETC.
  
 4) NOTE: PLEASE KNOW, BASED ON THE COMMENT #3, THE
 LOADS BACK TO PANEL PP1 HAVE NOT BEEN IDENTIFIED BASED
 ON THE OCP AND FEED TO THE EXISTING PANEL KPR.
 220
  
 5) NOTE: PLEASE KNOW WHEN PLANS ARE NOT DONE BY AN
 ARCHITECT OR ENGINEER AND DONE BY THE CONTRACTOR, THE
 PERSON TAKING RESPONSIBILITY OF THE PLANS SHALL CLEARLY
 PRINT AND SIGN THEIR NAME.
 FBC106.1.2 ADMIN SECTION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 14:52 Rev Time 0.00
Received By dpalmer Date 2006-10-24 Time 14:52 Sent To PC
Notes
2006-10-24 15:03:29***UNSAT **
  
 1) NOTE: PLEASE SEE NEW SCOPE OF WORK AND RISER
 INCLUDES NEW WORK FOR 277/480V WHICH IS REQUIRED TO BE
 DONE BY A PE.
 PLEASE SEE FS 471.003(2)(H)2A)
  
 2) NOTE: PLEASE SEE LOCATION OF THE NEW GROUNDIGN
 ELECTRODE SYSTEM FORTHE NEW SD SYSTEM IS NOT SHOWN.
 ATTACHMENT ETC. 250.66, 250.50,250.30,250.20
  
 3) NOTE: PLEASE SEE RISER SHOWS A NUETRAL CONDUCTOR
 BEING INSTALLED TO THE SD SYSTEM???
  
 4) NOTE: PLEASE SEE NO OCP SHOWN FOR NEW FEED FROM
 EXISTING KPR? 450.3. ,
 SHOWS 3KVA TRANSFORMER?
  
 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR ALL
 INCREASED AND ADDED LOADS.
  
 THESE NOTES ARE PRELIMINARYBASED ON THE RISER
 SUIBMITTED, HOWEVER ONCE PLANS SUBMITTED DONE BY AN PE,
 A REVIEW WILL COMMENCE ON THOSE SAID PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-10-24 14:54:13REVISION RECEIVED FROM FRONT COUNTER SUPREVISOR ON
 10/23/06 AS THIS WAS SUBMITTED IN ERROR UNDER THE WRONG
 PERMIT NUMBER. (06082172)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2005-11-10 Time 20:19 Sent To  
Notes
2005-11-10 00:00:00OK, STAMPED.
 REDLINED MISSING EQUIPMENT GROUNDING
 CONDUCTOR TO NEW SUB-PANEL.
 VIF.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By dpalmer Date 2005-07-14 Time 20:00 Rev Time 0.00
Received By jwitmer Date 2005-11-18 Time 15:28 Sent To  
Notes
2005-07-14 00:00:00** UNSAT **
  
 PLEASE SEE THE PLANS ARE COMNING BACK
 DUE TO ZONING COMMENTS. PLEASE MAKE THE
 BELOW CORRECTIONS AT THIS TIME.
  
 1)NOTE: PLEASE SHOW LOAD FOR EXISTING
 PANEL "LG". PLEASE SEE PLANS MENTIONS TO
 REMOVE A COOLER/FREEZER CIRCUIT AND
 INSTALL NEW 50A BRKR FOR NEWSUB-PANEL,
 HOWEVER WHAT SIZE WAS EXISTING BRKR? WAS
 THERE AN INCREASE IN LOAD?
 220,215.5
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM EXISTING PANEL
 TO NEW SUB PANEL.
 250.110,250.24,250.122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-01-20 Cont ID  
Sent By mwennerg Date 2006-01-20 Time 15:28 Rev Time 0.00
Received By mwennerg Date 2006-01-20 Time 15:28 Sent To  
Notes
2006-01-20 00:00:00******PROVISO******
  
 IN REFERENCE TO HANDRAILS, PLEASE REFER
 TO NFPA 101, 2003 EDITION SEC.
 7.2.2.4.1.1.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-11-15 Cont ID  
Sent By nmccray Date 2005-11-15 Time 15:06 Rev Time 0.00
Received By nmccray Date 2005-11-15 Time 14:57 Sent To  
Notes
2005-11-15 00:00:00DENIED
  
 1) PLEASE PROVIDE STAIRS DETAIL OR SHOW
 THE HANDRAILS AND GUARDS ON THE FLOOR
 PLAN.
  
 2) AGAIN WILL THE NEW WALK-IN COOLER
 IMPACT EXISTING MEANS OF EGRESS?
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By mwennerg Date 2005-07-20 Time 14:24 Rev Time 0.00
Received By mwennerg Date 2005-07-20 Time 14:24 Sent To  
Notes
2005-07-20 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT APPROVAL HAS NOT
 BEEN OBTAINED BY ZONING.
  
 2) HANDRAILS ARE REQUIRED ON BOTH SIDES
 OF STAIRS. GUARDS SHALL BE PROVIDED AT
 OPEN SIDES OF STAIRS IF GREATER THAN 30"
 FROM GRADE LEVEL.
  
 3) WILL THE NEW WALK IN COOLER IMPACT
 EXISTING MEANS OF EGRESS?
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 17:02 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 17:02 Sent To E
Notes
2006-12-16 17:03:01TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 17:52 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 17:52 Sent To E
Notes
2006-11-29 17:52:45REVISION/TO DPALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-15 Cont ID  
Sent By adarroug Date 2005-12-15 Time 17:26 Rev Time 0.00
Received By adarroug Date 2005-12-15 Time 17:26 Sent To  
Notes
2006-01-17 00:00:00TO "COMM" BD#50
2005-12-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-07 Cont ID  
Sent By adarroug Date 2005-10-07 Time 08:47 Rev Time 0.00
Received By adarroug Date 2005-10-07 Time 08:47 Sent To  
Notes
2005-10-20 00:00:00TO "COMM" BD#20
2005-10-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 14:02 Rev Time 0.00
Received By jwitmer Date 2005-06-22 Time 13:04 Sent To  
Notes
2005-06-27 00:00:00TO "COMM" BD#49
2005-06-22 00:00:00WAITING FOR SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By pkrauss Date 2005-07-20 Time 10:04 Rev Time 0.25
Received By pkrauss Date 2005-07-20 Time 10:04 Sent To  
Notes
2005-07-20 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIRED FOR WALK-IN
 COOLER.PLEASE PROVIDE MANUFACTURER'S
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 PLEASE NOTE, WALK-IN COOLER CANNOT BE
 INSTALLED PRIOR TO ZONING APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 14:02 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-11-23 Time   Rev Time 0.00
Received By   Date 2005-11-22 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By lshapiro Date 2005-07-14 Time 13:08 Rev Time 0.00
Received By lshapiro Date 2005-07-14 Time 13:09 Sent To  
Notes
2005-07-14 00:00:00A SITE PLAN HAS NOT BEEN SUBMITTED
 REFLECTING THE EXPANSION.A MINOR
 AMENDMENT IS REQUIRED.
 PURDY CONSTRUCTION WAS CONTACTED ON
 07/14/05 AND TOLD A MINOR AMENDMENT IS
 NEEDED.