| 2005-07-19 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) REQUIRED DESIGN CRITERA IS INCORRECT. |
| | SEE FBC 1606.1.7. THE WIND SPEED FOR THE |
| | CITY OF WPB IS 140 MPH (3 SECOND GUST), |
| | THE BUILDING CATEGORY IS II AND THE WIND |
| | IMPORTANCE FACTOR IS 1.00. |
| | |
| | 4) REVISE THE COMPONENT AND CLADDING |
| | WINDLOAD PRESSURES FOR THE WINDOW AND |
| | DOOR OPENINGS ON SHEET 1 FOR 140 MPH |
| | WIND SPEED. SEE FBC 1606.2. |
| | |
| | 5) SUBMIT 2 COPIES OF A SURVEY. |
| | |
| | 6) SPECIFY THE MEAN ROOF HEIGHT OF THE |
| | STRUCTURE ON THE PLANS. SEE FBC 202 |
| | HEIGHT,BUILDING. |
| | |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND LISTING FOR THE FIREPLACE SHOWN ON |
| | SHEET 4. |
| | |
| | 8) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| | ON SHEET 5. SEE FBC 2309.6. |
| | |
| | 9) SPECIFY THE SIZE, LOCATION AND NUMBER |
| | OF THE ATTIC VENTS. SEE FBC 2309.7. |
| | |
| | 10) PROVIDE SECTIONS OF PORCH/BALCONY |
| | DECKS. INDICATE HOW WATERPROOFING WILL |
| | BE ACCOMPLISHED. |
| | |
| | 11) SPECIFY HOW IMPACT PROTECTION OF |
| | GLAZED OPENINGS WILL BE PROVIDED. SEE |
| | FBC 1606.1.4. SPECIFY ON THE PLAN THAT |
| | ADEQUATE SUBSTRATE WILL BE INSTALLED |
| | AROUND THE OPENINGS AT THE WOOD FRAME |
| | WALLS FOR ATTACHMENT OF THE STORM |
| | PANELS. |
| | |
| | 12) SPECIFY THE TREAD AND RISER |
| | DIMENSIONS FOR THE STAIRS ON THE PLANS. |
| | SEE FBC 104.2.1 WHICH REQUIRES ALL |
| | INFORMATION TO BE SPECIFIC AND TECHNICAL |
| | CODES SHALL NOT BE CITED AS A WHOLE OR |
| | IN PART AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 13) THE GUARDRAIL DETAIL ON CB2 |
| | CONFLICTS WITH FBC 1015.3. PLEASE |
| | REVISE. |
| | |
| | 14) ON SHEET 5, THE EXTERIOR WALL AT THE |
| | REAR PORCH IS INDICATED AS A 3-1/2" |
| | INTERIOR WOOD WALL. |
| | |
| | 15) CITY AMENDMENTS TO FBC 2111.1.9 |
| | REQUIRES A 1.5 INCH RECESS IN THE |
| | CONCRETE FLOOR SURFACE WHERE EXTERIOR |
| | WALL MASONRY UNITS BEAR. |
| | |
| | 16) SPECIFY ON THE FOOTER DETAIL ON |
| | SHEET 7, THAT THE FINISH FLOOR ELEVATION |
| | IS A MINIMUM OF 4" ABOVE FINISH GRADE AS |
| | REQUIRED BY CITY AMENDMENTS TO FBC |
| | 1804.1.7. |
| | |
| | 17) SPECIFY ON SHEET 7, THAT THE BOTTOM |
| | OF THE FOOTER IS A MINIMUM OF 12" BELOW |
| | FINISH GRADE. SEE FBC 1804.1.3. |
| | |
| | 18) THE COLUMN PADS ON SHEET 7 ARE |
| | SPECIFIED WITH CONTINOUS REBAR RATHER |
| | THAN #5 REBAR EACH WAY. PLEASE CORRECT. |
| | |
| | 19) REVISE THE ROOF TRUSS BOTTOM CORD |
| | LIVE LOAD ON SHEET 9. THE MINIMUM LIVE |
| | LOAD IS 10 PSF. SEE FBC TABLE 1604.1. |
| | |
| | 20) PLEASE REMOVE OR CROSS OUT THE |
| | DETAILS THAT DO NOT APPLY TO THIS |
| | PROJECT. INFORMATION IS REQUIRED TO BE |
| | SPECIFIC. SEE FBC 104.2.1. |
| | |
| | 21) SPECIFY THE LOCATION AND MATERIAL |
| | USED TO CREATE DRAFTSTOPS AT THE |
| | FLOOR/CEILING ASSEMBLY INTO 5OO SQFT |
| | AREAS AS REQUIRED BY FBC 2305.2.2. |
| | |
| | 22) REVISE THE ROOF SHEATHING FASTENING |
| | NOTES TO COMPLY WITH CITY AMENDMENTS TO |
| | FBC TABLE 2306.1. WHICH REQUIRES 8D |
| | COMMON NAILS AT 6"OC EDGES AND 6"OC IN |
| | THE FIELD IN ZONES 1 & 2 AND 4"OC AT THE |
| | EDGES AND 6"OC IN THE FIELD IN ZONE 3. |
| | |
| | 23) REVISE THE UPLIFT FOR THE USP "USC" |
| | CONNECTOR ON CB1. THE MAXIMUM UPLIFT IS |
| | 11,150# WITHOUT THE 1/3 STRESS INCREASE |
| | ON THE STEEL. SEE USP 2005 CATALOG. |
| | |
| | 24) THE GIRDER TRUSS ANCHORS SPECIFIED |
| | ON SHEET CB2 DO NOT MATCH THOSE |
| | SPECIFIED ON SHEET 9. |
| | |
| | 25) ON SHEET CB2 USP TRUSS ANCHOR RT6 |
| | ARE SPECIFIED AND ON SHEET 9 RT3 ARE |
| | SPECED. PLEASE CORRECT. |
| | |
| | 26) SPECIFY THE 1-1/2" BLOCK RECESS IN |
| | THE SLAB AT THE WALL SECTIONS ON CB2. |
| | |
| | 27) SUBMIT TWO COMPLETE SETS OF ENERGY |
| | CALCULATIONS AND MANUAL "J" CALCS. |
| | INFORMATION ON PLANS DO NOT MATCH THE |
| | FORM 600A THAT WAS SUBMITTED. PLEASE |
| | CORRECT. |
| | |
| | 28) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 29) SUBMIT TWO COPIES OF ALL PRODUCT |
| | APPROVALS. |
| | |
| | 30) SUBMIT PRODUCT APPROVALS FOR THE |
| | FOLLOWING: TRUSS CONNECTORS, INSWING |
| | DOORS AT ENRTY WITH NO GLAZING, ROOFING |
| | MATERIAL AND 18' WIDE OVER HEAD GARAGE |
| | DOOR (ONE SUBMITTED IS FOR MAX OF 16'). |
| | |
| | 31) SUBMIT THE COMPLETE PRODUCT APPROVAL |
| | WITH STATE OF FL COVERSHEET, COMPLETE |
| | NOA OR OTHER APPROVED REPORT LISTING THE |
| | DESIGN PRESSURES, LIMITATIONS AND |
| | INSTALLATION DRAWINGS. |
| | |
| | 32) SUBMIT TWO COPIES OF PRODUCT |
| | APPROVAL, KEY PLAN AND INSTALLATION |
| | INSTRUCTIONS WITH MOUNT TYPE, FASTENER |
| | TYPE AND SPACINGS. |
| | |
| | 33) SPECIFY THE CLADDING MATERIAL FOR |
| | THE SOFFITS AND THE COVERED PORCHES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |