Plan Review Details - Permit 05061347
Plan Review Stops For Permit 05061347
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-08-03 Cont ID  
Sent By rmcdouga Date 2005-08-03 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2005-08-03 Time 15:44 Sent To  
Notes
2005-08-03 00:00:00REVISED ROOF COVER FOR FLAT DECK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-03 Cont ID  
Sent By rmcdouga Date 2005-08-03 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2005-08-03 Time 14:25 Sent To  
Notes
2005-08-03 00:00:00REVISION TO CHANGE ROOF COVERING ON FLAT
 DECK IS DENIED.
  
 1) MAXIMUM UPLIFT PRESSURE OF -45PSF
 DOES NOT MEET REQUIREMENT FOR STRUCTURE
 OF -89 PSF IN THE CORNERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-22 Cont ID  
Sent By lsmith Date 2005-06-22 Time 11:23 Rev Time 1.00
Received By lsmith Date 2005-06-22 Time 11:23 Sent To  
Notes
2005-06-22 00:00:00BUILDING PLAN REVIEW:
  
 NOTE: THE CONTRACTOR ENRIQUE IS A
 QUALIFIED APPLICATOR WITH POLYFOAM.
 VERIFIED BY PHONE LS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By lsmith Date 2005-06-21 Time 13:31 Rev Time 0.50
Received By lsmith Date 2005-06-21 Time 13:31 Sent To  
Notes
2005-06-21 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 SUBMIT FLORIDA PRODUCT APPROVALS FOR THE
 FOLLOWING:
 1. TWO COMPONENT POLYURETHENE FOAM
 ADHESIVE
 2. GAF RUBEROID MODIFIED BITUMEN ROOF
 SYSTEMS FOR WOOD DECKS
 3. ARGUEY "S" CLAY TILE.
  
 2. ON THE NOA FOR THE FLAT ROOF PAGES
 2-8 CIRCLE THE PRODUCTS TO BE USED IN
 THE ROOF APPLICATION.
 3. ON PAGE 26-7 CIRCLE THE TYPE OF BASE
 SHEET & FASTENING OPTIONS.
 4. WHAT IS THE DESIGN PRESSURE? CIRCLE
 THE FASTENING OPTIION TO BE USED.
 5. PLY SHEET: ARE YOU USING ANY OF THE
 PRODUCTS SHOWING?
 6. MEMBRANE: DESCRIBE THE MEMBRANE TO BE
 USED.
 7. SURFACING: CIRCLE IF BEING USED.
 8. PAGE 32: SEE NOTE #7 FOR DESIGN
 PRESSURE ATTACHMENTS.
 9. PAGE 32: WOOD DECK LIMITATIONS:
 CIRCLE IF REQUIRED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713
 5.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-06-21 Cont ID  
Sent By lsmith Date 2005-06-21 Time 13:32 Rev Time 0.00
Received By lsmith Date 2005-06-21 Time 13:31 Sent To  
Notes
2005-06-21 00:00:00OK PER F MITNER NO FEE 6-21-05