Plan Review Details - Permit 05061237
Plan Review Stops For Permit 05061237
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-24 Cont ID  
Sent By alange Date 2005-08-24 Time 16:50 Rev Time 1.50
Received By alange Date 2005-08-24 Time 15:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By mmclean Date 2005-08-10 Time 14:38 Rev Time 1.25
Received By alange Date 2005-07-27 Time 06:51 Sent To  
Notes
2005-07-27 00:00:00DENIED
  
 1.SQUARE FOOTAGE ADDED FROM FIRST AND
 SECOND FLOOR HAS BEEN REVISED TO
 568SQ.FT..
  
 2.SHOW SPIRAL STAIRCASE DETAIL
 COMPLYING WITH FBC 1007.8.2.3
  
 3.ROOF SHEATHING NAILING SHALL COMPLY
 WITH FBC 2306.1 WPB AMMENDMENTS.
  
 4. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 5. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6. FBC 2304.3.4 WHEN WOOD JOISTS OR THE
 BOTTOM OF WOOD STRUCTURAL FLOORS
 WITHOUT JOISTS ARE CLOSER THAN 18
 INCHES (457 MM) OR WOOD GIRDERS ARE
 CLOSER THAN 12 INCHES (305 MM) TO
 EXPOSED GROUND LOCATED WITHIN THE
 PERIPHERY OF THE BUILDING OVER CRAWL
 SPACE OR UNEXCAVATED AREAS, THEY
 SHALL BE OF APPROVED NATURALLY DURABLE
 WOOD OR PRESERVATIVE-TREATED WOOD.
  
 7. FBC 1804.6.3.2 ACCESS. USABLE CRAWL
 SPACES UNDER BUILDINGS WITHOUT
 BASEMENTS SHALL BE PROVIDED WITH A
 MINIMUM OF ONE ACCESS OPENING NOT
 LESS THAN 18X24 INCHES (457X610 MM).
 ACCESS OPENINGS SHALL BE READILY
 ACCESSIBLE AND PROVIDED WITH A DOOR
 OR DEVICE THAT MAY BE EASILY REMOVED
 OR OPERATED.FOR ACCESS TO
 MECHANICAL EQUIPMENT INSTALLED IN
 UNDERFLOOR
 AREAS OF THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 8.SHOW METHOD AND SIZE OF CRAWL SPACE
 VENTILATION COMPLYING WITH FBC
 1804.6.3.1
  
 9. KOLBE DOUBLE HUNG WINDOW DOES NOT
 HAVE A STATE APPROVAL SUBMITTED.
 PLEASE ATTACH THE FOLLOW STATE PRODUCT
 APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10. SUBMIT PRODUCT APPROVALS FOR
 EXTERIOR DOORS AND STRAPS AND TIE-DOWNS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-09 Cont ID  
Sent By btrobaug Date 2006-01-09 Time 16:19 Rev Time 0.50
Received By btrobaug Date 2006-01-09 Time 14:58 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-17 Cont ID  
Sent By btrobaug Date 2005-08-17 Time 07:33 Rev Time 0.50
Received By btrobaug Date 2005-08-17 Time 07:10 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-07 Cont ID  
Sent By btrobaug Date 2005-07-07 Time 10:25 Rev Time 0.50
Received By btrobaug Date 2005-07-07 Time 09:02 Sent To P
Notes
2005-07-07 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE THAT A EGRESS LIGHT AND
 SWITCH MUST BE INSTALLED AT THE BATH
 EXIT PER 210.70(A)(2)(B).
  
 2} THE BATH CIRCUIT MUST COMPY WITH
 210.11(C)(3). MAY NOT EXTEND BEYOND THE
 BATHROOM. INDICATE ON PLAN AND PANEL
 SCHEDULE.
  
 3} A SMOKE DETECTOR IS REQUIRED IN CLOSE
 PROXIMETY OF THE FIRST FLOOR STAIRWELL
 PER 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-06 Cont ID  
Sent By adarroug Date 2006-01-06 Time 17:06 Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 17:06 Sent To E
Notes
2006-01-06 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-23 Cont ID  
Sent By adarroug Date 2005-12-23 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-12-23 Time 09:30 Sent To M
Notes
2005-12-23 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 14:00 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 13:59 Sent To E
Notes
2005-08-16 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 11:03 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 11:03 Sent To Z
Notes
2005-08-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-30 Cont ID  
Sent By rregueir Date 2005-07-11 Time 10:59 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 10:21 Sent To E
Notes
2005-06-30 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 14:53 Rev Time 0.00
Received By shill Date 2005-06-20 Time 14:53 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-08-23 Cont ID  
Sent By prafter Date 2005-08-23 Time 15:47 Rev Time 0.50
Received By prafter Date 2005-08-23 Time 15:47 Sent To B
Notes
2005-08-23 00:00:00MECH.PLAN REVIEW:
  
 NOTE : PLAN AO4, A/C NOTE A/C
 CONTRACTOR TO SUBMIT A/C PLAN WITH
 EQUIPMENT INFORMATION AT A/C PERMIT
 TIME.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By rregueir Date 2005-07-11 Time 10:59 Rev Time 0.00
Received By rregueir Date 2005-07-11 Time 10:59 Sent To B
Notes
2005-07-11 00:00:00----------------FAILED------------------
 PER NOTE ON PAGE A04, SEPERATE PLANS
 WITH INFORMATION ON MECHANICAL WORK TO
 BE SUBMITTED.
  
 RONALD J REGUEIRO
 56-805-6734

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 10:20 Rev Time 0.00
Received By rregueir Date 2005-07-11 Time 10:56 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status N Date 2005-08-10 Cont ID  
Sent By mmclean Date 2005-08-10 Time 14:40 Rev Time 0.00
Received By mmclean Date 2005-08-10 Time 14:40 Sent To I
Notes
2005-08-10 00:00:00ZONING REVIEWED & APPROVED 6/20/05.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-10 Cont ID  
Sent By mmclean Date 2005-06-28 Time 14:29 Rev Time 0.00
Received By mmclean Date 2005-06-28 Time 14:29 Sent To B
Notes
***NONE***