| Plan Review Stops For Permit 05061360 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-11-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-09 |
Time |
15:45 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-11-09 |
Time |
15:45 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-10-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-10-07 |
Time |
14:50 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-10-06 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2005-10-07 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | **NOTE - NEW PLANS SUBMITTED** | | | | | | 1.)FBC104.2.1, INFORMATION ON THE | | | DRAWINGS IS TO BE SPECIFIC.GENERAL | | | NOTES 3 AND 6, SHEET A-1.0, SHOULD GIVE | | | SPECIFIC DESIGN CRITERIA.HANDRAILS AND | | | GUARDRAILS ARE TO COMPLY WITH | | | FBC1608.2.1 AND 1608.2.2 RESPECTIVELY. | | | | | | 2.)PLEASE PROVIDE AN ORIGINAL SOILS | | | REPORT.DOCUMENTS PREPARED BY AN | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD | | | ARE TO BE SIGNED, SEALED AND DATED | | | ORIGINALS.CERTIFICATE OF | | | AUTHORIZATION REQUIRED ON THE DOCUMENT. | | | FAC61G15-23.002. | | | | | | 3.)A-2.0, WEST DECK PLAN, STATES "NEW | | | WOOD RAMP AND RAILING SEE DETAIL." | | | DETAIL NOT PROVIDED.PROVIDE A DETAIL | | | SHOWING GUARDRAIL AND HANDRAIL IN | | | COMPLIANCE WITH FBC11-4.8.5 AND | | | FBC11-4.9.4. | | | | | | 4.)SHOW RAMP WIDTH, FBC11-4.8.3. | | | | | | 5.)IF THE RAMP CHANGES DIRECTION AT | | | LANDINGS, THE MINIMUM LANDING SIZE SHALL | | | BE 60IN X 60IN. | | | | | | 6.)WHAT IS THE PAVER AT THE EAST DECK | | | TO BE USED FOR?SEE FBC11-4.1.2(1). | | | SHOW ACCESSIBLE ROUTE. | | | | | | 7.)PROVIDE A DETAIL FOR THE STAIR | | | HANDRAIL WHICH SHOWS THE BOTTOM | | | EXTENSION, FBC11-4.9.4, FIGURE 19. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-19 |
Time |
18:57 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2005-07-19 |
Time |
15:00 |
Sent To |
FIRE |
|
| Notes |
| 2005-07-19 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PROVIDE STRUCTURAL INFORMATION | | | REGARDING THE TRAILER TO COMPLY WITH | | | FBC*104.3.1.1, FBC1606.PROVIDE WALL | | | SECTIONS, CONTINUOUS FROM THE FOUNDATION | | | THROUGH THE ROOF.ALSO PROVIDE TOTAL | | | SQUARE FEET. | | | | | | 2.)PROVIDE WIND DESIGN INFORMATION | | | FBC1606.1.7. | | | | | | 3.)FBC1604.1, SPECIFY FLOOR LOADING | | | INFORMATION. | | | | | | 4.)WALL SECTION 2-A3.0 STATES ?TO | | | BRACE BACK TO TRAILER?.PROVIDE A | | | DETAIL. | | | | | | 5.)SPECIFY HURRICANE STRAPPING.SOME | | | DETAILS DO NOT SHOW STRAPS, ANOTHER | | | (6-A4.0) DOES NOT SPECIFY WHICH STRAP TO | | | USE. | | | | | | 6.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC FBC13-101.2.PLEASE CONFIRM | | | THAT THE ENERGY CALC SQUARE FOOTAGE | | | MATCHES THE PLAN PRIOR TO RESUBMITTAL. | | | | | | 7.)PROVIDE A HURRICANE SHUTTER | | | INSTALLATION SCHEDULE, SEE ATTACHED. | | | | | | 8.)PROVIDE PRODUCT APPROVALS FOR: | | | | | | WINDOWS | | | DOORS | | | ROOF | | | IMPACT PROTECTION | | | | | | 9.)PROVIDE A SOILS INVESTIGATION | | | REPORT. | | | | | | 10.)SHOW THE ACCESSIBLE ROUTE FROM THE | | | PUBLIC WAY, FBC11-4.3.2(1). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-07-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-18 |
Time |
17:49 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-07-18 |
Time |
17:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2005-09-22 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-09-22 |
Time |
11:10 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-09-22 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2005-09-22 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. PRIOR TO ANY CONNECTION TO THE | | | CITY' SERVICES (WATER AND SEWER), MUST | | | SUBMIT, CIVIL PLANS ONLY TO PUBLIC | | | UTILITIES AND ENGINEERING ATT; MANNY | | | GONZALEZ, 494-1085 | | | 2. NOTE THAT A SEPARATE PERMIT FROM | | | PALM BEACH COUNTY HEALTH DEPARTMENT FOR | | | THE PROPOSED 300 GAL. HOLDING TANK IS | | | REQUIRED, SUBMIT A COPY TO THE PUBLIC | | | UTILITIES AND ENGINEERING, ATT; MANNY | | | GONZALEZ 494-1085. | | | 3. POLLUTION / EROSION COTROL DEVICES | | | MUST BE IN PLACED PRIOR TO DO ANY | | | CONSTRUCTION ACTIVITIES, SILT FENCE, | | | ETC.. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-11-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-11-18 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-11-18 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2005-11-18 00:00:00 | ******PROVISO****** | | | | | | WATER SUPPLY SHALL BE SECURED EITHER BY | | | FIRE HYDRANT OR TANKER PRIOR TO | | | CONSTRUCTION. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-10-12 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-10-12 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-10-12 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2005-10-12 00:00:00 | DENIED: | | | | | | 1) MUST PROVIDE TEMPORARY WATER SUPPLY | | | (I.E. WATER TANKER ) FOR FIRE PROTECTION | | | TO THE SALES TRAILER UNTIL FIRE HYDRANTS | | | ARE INSTALLED. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-20 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-20 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | ******DENIED****** | | | | | | 1) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) AN ADDRESS IS REQUIRED ON THE | | | BUILDING, AND MUST BE AT LEAST 6" IN | | | HEIGHT AND CONTRASTING WITH THE | | | BACKGROUND. | | | | | | 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR GUARDS AND HANDRAILS. | | | | | | 4) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 5) PLEASE INDICATE LOCATION AND DISTANCE | | | FROM PROJECT TO NEAREST FIRE HYDRANT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-30 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-30 |
Time |
15:10 |
Sent To |
Z |
|
| Notes |
| 2005-11-30 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-11-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-18 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-18 |
Time |
14:04 |
Sent To |
FIRE |
|
| Notes |
| 2005-11-18 00:00:00 | TO "MWENNEGREN" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-11-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-10 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-10 |
Time |
16:28 |
Sent To |
Z |
|
| Notes |
| 2005-11-10 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-09-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-09 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-23 |
Time |
14:24 |
Sent To |
B |
|
| Notes |
| 2005-09-23 00:00:00 | TO "SHILL" DESK/RESUB-FOUNDATION PLANS | | | ONLY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-19 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-19 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2005-09-20 00:00:00 | TO "COMM" BD#47 | | 2005-09-19 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-20 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-22 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | TO "LMARTINEZ" DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-07-15 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-07-15 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-07-15 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2005-07-15 00:00:00 | PASS PRIVISO | | | PLEASE REFER TO SECTION 606.2.1 FBC(M) | | | SUPPLY AIR SYSTEM SMOKE DETECTOR AND | | | SECTION 606.4.1 SUPERVISION SMOKE | | | DETECTORS | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-11-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-11-10 |
Time |
13:47 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-11-10 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2005-11-10 00:00:00 | IRRIGATION PERMIT REQUIRED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-10-17 |
Time |
15:47 |
Rev Time |
0.62 |
| Received By |
kstevens |
Date |
2005-10-17 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2005-10-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FBC-2001 FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: | | | 2. SHT A-1.0 INDICATES A SANITARY | | | HOLDING TANK. A PERMIT FROM THE COUNTY | | | HEALTH DEPT. IS REQUIRED FOR THE HOLDING | | | TANK. PLEASE CONTACT FRANK LOMBARDO | | | (561) 233-5139. PERMIT SHALL BE | | | SUBMITTED WITH PLANS WHEN RESUBMITTING | | | FOR REVIEW FOR PERMIT. SECTION 104.7.1 - | | | PERMIT FOR HOLDING TANK NOT SUBMITTED | | | 3. SHT A-2.0 SHOW THE CLEAR FLOOR SPACE | | | FOR THE FOLLOWING: | | | A. 11-4.15.5 WATER COOLER | | | B. 11-4.16.2 WATER CLOSETS | | | C. 11-4.19.3 LAVS | | | RESPONSE NOTED BUT NEW TOILET ROOMS | | | SHALL MEET CODE REQUIREMENTS. | | | 4. SHT A-3.0 RESTROOM DETAILS - SHOW THE | | | FOLLOWING: | | | (FOR W/C'S) | | | A. 11-4.16.5 FLUSH CONTROLS | | | B. 11-4.16.6 DISPENSERS | | | (FOR LAVS) | | | A. 11-4.19.4 EXPOSED PIPES & SURFACES | | | B. 11-4.19.5 FAUCETS | | | RESPONSE NOTED BUT NEW TOILET ROOMS | | | SHALL MEET CODE REQUIREMENTS. | | | 5. WATER COOLER SHALL BE ARI-1010 | | | COMPLIANT. SUBMIT MANUF. SPECIFICATION | | | SHEETS. - RESPONSE NOTED, BUT | | | SPECIFICATION SHEETS WERE NOT FOUND. | | | 6. SHT M-2 WATER RISER DIAGRAM. AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | RISER. SECTION 604.9. - THERMAL | | | EXPANSION CONTROL IS REQUIRED. SECTION | | | 607.3.2. SHOW HOW THIS IS BEING | | | ADDRESSED. - RESPONSE NOTED, BUT CODE | | | REQUIREMENTS SHALL BE MET. | | | 7. SEPARATE IRRIGATION PLANS & PERMIT IS | | | REQUIRED. SECTION 104.3.1.1. - RESPONSE | | | NOTED, BUT IRRIGATION PLANS WERE NOT | | | LOCATED. | | | **************NEW COMMENTS************** | | | 1B. SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS 553.80(2)(B). | | | THIS IS A NOTICE ONLY. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-16 |
Time |
06:20 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-07-16 |
Time |
06:20 |
Sent To |
B |
|
| Notes |
| 2005-07-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1. SHT A-1.0 AN RPZ BACKFLOW IS REQUIRED | | | ON THE WATER SERVICE FOR THE TRAILERS. | | | SHOW WATER SERVICE AND BACKFLOW ON | | | PLANS. | | | 2. SHT A-1.0 INDICATES A SANITARY | | | HOLDING TANK. A PERMIT FROM THE COUNTY | | | HEALTH DEPT. IS REQUIRED FOR THE HOLDING | | | TANK. PLEASE CONTACT FRANK LOMBARDO | | | (561) 233-5139. PERMIT SHALL BE | | | SUBMITTED WITH PLANS WHEN RESUBMITTING | | | FOR REVIEW FOR PERMIT. SECTION 104.7.1 | | | 3. SHT A-2.0 SHOW THE CLEAR FLOOR SPACE | | | FOR THE FOLLOWING: | | | A. 11-4.15.5 WATER COOLER | | | B. 11-4.16.2 WATER CLOSETS | | | C. 11-4.19.3 LAVS | | | 4. SHT A-3.0 RESTROOM DETAILS - SHOW THE | | | FOLLOWING: | | | (FOR W/C'S) | | | A. 11-4.16.5 FLUSH CONTROLS | | | B. 11-4.16.6 DISPENSERS | | | (FOR LAVS) | | | A. 11-4.19.4 EXPOSED PIPES & SURFACES | | | B. 11-4.19.5 FAUCETS | | | 5. WATER COOLER SHALL BE ARI-1010 | | | COMPLIANT. SUBMIT MANUF. SPECIFICATION | | | SHEETS. | | | 6. SHT M-2 WATER RISER DIAGRAM. AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | RISER. SECTION 604.9. - THERMAL | | | EXPANSION CONTROL IS REQUIRED. SECTION | | | 607.3.2. SHOW HOW THIS IS BEING | | | ADDRESSED. | | | 7. SEPARATE IRRIGATION PLANS & PERMIT IS | | | REQUIRED. SECTION 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2005-11-30 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2005-11-30 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2005-11-30 00:00:00 | PER ERIC SCHNEIDER |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2005-11-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2005-11-17 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2005-11-17 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2005-11-17 00:00:00 | 1) ZONING CODE REQUIRES A 20 FOOT WIDE | | | LANDSCAPED AREA TO BE MAINTAINED BETWEEN | | | TEMPORARY SALES OFFICES AND ADJACENT | | | REZIDENTIALLY ZONED PROPERTIES.PLANS | | | SHOW ONLY 13 FEET BETWEEN THE PROPOSED | | | TRAILER AND THE PROPERTY LINE TO THE | | | SOUTH.SECTION 94-273(D)(73)B.8 | | | 2) IS THE PORCH ON THE REAR OF THE | | | BUILDING COVERED OR UNCOVERED?IF | | | COVERED IT MAY NOT ENCROACH INTO THE 20 | | | FOOT LANDSCAPE AREA. | | | 3) ZONING CODE REQUIRES THAT DRIVE | | | AISLES BE 24 FEET WIDE AT LOCATIONS | | | WHERE 2-WAY TRAFFIC IS ADJACENT TO | | | PARKING SPACES.SECTION 94-485(J)(2) | | | 4)THE LANDSCAPE PLAN INCORRECTLY LISTS | | | THE DIMENSIONS OF THE DRIVE AISLE AT | | | 1'9" WIDE AND THE DISABLED PARKING | | | SPACES AS 1'0" WIDE.CHECK ALL | | | DIMENSION LINES. | | | 5) 30% FOUNDATION PLANTING IS REQUIRED. | | | 6) REQUIRED SHADE TREES AND HEDGE NOT | | | SHOWN IN THE SOUTHERN LANDSCAPE BUFFER. | | | 7) VERIFY THAT THE PERCENTAGE OF | | | SHADES/PALMS FOR THE REQUIRED TREES | | | MEETS CODE. | | | CONTACT ERIC SCHNEIDER (561) 822-1435. | | | 8) SETBACKS ON SITE PLAN INCORRECT. | | | GIVEN TO INCOMING MM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-10-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2005-10-18 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2005-10-18 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2005-10-18 00:00:00 | 1) SITE, LANDSCAPE AND CIVIL PLANS DO | | | NOT MATCH. | | | 2) LANDSCAPE PLAN SHALL SHOW HOW THE | | | REQUIRED 20 FOOT LANDSCAPE BUFFER | | | BETWEEN THE BUILDING AND PARKING AND THE | | | ADJACENT RESIDENTIAL ZONED PROPERTIES IS | | | MET. | | | | | | CONTACT ERIC SCHNEIDER @ 822-1435. |
|
|