Plan Review Details - Permit 05061293
Plan Review Stops For Permit 05061293
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-13 Cont ID  
Sent By jwitmer Date 2005-08-13 Time 09:29 Rev Time 0.33
Received By jwitmer Date 2005-08-13 Time 09:21 Sent To Z
Notes
2005-08-13 00:00:00SERVED NOTICE:
 FL S S 472.025 / 61G17-6.002(8)(E)
  
 61G17-6.002(8)(E) ALL SURVEY MAPS AND
 REPORTS OR COPIES THEREOF ARE NOT VALID
 WITHOUT THE ORIGINAL SIGNATURE, AND THE
 ORIGINAL RAISED SEAL OF A FLORIDA FOR
 LICENSED SURVEYORS AND MAPPERS.
  
 61G17-6.002(8)(C) ALL SURVEY MAPS AND
 REPORTS MUST BEAR THE NAME, "CERTIFICATE
 OF AUTHORIZATION NUMBER", AND THE STREET
 MAILING ADDRESS OF THE BUSINESS ENITITY
 ISSUING THE MAP OR REPORT, ALONG WITH
 NAME AND LICENSE NUMBER OF THE SURVEYOR
 AND MAPPER IN RESPONSIBLE CHARGE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-29 Cont ID  
Sent By btrobaug Date 2005-07-29 Time 10:15 Rev Time 0.33
Received By btrobaug Date 2005-07-27 Time 08:28 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-08 Cont ID  
Sent By btrobaug Date 2005-07-08 Time 14:14 Rev Time 0.50
Received By btrobaug Date 2005-07-08 Time 13:19 Sent To Z
Notes
2005-07-08 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT THE GENERATOR AND TRANSFER
 SWITCH MANUFACTURERS SPEC'S. HI-LITE THE
 PRIME MOVER.
  
 2} ONE SHEET INDICATES A 25K GENERATOR
 AND THE OTHER A 30K. PLEASE CORRELATE.
  
 3} SEE 445.13 FOR FEEDER SIZE. 115%.
  
 DISCONNECTING MEANS PER 225.30 AND
 225.36. INDICATE SAME, TRANSFER SWITCH
 MAY NOT BE SERVICE RATED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-07-21 Cont ID  
Sent By pschmitz Date 2005-07-21 Time 08:50 Rev Time 0.00
Received By pschmitz Date 2005-07-21 Time 08:50 Sent To M
Notes
2005-07-21 00:00:00GAS PERMIT #05061726 APPLIED FOR.PES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 09:53 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 09:53 Sent To E
Notes
2005-07-21 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 10:52 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 10:52 Sent To P
Notes
2005-07-14 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By mmclean Date 2005-07-13 Time 15:31 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 13:52 Sent To  
Notes
2005-06-21 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-01 Cont ID  
Sent By rregueir Date 2005-08-01 Time 17:57 Rev Time 0.00
Received By rregueir Date 2005-08-01 Time 17:56 Sent To B
Notes
2005-08-01 00:00:00---------------PROVISO------------------
 GENERATOR EXHAUST TO BE MIN, 10' FROM
 BUILDING OPENINGS (DOORS,WINDOWS), ALSO
 IN COMPLIANCE WITH FBC,M 804.3
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-10 Cont ID  
Sent By jleech Date 2005-08-10 Time 12:33 Rev Time 0.00
Received By jleech Date 2005-08-10 Time 12:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-15 Cont ID  
Sent By mmclean Date 2005-08-15 Time 16:27 Rev Time 0.00
Received By mmclean Date 2005-08-15 Time 16:27 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By mmclean Date 2005-07-13 Time 14:44 Rev Time 0.00
Received By mmclean Date 2005-07-13 Time 14:44 Sent To I
Notes
2005-07-13 00:00:00DENIED,
 1. MUST PROVIDE A LETTER FROM HOA
 APPROVING THE GENERATOR ON PROPERTY AND
 SURVEY & PLANS TO BE STAMPED BY HOA.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved