Plan Review Details - Permit 05061297
Plan Review Stops For Permit 05061297
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-16 Cont ID  
Sent By amorse Date 2005-12-16 Time 15:19 Rev Time 0.20
Received By amorse Date 2005-12-16 Time 15:19 Sent To PC
Notes
2005-12-16 00:00:00 
  
 DENIED
  
 2ND REQUEST;
  
 1) A RECORED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED BEFORE A PERMIT
 CAN BE ISSUED
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY AND THE PLANS STAMPED PRIOR
 TO A PERMIT BEING ISSUED. A COPY OF THE
 RECEIPT SHALL BE SUBMITTED TO THE CITY
 OF WPB CONSTRUCTION DEPT.
  
 3) A SITE SPECIFIC SECTION OF THE STAIRS
 THAT COMPLY WITH THE FBC SHOWING TOTAL
 RISE AND RUN, ACTUAL RISER AND TREAD
 SIZES
  
 4) GUARDRAIL DETAIL ON 5/10 IS NOT CODE
 COMPLIANT
  
 5) ENERGY CALC'S THAT WERE SUBMITTED ARE
 NOT SIGNED BY OWNER/AGENT AND PAGE 600A
 DOES NOT MATCH SPEC'S IN DRAWINGS.
 EG. #10 ON 600A SPEC'S R19, DRAWING CB1
 & CB2 SPEC'S R30
  
 6) SUBMIT 2 COPIES OF ALL PRODUCT
 APPROVALS MARK ALL PERTINENT INFORMATION
 ON THE NOA'S THAT WILL BE USED ON JOB
 EG. DESIGN PRESSURES,FASTENERS,SPACING
 ETC.
  
 7) SHUTTER PRODUCT APPROVALS SHALL BE
 ACCOMPANIED BY A KEY PLAN SHOWING
 EMERGENCY EGRESS OPENING AND A SCHEDULE
 SIMILAR TO A SAMPLE THAT IS ATTACHED TO
 THIS NOTE
  
 8) ANY DRAWINGS THAT ARE NOT RELEVANT
 SHOULD BE REMOVED FROM SUBMITTALS
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-19 Cont ID  
Sent By rmcdouga Date 2005-07-19 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2005-07-19 Time 07:15 Sent To  
Notes
2005-07-19 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) REQUIRED DESIGN CRITERA IS INCORRECT.
 SEE FBC 1606.1.7. THE WIND SPEED FOR THE
 CITY OF WPB IS 140 MPH (3 SECOND GUST),
 THE BUILDING CATEGORY IS II AND THE WIND
 IMPORTANCE FACTOR IS 1.00.
  
 4) REVISE THE COMPONENT AND CLADDING
 WINDLOAD PRESSURES FOR THE WINDOW AND
 DOOR OPENINGS ON SHEET 1 FOR 140 MPH
 WIND SPEED. SEE FBC 1606.2.
  
 5) SUBMIT 2 COPIES OF A SURVEY.
  
 6) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE ON THE PLANS. SEE FBC 202
 HEIGHT,BUILDING.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING FOR THE FIREPLACE SHOWN ON
 SHEET 4.
  
 8) SPECIFY THE SIZE OF THE ATTIC ACCESS
 ON SHEET 5. SEE FBC 2309.6.
  
 9) SPECIFY THE SIZE, LOCATION AND NUMBER
 OF THE ATTIC VENTS. SEE FBC 2309.7.
  
 10) PROVIDE SECTIONS OF PORCH/BALCONY
 DECKS. INDICATE HOW WATERPROOFING WILL
 BE ACCOMPLISHED.
  
 11) SPECIFY HOW IMPACT PROTECTION OF
 GLAZED OPENINGS WILL BE PROVIDED. SEE
 FBC 1606.1.4. SPECIFY ON THE PLAN THAT
 ADEQUATE SUBSTRATE WILL BE INSTALLED
 AROUND THE OPENINGS AT THE WOOD FRAME
 WALLS FOR ATTACHMENT OF THE STORM
 PANELS.
  
 12) SPECIFY THE TREAD AND RISER
 DIMENSIONS FOR THE STAIRS ON THE PLANS.
 SEE FBC 104.2.1 WHICH REQUIRES ALL
 INFORMATION TO BE SPECIFIC AND TECHNICAL
 CODES SHALL NOT BE CITED AS A WHOLE OR
 IN PART AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 13) THE GUARDRAIL DETAIL ON CB2
 CONFLICTS WITH FBC 1015.3. PLEASE
 REVISE.
  
 14) ON SHEET 5, THE EXTERIOR WALL AT THE
 REAR PORCH IS INDICATED AS A 3-1/2"
 INTERIOR WOOD WALL.
  
 15) CITY AMENDMENTS TO FBC 2111.1.9
 REQUIRES A 1.5 INCH RECESS IN THE
 CONCRETE FLOOR SURFACE WHERE EXTERIOR
 WALL MASONRY UNITS BEAR.
  
 16) SPECIFY ON THE FOOTER DETAIL ON
 SHEET 7, THAT THE FINISH FLOOR ELEVATION
 IS A MINIMUM OF 4" ABOVE FINISH GRADE AS
 REQUIRED BY CITY AMENDMENTS TO FBC
 1804.1.7.
  
 17) SPECIFY ON SHEET 7, THAT THE BOTTOM
 OF THE FOOTER IS A MINIMUM OF 12" BELOW
 FINISH GRADE. SEE FBC 1804.1.3.
  
 18) THE COLUMN PADS ON SHEET 7 ARE
 SPECIFIED WITH CONTINOUS REBAR RATHER
 THAN #5 REBAR EACH WAY. PLEASE CORRECT.
  
 19) REVISE THE ROOF TRUSS BOTTOM CORD
 LIVE LOAD ON SHEET 9. THE MINIMUM LIVE
 LOAD IS 10 PSF. SEE FBC TABLE 1604.1.
  
 20) PLEASE REMOVE OR CROSS OUT THE
 DETAILS THAT DO NOT APPLY TO THIS
 PROJECT. INFORMATION IS REQUIRED TO BE
 SPECIFIC. SEE FBC 104.2.1.
  
 21) SPECIFY THE LOCATION AND MATERIAL
 USED TO CREATE DRAFTSTOPS AT THE
 FLOOR/CEILING ASSEMBLY INTO 5OO SQFT
 AREAS AS REQUIRED BY FBC 2305.2.2.
  
 22) REVISE THE ROOF SHEATHING FASTENING
 NOTES TO COMPLY WITH CITY AMENDMENTS TO
 FBC TABLE 2306.1. WHICH REQUIRES 8D
 COMMON NAILS AT 6"OC EDGES AND 6"OC IN
 THE FIELD IN ZONES 1 & 2 AND 4"OC AT THE
 EDGES AND 6"OC IN THE FIELD IN ZONE 3.
  
 23) REVISE THE UPLIFT FOR THE USP "USC"
 CONNECTOR ON CB1. THE MAXIMUM UPLIFT IS
 11,150# WITHOUT THE 1/3 STRESS INCREASE
 ON THE STEEL. SEE USP 2005 CATALOG.
  
 24) THE GIRDER TRUSS ANCHORS SPECIFIED
 ON SHEET CB2 DO NOT MATCH THOSE
 SPECIFIED ON SHEET 9.
  
 25) ON SHEET CB2 USP TRUSS ANCHOR RT6
 ARE SPECIFIED AND ON SHEET 9 RT3 ARE
 SPECED. PLEASE CORRECT.
  
 26) SPECIFY THE 1-1/2" BLOCK RECESS IN
 THE SLAB AT THE WALL SECTIONS ON CB2.
  
 27) SUBMIT TWO COMPLETE SETS OF ENERGY
 CALCULATIONS AND MANUAL "J" CALCS.
 INFORMATION ON PLANS DO NOT MATCH THE
 FORM 600A THAT WAS SUBMITTED. PLEASE
 CORRECT.
  
 28) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 29) SUBMIT TWO COPIES OF ALL PRODUCT
 APPROVALS.
  
 30) SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING: TRUSS CONNECTORS, INSWING
 DOORS AT ENRTY WITH NO GLAZING, ROOFING
 MATERIAL AND 18' WIDE OVER HEAD GARAGE
 DOOR (ONE SUBMITTED IS FOR MAX OF 16').
  
 31) SUBMIT THE COMPLETE PRODUCT APPROVAL
 WITH STATE OF FL COVERSHEET, COMPLETE
 NOA OR OTHER APPROVED REPORT LISTING THE
 DESIGN PRESSURES, LIMITATIONS AND
 INSTALLATION DRAWINGS.
  
 32) SUBMIT TWO COPIES OF PRODUCT
 APPROVAL, KEY PLAN AND INSTALLATION
 INSTRUCTIONS WITH MOUNT TYPE, FASTENER
 TYPE AND SPACINGS.
  
 33) SPECIFY THE CLADDING MATERIAL FOR
 THE SOFFITS AND THE COVERED PORCHES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-16 Cont ID  
Sent By btrobaug Date 2005-11-16 Time 18:13 Rev Time 1.00
Received By btrobaug Date 2005-11-16 Time 17:17 Sent To M
Notes
2005-11-16 00:00:00 
 MAKE ALL REDLINED CORRECTIONS ON NEXT
 RESUB, OR REVISION , PRIOR TO ROUGH
 ELECTRICAL INSPECTION.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-24 Cont ID  
Sent By btrobaug Date 2005-06-24 Time 18:09 Rev Time 0.50
Received By btrobaug Date 2005-06-24 Time 17:43 Sent To M
Notes
2005-06-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE LOAD CALCULATIONS AND
 PANEL SCHEDULES PER 215.5.
  
 2} INDICATE AIC RATING OF ALL SERVICE
 EQUIPMENT PER 110.9 & 10.
  
 3} SHOW GEC SYSTEM PER 250.50, SIZED PER
 250.66.
  
 4} SHOW ALL EQUIPMENT THAT IS SERVICE
 RELATED ON THE RISER DIAGRAM, DO NOT USE
 A GENERIC MODEL.
  
 5} THERE ARE SEVERAL LOCATIONS WHERE
 RECEPTACLE SPACING DOES NOT MEET THE
 REQUIREMENTS OF 210.52(A)(1),(2). SEE
 REVIEWED PLANS .
  
 6} A RECEPTACLE IS NEEDED AT THE
 CONDENSER PER 210.63.
  
 7} A RECEPTACLE MUST BE PLACED OUTSIDE
 IN THE FRONT FOR COMPLIANCE WITH
 210.52(E).
  
 8 A SMOKE DETECTOR AT THE STAIRS ON THE
 FIRST FLOOR IS NEEDED PER 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 13:04 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 13:04 Sent To E
Notes
2005-11-10 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-13 Cont ID  
Sent By adarroug Date 2005-10-13 Time 08:34 Rev Time 0.00
Received By adarroug Date 2005-10-13 Time 08:34 Sent To Z
Notes
2005-10-13 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 10:11 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 10:11 Sent To E
Notes
2005-06-24 00:00:00TO "SFR" "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-19 Cont ID  
Sent By rmcdouga Date 2005-07-19 Time 14:54 Rev Time 0.00
Received By rmcdouga Date 2005-06-21 Time 14:08 Sent To  
Notes
2005-06-21 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-11-17 Cont ID  
Sent By pkrauss Date 2005-11-17 Time 08:52 Rev Time 0.40
Received By pkrauss Date 2005-11-17 Time 08:52 Sent To  
Notes
2005-11-17 00:00:00DENIED:
 PLEASE NOTE, PLAN SHEET 10 OF 10
 CONTAINS A/C EQUIPMENT INFORMATION &
 DUCT LAYOUT.A/C PLANS WERE ALSO
 SUBMITTED BY THE A/C CONTRACTOR (CMI).
 PLEASE ELIMATE THE PLANS THAT WILL NOT
 BE USED.
  
 2ND REQUEST:
 1.RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.(SEE ATTACHED COMMENT SHEET)
  
 SEE ATTACHED COMMENT SHEET ITEM #3 & 5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-05 Cont ID  
Sent By btrobaug Date 2005-07-05 Time 18:26 Rev Time 0.40
Received By pkrauss Date 2005-07-05 Time 16:02 Sent To B
Notes
2005-07-05 00:00:00DENIED:
 1.RETURN AIR JUMPERS SHALL BE A MINMUM
 OF 1 1/2 TIMES GREATER THAN THE SUPPLY
 AIR INTO THAT SPACE.ALL SUPPLY AIR
 INTO THE MASTER SUITE SHALL BE INCLUDED
 FOR PROPER SIZING OF THE RETURN AIR.
 (EXAMPLE - MASTER SUITE 1 INDICATES A
 16" SUPPLY, RETURN SHALL BE A MINIMUM OF
 20").2001 FBC(M)601.4 EXCEPTION 1 & 3.
 PLEASE SIZE ALL RETURN AIR JUMPERS
 ACCORDINGLY.
  
 2.PLEASE CLARIFY THE FOLLOWING ON THE
 1ST FLOOR 5 TON AHU.PROVIDE DETAIL FOR
 THE RETURN AIR INTO THE AHU.NO PLENUMS
 IN THE GARAGE AREA.INDICATE DOOR TYPE
 TO THE 1ST FLOOR AHU CLOSET.
  
 3.THE "GRAND ROOM" APPEARS TO HAVE A
 FIRE PLACE.PLEASE CLARIFY.SHOULD
 FIRE PLACE BE PLANNED, PLEASE PROVIDE
 MANUFACTURER'S SUBMITTAL DATA & INDICATE
 VENTING AND AIR MAKE-UP.
  
 4.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS PER 2001 FBC CHAPTER 13 SUB
 CHAPTER 6.
  
 5.PLANS INDICATE COMPLIANCE WITH 2001
 FBC FOR 130 MPH WIND LOAD.THIS SHOULD
 READ 140 MPH WIND LOAD IN ACCORDANCE
 WITH 2001 FBC AMENDMENTS 1606.1.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-11-22 Cont ID  
Sent By jleech Date 2005-11-22 Time 17:55 Rev Time 0.33
Received By jleech Date 2005-11-22 Time 17:55 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-25 Cont ID  
Sent By jleech Date 2005-06-25 Time 08:33 Rev Time 0.50
Received By jleech Date 2005-06-25 Time 08:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-10-31 Cont ID  
Sent By sgraham Date 2005-10-31 Time 14:59 Rev Time 0.00
Received By sgraham Date 2005-10-31 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-23 Cont ID  
Sent By mmclean Date 2005-06-23 Time 17:54 Rev Time 0.00
Received By mmclean Date 2005-06-23 Time 17:54 Sent To I
Notes
2005-06-23 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEYS.
 2. PROPOSED STRUCTURE EXCEEDS THE HEIGHT
 THAT IS REQUIRED BY THE ZONING
 GUIDELINES OF 33FT. PROPSED STRUCTURE
 MEASURED AT 35FT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved