Plan Review Details - Permit 05061057
Plan Review Stops For Permit 05061057
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-11-21 Cont ID  
Sent By shill Date 2005-11-21 Time 14:14 Rev Time 1.00
Received By shill Date 2005-11-21 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-08-11 Cont ID  
Sent By shill Date 2005-08-11 Time 20:14 Rev Time 0.00
Received By shill Date 2005-08-11 Time 20:10 Sent To  
Notes
2005-08-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS FOR BOTH THE MULLIONS
 AND THE WINDOWS.FAC9B71.THE FLORIDA
 STATE PRODUCT APPROVALS WHICH I PRINTED
 FOR YOU PREVIOUSLY ARE NO LONGER IN THE
 PACKAGE.
 WWW.FLORIDABUILDING.ORG
  
 2.)SUBMIT TWO COMPLETE SETS FOR PERMIT
 ISSUANCE.ONLY ONE ENGINEER'S LETTER
 WAS SUBMITTED, ONE MULLION NOA.PLEASE
 COLLATE TWO COMPLETE SETS FOR PERMIT
 ISSUANCE.
  
 3.)THE MULLION NOA HAS A DESIGN
 PRESSURE LIMITATION OF -128 FOR AN
 OPENING OF GREATER THAN 70"WIDE, 63"
 TALL.THE ENGINEER HAS SPECIFIED A
 DESIGN PRESSURE OF -130.THE NOA
 PROVIDED IS NONCOMPLIANT FOR THE WIND
 PRESSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-07-26 Cont ID  
Sent By shill Date 2005-07-26 Time 07:50 Rev Time 0.50
Received By shill Date 2005-07-26 Time 07:50 Sent To PC
Notes
2005-07-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)YOU ARE USING ENGINEERING TO
 DETERMINE WIND PRESSURES.ORIGINALS
 REQUIRED, FAC61G15-23.002.
  
 2.)THE DADE COUNTY NOAS SUBMITTED WERE
 ILLEGIBLE.I HAVE PRINTED NEW ONES FOR
 YOU BUT IN THE FUTURE PLEASE PROVIDE
 LEGIBLE COPIES, WWW.MIAMIDADE.GOV.
 (BUILDING CODE COMPLIANCE, PRODUCT
 CONTROL)
  
 3.)SEE PREVIOUS LISTS.FLORIDA STATE
 OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOA PROVIDED. I HAVE
 PRINTED THIS FOR YOU BUT IN THE FUTURE
 PLEASE PROVIDE THIS AS WELL.
 WWW.FLORIDABUILDING.ORG
  
 4.)PROVIDE MULLION PRODUCT APPROVALS
 (EVALUATION REPORT AS WELL AS STATE OR
 LOCAL PRODUCT APPROVAL).
  
 5.)THREE DIFFERENT PRODUCTS WERE
 SUBMITTED.PLEASE SUBMIT ONLY THE
 PRODUCT YOU WISH TO INSTALL AND CIRCLE
 METHOD OF ATTACHMENT IF DIFFERENT
 OPTIONS ARE AVAILABLE SO THAT CODE
 COMPLIANCE CAN BE DETERMINED.FOR
 INSTANCE, ON THE YALE OGREN NOA, SHEET
 2, NOT ALL OPTIONS ARE COMPLIANT WITH
 THIS WIND PRESSURE.
  
 6.)THE ENGINEERING IS TO HAVE A TITLE
 BLOCK CONTAINING ALL INFORMATION
 REQUIRED BY FAC61G15-23.002.A
 CERTIFICATE OF AUTHORIZATION NUMBER
 PRINTED ON THE PLAN IS REQUIRED FOR THE
 ERNING CORPORATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-18 Cont ID  
Sent By shill Date 2005-07-18 Time 15:37 Rev Time 0.50
Received By shill Date 2005-07-18 Time 15:37 Sent To  
Notes
2005-07-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO
 NOA/TEST REPORT.PREVIOUS LIST NOT
 ADDRESSED.
  
 2.)PROVIDE THE MEAN ROOF HEIGHT OF THE
 BUILDING AND DESIGN PRESSURES FOR THESE
 OPENINGS FBC CHAPTER 16. ENGINEERING MAY
 BE REQUIRED.
  
 3.)IMPACT PROTECTION MAY BE REQUIRED,
 FBC1606.1.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By shill Date 2005-06-21 Time 11:49 Rev Time 0.50
Received By shill Date 2005-06-21 Time 11:49 Sent To PC
Notes
2005-06-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO THE NOA
 THAT WAS PROVIDED, FAC9B72.THIS
 PRODUCT HAS A STATUS OF "REAPPLY", SEE
 ATTACHED.
  
 YOU MAY APPLY FOR A LOCAL PRODUCT
 APPROVAL.SEE WWW.FLORIDABUILDING.ORG
 FOR MORE INFORMATION.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 16:24 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 16:24 Sent To B
Notes
2005-11-16 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-05 Cont ID  
Sent By shill Date 2005-08-05 Time 10:56 Rev Time 0.00
Received By shill Date 2005-08-05 Time 10:56 Sent To PC
Notes
2005-08-05 00:00:00PULLED FROM PLAN REVIEW AT CONTRACTOR'S
 REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 16:43 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 16:43 Sent To B
Notes
2005-07-28 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-25 Cont ID  
Sent By adarroug Date 2005-07-25 Time 16:48 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 16:48 Sent To B
Notes
2005-07-25 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 11:49 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 11:49 Sent To B
Notes
2005-07-13 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-21 Time 20:10 Rev Time 0.00
Received By shill Date 2005-06-15 Time 15:48 Sent To B
Notes
2005-06-15 00:00:00TO MISC BOX