Plan Review Details - Permit 05061227
Plan Review Stops For Permit 05061227
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By alange Date 2005-08-30 Time 08:14 Rev Time 0.25
Received By alange Date 2005-08-30 Time 08:14 Sent To E
Notes
2005-08-30 00:00:00PROVISIO
 SLAB TO BE AT A MIN. 6" ABOVE BASE
 FLOOD ELEVATION OF 7FT.ELEVATION
 SURVEY REQUIRED.
  
 ART LANGE
 BUILDING PLANS EXAMINER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-30 Cont ID  
Sent By alange Date 2005-08-30 Time 07:13 Rev Time 0.33
Received By alange Date 2005-08-30 Time 07:13 Sent To E
Notes
2005-08-30 00:00:00DENIED
  
 1.PROPERTY IS IN FLOOD ZONE "A".
 SUBMIT AN ELEVATION SURVEY SHOWING THAT
 THE TOP OF THE GENERATOR SLAB BEING AT
 6" ABOVE THE BASE FLOOD ELEVATION OF
 7FT..OR A MINIMUM OF 7FT 6 INCHES.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By dpalmer Date 2005-08-30 Time 11:30 Rev Time 1.00
Received By dpalmer Date 2005-08-29 Time 15:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-21 Cont ID  
Sent By btrobaug Date 2005-06-21 Time 12:31 Rev Time 1.00
Received By btrobaug Date 2005-06-21 Time 12:10 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 16:10 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 16:10 Sent To M
Notes
2005-07-01 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-08 Cont ID  
Sent By rregueir Date 2005-07-08 Time 11:40 Rev Time 0.00
Received By rregueir Date 2005-07-08 Time 11:40 Sent To P
Notes
2005-07-08 00:00:00PROVISO: GENERATOR EXHAUST TO TERMINATE
 MINIMUM 10' FROM OPENINGS INTO BUILDING
 STRUCTURE (DOORS,WINDOWS).

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-08-30 Cont ID  
Sent By dpalmer Date 2005-08-30 Time 11:31 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-08-30 00:00:00GASALREADY ISSUED UNDER SEPARATE
 PERMIT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 10:02 Rev Time 0.33
Received By jleech Date 2005-07-09 Time 10:02 Sent To B
Notes
2005-07-09 00:00:00GAS PLAN #05010476 DOES NOT SHOW
 GENERATOR. REVISED PLANS REQUIRED
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-29 Cont ID  
Sent By mmclean Date 2005-08-29 Time 16:47 Rev Time 0.00
Received By mmclean Date 2005-08-29 Time 16:47 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-30 Cont ID  
Sent By mmclean Date 2005-06-30 Time 13:29 Rev Time 0.00
Received By mmclean Date 2005-06-30 Time 13:29 Sent To I
Notes
2005-06-30 00:00:00DENIED,
 1. NEED TO PROVIDE THE DIMENSION OF
 GENERATOR.
 2. NEED TO INDICATE HOW FAR THE
 GENERATOR WILL BE FROM STRUCTURE AND
 PROPERTY LINE
 3. ALL MUST BE SHOWN ON TWO COPY OF
 SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 8056720