| 2005-06-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05061261 |
| | ADD: 3071 CONTINENTAL DR. |
| | CONT: MARION CONST |
| | TEL: (561)662-3814 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE OPENING THAT COMMUNICATES WITHIN |
| | THE OLD TENANT SEPERATION WALL INDICATES |
| | |
| | A NEW 3'-0"X 6'-8" DOOR: |
| | 1A) IS THIS TO BE (2) SEPERATE TENANTS, |
| | OR A SINGLE TENANT SINCE PLANS SHOW A |
| | 20MIN RATING? |
| | |
| | 1B) THIS SAME DOOR IF IT IS TO |
| | COMMUNICATE WITHIN A SINGLE TENANT SPACE |
| | SWINGS THE WRONG WAY FOR EXITING FROM |
| | THE TENANT SPACE, |
| | 1012.1.2 EGRESS DOORS SHALL BE SIDE |
| | SWINGING TYPE. DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS FOR THE |
| | FOLLOWING:1012.1.2 (1). WHEN SERVING AN |
| | OCCUPANT LOAD OF 50 OR MORE. |
| | |
| | 2) THE DOOR # 2 DOES NOT MEET EGRESS NOR |
| | ACCESSIBILITY REQUIREMENTS: |
| | 2A)BUSINESS OCC. EGRESS DOOR/ 32" CLEAR: |
| | 1004. THE WIDTH OF THE MEANS OF EGRESS |
| | SHALL BE DETERMINED FROM THE OCCUPANTS |
| | SERVED IN ACCORDANCE WITH TABLE 1004. |
| | 2B)11-4.13.4 DOUBLE-LEAF DOORWAYS. IF |
| | DOORWAYS HAVE TWO INDEPENDENTLY |
| | OPERATED DOOR LEAVES, THEN AT LEAST |
| | ONE LEAF SHALL MEET THE SPECIFICATIONS |
| | IN 11-4.13.5 AND 11-4.13.6.THAT LEAF |
| | SHALL BE AN ACTIVE LEAF. |
| | 2C) PLANS INDICATE THAT THE DOOR ALSO |
| | HAS A CLOSER:11-4.13.10 DOOR CLOSERS. IF |
| | A DOOR HAS A CLOSER, THEN THE SWEEP |
| | PERIODOF THE CLOSER SHALL BE ADJUSTED |
| | SO THAT FROM AN OPEN POSITION OF 70 |
| | DEGREES, THE DOOR WILL TAKE AT LEAST 3 |
| | SECONDS TO MOVE TO A POINT 3 INCHES |
| | (75 MM) FROM THE LATCH, MEASURED TO THE |
| | LEADING EDGE OF THE DOOR. |
| | |
| | 2D) THIS SAME DOOR IS PART OF A EGRESS, |
| | BUT NO SIGNAGE FOR EXITING, 1016.1.1 |
| | ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH THIS SECTION FOR EVERY |
| | BUILDING AND STRUCTURE.FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS AND PASSAGEWAYS LEADING TO |
| | AN EXIT.FOR THE PURPOSES OF THIS |
| | REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY DESIGNATED STAIRS, |
| | AISLES, CORRIDORS, RAMPS, ESCALATORS, |
| | WALKWAYS AND EXIT PASSAGEWAYS LEADING |
| | TO A PUBLIC WAY. |
| | |
| | |
| | 3) PLANS INDICATE REVERSE DOOR SWING: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |