Plan Review Details - Permit 05061261
Plan Review Stops For Permit 05061261
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 15:45 Rev Time 1.11
Received By jwitmer Date 2005-07-24 Time 15:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-30 Cont ID  
Sent By jwitmer Date 2005-06-30 Time 12:36 Rev Time 0.00
Received By jwitmer Date 2005-06-30 Time 12:36 Sent To  
Notes
2005-06-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061261
 ADD: 3071 CONTINENTAL DR.
 CONT: MARION CONST
 TEL: (561)662-3814
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE OPENING THAT COMMUNICATES WITHIN
 THE OLD TENANT SEPERATION WALL INDICATES
  
 A NEW 3'-0"X 6'-8" DOOR:
 1A) IS THIS TO BE (2) SEPERATE TENANTS,
 OR A SINGLE TENANT SINCE PLANS SHOW A
 20MIN RATING?
  
 1B) THIS SAME DOOR IF IT IS TO
 COMMUNICATE WITHIN A SINGLE TENANT SPACE
 SWINGS THE WRONG WAY FOR EXITING FROM
 THE TENANT SPACE,
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE
 FOLLOWING:1012.1.2 (1). WHEN SERVING AN
 OCCUPANT LOAD OF 50 OR MORE.
  
 2) THE DOOR # 2 DOES NOT MEET EGRESS NOR
 ACCESSIBILITY REQUIREMENTS:
 2A)BUSINESS OCC. EGRESS DOOR/ 32" CLEAR:
 1004. THE WIDTH OF THE MEANS OF EGRESS
 SHALL BE DETERMINED FROM THE OCCUPANTS
 SERVED IN ACCORDANCE WITH TABLE 1004.
 2B)11-4.13.4 DOUBLE-LEAF DOORWAYS. IF
 DOORWAYS HAVE TWO INDEPENDENTLY
 OPERATED DOOR LEAVES, THEN AT LEAST
 ONE LEAF SHALL MEET THE SPECIFICATIONS
 IN 11-4.13.5 AND 11-4.13.6.THAT LEAF
 SHALL BE AN ACTIVE LEAF.
 2C) PLANS INDICATE THAT THE DOOR ALSO
 HAS A CLOSER:11-4.13.10 DOOR CLOSERS. IF
 A DOOR HAS A CLOSER, THEN THE SWEEP
 PERIODOF THE CLOSER SHALL BE ADJUSTED
 SO THAT FROM AN OPEN POSITION OF 70
 DEGREES, THE DOOR WILL TAKE AT LEAST 3
 SECONDS TO MOVE TO A POINT 3 INCHES
 (75 MM) FROM THE LATCH, MEASURED TO THE
 LEADING EDGE OF THE DOOR.
  
 2D) THIS SAME DOOR IS PART OF A EGRESS,
 BUT NO SIGNAGE FOR EXITING, 1016.1.1
 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY
 BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS, RAMPS, ESCALATORS,
 WALKWAYS AND EXIT PASSAGEWAYS LEADING
 TO A PUBLIC WAY.
  
  
 3) PLANS INDICATE REVERSE DOOR SWING:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By dpalmer Date 2005-07-20 Time 16:46 Rev Time 0.25
Received By dpalmer Date 2005-07-20 Time 16:46 Sent To  
Notes
2005-07-20 00:00:00REDLINED 600.5 EXIST ? TO BE FIELD
 VERIFIED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 07:29 Rev Time 0.33
Received By dpalmer Date 2005-07-01 Time 07:29 Sent To  
Notes
2005-07-01 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE INDICATE NEW CIRCUITING
 ON PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUTING OF
 EM/EXT LTS. THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 2)NOTE: PLEASE CLARIFY IF NEW OR EXSITNG
 REQUIRED SIGN CIRCUIT PER 600.5 EXISTS?
  
 3)NOTE: PLEASE SEE 210.8B3WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 TENANT SPACE(S)?
 APPEARS TWO TENANTS ARE BECOMING ONE.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S)WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-02 Cont ID  
Sent By mwennerg Date 2005-08-02 Time 14:09 Rev Time 0.00
Received By mwennerg Date 2005-08-02 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By mwennerg Date 2005-07-01 Time 09:51 Rev Time 0.00
Received By mwennerg Date 2005-07-01 Time 09:35 Sent To  
Notes
2005-07-01 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO DOOR SWING AS A COMPONENT OF
 MEANS OF EGRESS.
  
 2) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 3) PLEASE INDICATE IF THIS IS A SINGLE
 OR 2 SEPARATE TENANTS. IF SEPARATE,
 PLEASE ILLUSTRATE HOW SEPARATION
 REQUIREMENTS WILL BE MET.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 13:42 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 13:42 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#10
2005-07-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 08:25 Rev Time 0.00
Received By pkrauss Date 2005-06-21 Time 15:22 Sent To  
Notes
2005-07-01 00:00:00MOVED TO BLD-OUT BOARD #8
2005-06-23 00:00:00TO "COMMM" BD#62
2005-06-21 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-06 Cont ID  
Sent By pkrauss Date 2005-07-06 Time 07:02 Rev Time 0.35
Received By pkrauss Date 2005-07-06 Time 06:53 Sent To  
Notes
2005-07-06 00:00:00RELOCATING & INSTALLATION OF GRILLES TO
 EXISTING DUCTWORK PER PLAN.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-08 Cont ID  
Sent By kstevens Date 2005-08-08 Time 12:39 Rev Time 1.50
Received By kstevens Date 2005-08-08 Time 12:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-05 Cont ID  
Sent By kstevens Date 2005-07-05 Time 07:37 Rev Time 1.00
Received By kstevens Date 2005-07-05 Time 07:37 Sent To  
Notes
2005-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT 1 IN THE INSTALLATION OR REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD
 ENDS SHALL BE PROHIBITED. SECTION 704.5.
 ALL CAPPED OFF PIPING SHALL BE FIELD
 INSPECTED PRIOR TO COVERING.
 2. SHT 2 SUBMIT A DETAIL FOR DRINKING
 FOUNTAIN SHOWING THE FOLLOWING:
 A. SPOUT HEIGHT 11-4.15.2
 B. SPOUT LOCATION 11-4.15.3
 C. CONTROLS 11-4.15.4
 D. CLEARANCES/CLEAR FLOOR SPACE
 11-4.15.5
 E. PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION
 11-4.1.3(10)(A)
 3. SHOW THE FOLLOWING REQUIREMENTS FOR
 THE BREAK ROOM SINK:
 A. SINK DEPTH 11-4.24.4
 B. CLEAR FLOOR SPACE 11-4.24.5 FORWARD
 APPROACH REQUIRED MAXIMUM 19" UNDERNEATH
 THE SINK.
 4. SUBMIT A SANT. AND A WATER RISER
 DIAGRAM. SHOW ALL PIPE SIZES, POINTS OF
 CONNECTION, VENTS, VALVES, AND WATER
 HAMMER ARRESTORS IF REQUIRED BY SECTION
 604.9. SECTION 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]