Plan Review Details - Permit 05061295
Plan Review Stops For Permit 05061295
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By rmcdouga Date 2005-07-13 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2005-07-13 Time 14:26 Sent To  
Notes
2005-07-13 00:00:00DENIED
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OCCUPANCY OF THE BUILD OUT
 APPEARS TO BE GROUP I UNRESTRAINED PER
 FBC 309.1. INDICATE TYPE OF OCCUPANCY ON
 THE PLANS. CLARIFY IF PATIENTS ARE
 MEDICATED AND LENGTH OF STAY, ETC.
  
 3) FBC TABLE 500 REQUIRES THIS OCCUPANCY
 TYPE TO HAVE AN APPROVED SPRINKLER
 SYSTEM. SPECIFY ON THE PLANS.
  
 4) SEE FBC TABLE 803.3 FOR MINIMUM
 INTERIOR FINISH CLASSIFICATIONS. ALSO
 SEE NOTE 1.
  
 5) INSTITUTIONAL OCCUPANCIES ARE
 REQUIRED TO HAVE A 2 HOUR FIRE
 SEPARATION FROM OTHER OCCUPANCIES PER
 FBC 704.1.1.
  
 6) FBC TABLE 704.2.4 REQUIRES EXIT
 ACCESS WALLS TO RESIST THE PASSAGE OF
 SMOKE. SEPECIFY THE RATING OF THE
 EXISTING TENANT SEPARATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 17:36 Rev Time 0.33
Received By dpalmer Date 2005-07-01 Time 17:33 Sent To  
Notes
2005-07-01 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE BOTH SETS OF PLANS
 CONTAIN A "STAMP" FOR THE ARCHITECT'S
 REQUIRED ORIGINAL SIGNATURE. PLEASE SEE
 FS 481.221 WHICH REQUIRES THE ARCHITECT
 TO SIGN, DATE AND SEAL PLANS WITH AN
 ORIGINAL SIGNATURE. THIS HAS BEEN
 COMMENTED BEFORE ON PREVIOUS PROJECTS.
 ONE SET OF PLANS IS BEING RETAINED FOR
 FILE AND SHALL BE PLACED WITH OTHER SADI
 PLANS. THESE MAY BE SUBMITTED TO THE
 FLORIDA BOARD OF ARCHITECT/ DBPR.
  
 2)NOTE: PLEASE SEE 230.2 FOR ADDITIONAL
 SERVICES PERMITTED. PLEASE SEE THIS DOES
 NOT SEEM TO FALL UNDER ANY OF THE
 EXCEPTIONS.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW MAINS. 110.9,215.5
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT TWO COMPLETE SETS OF
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 13:11 Sent To  
Notes
2005-07-11 00:00:001. ACCORDING TO THE PERMIT APPLICATION
 THE PROPOSED CONSTRUCTION IS FOR A
 SLEEP CENTER. IF PERSONS ARE EXPECTED
 TO SLEEP INSIDE THE LOCATION, ELECTRIC
 POWERED SMOKE DETECTORS WILL BE REQUIRED
 THROUGHOUT THE PREMISE.
  
 2. THE NOTE ON PAGE E-2 DOES NOT APPEAR
 TO BE CORRECT. EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WHEN IT IS
 OCCUPIED. PLEASE REVIEW SPECIAL
 LOCKING ARRANGEMENTS WITHIN THE LIFE
 SAFETY CODE, 2003 EDITION. PLEASE VERIFY
 COMPLIANCE WITH THE APPLICABLE CODE
 REQUIREMENTS FOR LOCKING DEVICES.
  
 3. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-19 Cont ID  
Sent By adarroug Date 2005-07-19 Time 14:34 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 14:09 Sent To  
Notes
2005-07-12 00:00:00TAKEN FROM "COMM" BD#11/TO BOB BD#3
2005-06-23 00:00:00TO "COMM" BD#11
2005-06-21 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By hmoser Date 2005-07-15 Time 13:30 Rev Time 0.00
Received By hmoser Date 2005-07-15 Time 13:12 Sent To  
Notes
2005-07-15 00:00:00PLEASE SUBMIT TWO CONPLETE SETS OF PLANS
 PLAN REVIEW BY HAROLD MOSER.561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By kstevens Date 2005-07-13 Time 17:10 Rev Time 0.63
Received By kstevens Date 2005-07-13 Time 17:10 Sent To  
Notes
2005-07-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE PERSONAL SIGNATURE OF
 THE ARCHITECT SHALL APPEAR ON ALL
 ARCHITECTURAL DOCUMENTS. THE SEAL HAS
 BEEN STAMPED WITH THE ARCHITECTS NAME
 AND IS NOT THE REQUIRED SIGNATURE. FAC
 61G1-16.003 & FS 481.2055
 2. SHTS A-1 AND P-1 BED #3 EXISTING SINK
 BEING CAPPED OFF. IN THE REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS ARE
 NOT APPROVED. SECTION 704.5.
 3. SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. FLOOR PLAN
 SHOWS THE BUILDING DRAIN LINE TO THE
 RIGHT SIDE OF THE FIXTURES AND THE SANT.
 RISER DIAGRAM SHOWS THE BUILDING DRAIN
 LINE TO THE LEFT SIDE OF THE FIXTURES.
 PLEASE CORRELATE FLOOR PLAN & RISER. -
 SHOW ALL PIPE SIZES. SECTION 104.2.1.
 4. SHT P-1 FIRST FLOOR PLUMBING PLAN,
 FITTINGS CONNECTING THE TOILET ROOMS AND
 THE BRANCH LINE DO NOT COMPLY WITH
 SECTION 706.3. THEY DO NOT GUIDE THE
 WASTE IN THE DIRECTION OF FLOW.
 5. SHT P-1 WATER RISER DIAGRAM, THE
 HEATER SHALL HAVE THERMAL EXPANSION
 CONTROL PER SECTION 607.3.2.
 6. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE SPACE OR BUILDING.
 SECTION 608.13.2.
 7 SHT P-1 TOILET DETAILS. SHOW THE
 FOLLOWING:
 FOR THE TOILET
 A. CLEAR FLOOR SPACE 11-4.16.2
 B. FLUSH CONTROLS 11-4.16.5
 FOR THE LAV
 A. CLEAR FLOOR SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-19 Cont ID  
Sent By jroach Date 2005-07-19 Time 14:18 Rev Time 0.00
Received By jroach Date 2005-07-19 Time 14:18 Sent To  
Notes
***NONE***