Plan Review Details - Permit 05061271
Plan Review Stops For Permit 05061271
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-31 Cont ID  
Sent By jwitmer Date 2005-07-31 Time 08:39 Rev Time 0.33
Received By jwitmer Date 2005-07-31 Time 08:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-30 Cont ID  
Sent By btrobaug Date 2005-06-30 Time 14:39 Rev Time 0.00
Received By   Date 2005-06-30 Time 13:35 Sent To M
Notes
2005-06-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT TWO COPIES OF THE GENERATOR
 AND TRANSFER SWITCH SPECIFICATIONS.
 INDICATE THE PRIME MOVER, HI-LITE
 CORRECT ONE IF TWO ARE LISTED IN SPEC'S.
  
 2} THE TOTAL VALUE OF THE EQUIPMENT AND
 LABOR MUST BE ON THE APPLICATION. IF
 THIS IS OBJECTIONAL TO THE CONTRACTOR,
 THEN THE OWNER MUST APPLY FOR A PERMIT
 TO SET THE GENERATOR DECLARING TOTAL
 VALUE AT THE SAME TIME THE OTHER
 REQUIRED APPLICATIONS ARE SUBMITTED, PER
 104.6.5 CWPB AMMENDMENDTS.
  
 3} PLEASE SUBMIT A SITE/FLOOR PLAN
 INDICATING THE PHYSICAL LOCATION OF ALL
 SERVICE AND GENERATOR EQUIPMENT SO
 COMPLIANCE WITH 225.32 AND 225.36 CAN BE
 REVIEWED.
  
 4} SUBMIT LOAD CALCULATIONS FOR THE LOAD
 SERVED BY THE GENERATOR PER 230.31(B).
 SEE 702.5 INDICATING 100% OF DEMAND.
 THIS OFFICE WILL ACCEPT 230.31(B). 3VA
 FOR APPLIANCES AND GENERAL LIGHTING LOAD
 .
  
 5} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN NAME ON THE
 PLANS. 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 13:36 Rev Time 0.33
Received By jleech Date 2005-07-09 Time 13:36 Sent To B
Notes
2005-07-09 00:00:00DENIED;
 GAS PERMIT REQUIRED. PLUMBING CONTRACTOR
 SHALL MAKE APPLICATION AND SUBMIT PLANS.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-31 Cont ID  
Sent By jwitmer Date 2005-07-31 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2005-06-27 Time 10:57 Sent To  
Notes
2005-07-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061271
 ADD: 128 ELLAMAR RD
 CONT: CARPENTER ELEC
 TEL: (561)848-7881
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 104.6.5* CITY AMENDMENTS, TOTAL VALUE
 OF JOB EQUIPMENT AND LABOR.
  
 3) PROVIDE ANCHORING DETAILS.
 1606.1.3 ANCHORAGE AGAINST OVERTURNING,
 UPLIFT AND SLIDING. STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS
 AND CLADDING IN A BUILDING OR
 STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT
 AND SLIDING AND TO PROVIDE CONTINUOUS
 LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE
 RESISTANCE TO THESE FORCES IS PROVIDED
 BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN
 WIND EVENT SHALL BE USED.
  
 NOTE; LOCATED IN A "B" FLOOD ZONE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
2005-06-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 15:52 Rev Time 0.00
Received By shill Date 2005-06-20 Time 15:52 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-08 Cont ID  
Sent By rregueir Date 2005-07-08 Time 14:01 Rev Time 0.00
Received By rregueir Date 2005-07-08 Time 14:01 Sent To G
Notes
2005-07-08 00:00:00RPOVISO: GENERATOR EXHAUST TO TERMINATE
 MINIMUM 10' FROM OPENINGS INTO BUILDING
 STRUCTURE (DOORS, WINDOWS).
  
  
 RONALD J REGUEIRO
 561-805-6734

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 13:36 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-24 Cont ID  
Sent By mmclean Date 2005-06-24 Time 14:48 Rev Time 0.00
Received By mmclean Date 2005-06-24 Time 14:48 Sent To I
Notes
2005-06-24 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEYS
 2. MUST PROVIDE THE DIMENSION OF THE
 GENERATOR WITH SETBACK FROM STRUCTURE
 AND TO PROPERTY LINE
 *NOTE: GENERATORS CAN ONLY ENROACH 4FT
 INTO SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720