Plan Review Details - Permit 05061345
Plan Review Stops For Permit 05061345
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-07-24 Cont ID  
Sent By shill Date 2005-07-24 Time 14:49 Rev Time 0.50
Received By shill Date 2005-07-24 Time 14:42 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 19:57 Rev Time 0.25
Received By dpalmer Date 2005-07-01 Time 19:55 Sent To  
Notes
2005-07-01 00:00:00**** REDLINED NOTE*****
  
 PLEASE SEE 700.12E FOR WIRING OF EM/EXT
 LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By mamini Date 2005-07-06 Time 11:15 Rev Time 0.50
Received By mamini Date 2005-07-06 Time 11:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 13:27 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 13:26 Sent To  
Notes
2005-07-11 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED DAILY FROM
 THE SITE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 10:11 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 10:11 Sent To P
Notes
2005-12-16 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-11 Cont ID  
Sent By adarroug Date 2005-08-11 Time 18:19 Rev Time 0.00
Received By adarroug Date 2005-08-11 Time 18:19 Sent To P
Notes
2005-08-11 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-24 Cont ID  
Sent By shill Date 2005-07-24 Time 14:52 Rev Time 0.00
Received By shill Date 2005-06-23 Time 14:42 Sent To  
Notes
2005-06-30 00:00:00TO "COMM" BD#22
2005-06-23 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By pkrauss Date 2005-07-20 Time 13:42 Rev Time 0.35
Received By pkrauss Date 2005-07-20 Time 13:31 Sent To  
Notes
2005-07-20 00:00:00MECHANICAL CONTRACTOR OR WORK NOT
 INDICATED WITH PERMIT APPLICATION.
 PLEASE NOTE, MECHANICAL EXHAUST REQUIRED
 FROM THE BATHROOM AREA PER 2001 FBC(M)
 TABLE 403.3, 50 CFM PER WATER CLOSET OR
 URINAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-24 Cont ID  
Sent By jleech Date 2006-01-24 Time 08:40 Rev Time 1.00
Received By jleech Date 2006-01-24 Time 08:40 Sent To  
Notes
2006-01-24 00:00:00REVISED SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By jleech Date 2005-08-22 Time 10:11 Rev Time 1.00
Received By jleech Date 2005-08-22 Time 10:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By kstevens Date 2005-07-15 Time 10:56 Rev Time 1.75
Received By kstevens Date 2005-07-14 Time 14:32 Sent To  
Notes
2005-07-15 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM. SHOW ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. SECTION
 104.3.1.1. LOCATION OF WATER HAMMER
 ARRESTORS SHALL BE NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING
 IF PROVIDED. PDI-WH 201.
 2. SHT A1 INDICATE IF WATER WILL BE
 SUPPLIED TO THE BEVERAGE BAR. IS SO, A
 WATER RISER DIAGRAM WILL BE REQUIRED FOR
 THAT AREA ALSO. SECTION 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-14 Cont ID  
Sent By mmclean Date 2005-07-14 Time 09:48 Rev Time 0.00
Received By mmclean Date 2005-07-14 Time 09:48 Sent To  
Notes
2005-07-14 00:00:00PARKING MUST BE DOUBLE STRIPPED.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-08 Cont ID  
Sent By mmclean Date 2005-07-08 Time 12:48 Rev Time 0.00
Received By mmclean Date 2005-07-08 Time 12:48 Sent To  
Notes
2005-07-08 00:00:00DENIED,
 1. NEED TO APPLY FOR A MINOR AMENDMENT
 WITH THE PLANNING DEPT. 822-1435


Account Summary | Usage Policy | Privacy Policy