Plan Review Details - Permit 05061023
Plan Review Stops For Permit 05061023
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-06 Cont ID  
Sent By jwitmer Date 2005-09-06 Time 16:38 Rev Time 1.33
Received By jwitmer Date 2005-09-06 Time 16:38 Sent To  
Notes
2005-09-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061023
 ADD: 700 S ROSEMARY # 140
 CONT:"PLAN REVIEW"
 NO CONTACT
 TEL:NO CONTACT
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) COMMENT# 4 FROM THE PREVIOUS REVIEW,
 TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 2)COMMENT# 5 FROM THE PREVIOUS REVIEW,
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) COMMENT# 6 FROM THE PREVIOUS REVIEW,
 SHEET T-1 BUILDING DESCRIPTION INDICATES
 THIS IS A TYPE V-UNPROTECTED BUILDING.
 THIS IS INCORRECT THIS IS A TYPE II
 BUILDING, FULLY SPRINKLERED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 08:40 Rev Time 1.11
Received By jwitmer Date 2005-07-24 Time 08:40 Sent To FIRE
Notes
2005-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061023
 ADD: 700 S ROSEMARY # 140
 CONT:"PLAN REVIEW"
 NO CONTACT
 TEL:NO CONTACT
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) LADIES RESTROOM, ENTRY DOOR CLEAR
 FLOOR SPACE OVERLAPS LAV CLEAR FLOOR
 SPACE.11-4.22.2(1) ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH
 11-4.13.DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
  
 2) PLANS DO NOT PROVIDE A MINIMUM 44"
 CLEAR CORRIDOR OR AISLW WIDTH, SEE TABLE
  
 1004 GROUP A. SHEET A1.1
  
 BUILDING PLAN REVIEW
 PERMIT: 05061023
 ADD: 700 S ROSEMARY # 140
 CONT:"PLAN REVIEW"
 NO CONTACT
 TEL:NO CONTACT
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 17:49 Rev Time 0.75
Received By dpalmer Date 2005-09-03 Time 17:24 Sent To  
Notes
2005-09-03 00:00:00*********** UNSAT **************
  
 PLEASE KNOW THAT PLANS ARE ONLY
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT AS OF YET.
 PLEASE ALSO KNOW, THE STATE OF FLORIDA
 IS SET TO CHANGE CODES ON OCT 1ST 2005.
 IF PLANS HAVE NOT BEEN SUBMITTED FOR
 PERMIT AND FEES PAID BEFORE THAT TIME,
 ALL DESIGNS WILL BE REQUIRED UNDER THE
 NEW FBC 2004 FBCADOPTED CODES.
  
 1)NOTE: PLEASE SHOW THE ATTACHMENT FOR
 NEW TRANSFORMER SHOWN.
 PLEASE SEE 250.30,250.66.TRANSFORMER
 IS NOT SHOWNATTACHED TO GROUNDING
 DETAIL SHOWN ON PLANS?
  
 2)NOTE:PLEASE SEE PANEL SCHEDULE FOR HA
 PANEL IS SHOWING "SPARE" FOR WHAT APPEAR
 TO BE RTU'S/ A/C EQUIPMENT?
 PLEASE ALSO SEE LOAD CALCULATIONS
 INDICATE "0" FOR LARGEST MOTOR LOAD(S).
 MIN 125%, SHALL BE FIGURED.
 215.3
  
 3)NOTE: PLEASE SEE NEW 600A MAIN
 INDICATES A NEW GROUNDING ELECTRODE
 CONDUCTOR WITH ATTACHMENT TO NEW
 GROUNDING ELECTRODE???
 PLEASE CLARIFY.
 PLEASE SEE PREVIOUS NOTES WHICH
 REQUESTED INFORMATION WHETHER
 "LANDLORDS" WIREWAY CONTAINED A "MAIN"
 AHEAD OF WIREWAY?
 PLEASE SEE IF NOT THEN AN "EQIPMENT
 GROUNDING CONDUCTOR" WOULD ONLY BE
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.(NEW 600A MAIN) PLEASE SEE
 RISER SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR FROM WIREWAY TO NEW 600A MAIN.
 THIS IS OK IF THERE IS A MAIN ON THE
 LINE-SIDE OF THE WIREWAY SHOWN.
 PLEASE SEE 250.24, AND 250.6.
 PLEASE BE SURE NEUTRAL "IS NOT"
 PARALLED.
  
 4)NOTE: PLEASE SEE LOAD SHOWN ON PANEL
 "A" IS SHOWN AT 198A'S AFTER DEMANDS
 TAKEN. PLEASE SEE 75KVA TRANSFORMER
 @208V ON SECONDARY SIDE IS ONLY RATED AT
 208A'S MAX.
 PLEASE SEE 90.7, WHICH STATES ANY DESIGN
 IN AN ELECTRICAL SYSTEM SHOULD PROVIDE
 ROOM FOR "FUTURE PLANNING" OF POSSIBLE
 EXPANSION OF ELECTRICAL.
  
 5)NOTE: PLEASE CORRELATE ROOF TOP
 EQUIPMENT EF-1 AND MUA-1 WITH PANEL
 SCHEDULES, EF-1 COULD NOT BE LOCATED,
 ONLY EF-2? (MISPRINT)?
 PLEASE CORRELATE WITH MECHANICAL PLANS.
 MUA-1 COULD NOT BE LOCATED ON A PANEL
 SCHEDULE.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING>
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-05 Cont ID  
Sent By dpalmer Date 2005-07-05 Time 08:25 Rev Time  
Received By dpalmer Date 2005-07-05 Time 08:25 Sent To  
Notes
2005-07-05 00:00:00********* UNSAT *************
  
 ** PLAN REVIEW ONLY **
 NOT SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS PER FAC
 61G1-16.004,61G15-23.002, FS 481.219,
 471.023.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENTS ARE
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE FS 481.221, 471.025
 WHICH REQUIRES PLANS TO BE SIGNED BY
 ARCH/ ENG. PLEASE SEE PLANS APPEAR TO BE
 "SIGNED" WITH INITIALS? IF THIS IS
 INDEED THE LEGAL SIGNATURE, PLEASE
 PROVIDE A SIGNED, SEALED, DATED LTR FOR
 VERIFICATION OF LEGAL SIGNATURE. THIS
 LTR IS REQUIRD TO BE NOTORIZED UNDER THE
 GUIDELINES OF FS 117.
 THIS WILL BE PLACED IN SIGNATURE FILE
 FOR FUTURE REFERENCE.
  
 3)NOTE: PLEASE CLARIFY IF EXISITNG MAIN
 SHOWN IS THE FIRST MEANS OF DISCONNECT
 FOR SERVICE. IF SO, PLEASE SEE
 250.6,250.24 FOR EQUIPMENT GROUNDING
 CONDUCTOR SHOWN BEFORE THE FIRST MEANS
 OF DISC.
  
 4)NOTE: PLEASE SHOW THE GROUNDING
 ATTACHMENT FOR TRANSFORMER. 250.30
  
 5)NOTE: PLEASE SEE 700.12E FOR CIRCUTING
 OF EM/EXT LTS.THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE ALSO SEE 220.12 FOR TRACK LT
 LOADS TO BE SHOWN.
  
 7)NOTE: PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 08:40 Rev Time 0.00
Received By adarroug Date 2005-07-24 Time 08:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 15:08 Rev Time 0.00
Received By mcarsill Date 2005-09-12 Time 15:08 Sent To  
Notes
2005-09-12 00:00:001. SEPERATE PLANS AND PERMITS
 REQUIRED FOR HOOD, DUCT, AND FIRE
 SUPPRESSION SYSTEM.
  
 2. FIRE SPRINKLER REMODEL DRAWINGS
 AND PERMIT REQUIRED.
  
 3. FIRE SPRINKLER PROTECTION REQUIRED
 IN COOLER AND FREEZER.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODEL.
  
 5. FIRE RESCUE PHONE NUMBER AND FAX
 NUMBER HAS CHANGED. THE PHONE NUMBER IS
 NOW 804-4724 AND THE FAX IS 804-4774.
  
 6. FINAL OCCUPANT LOAD TO BE DETERMINED
 BY THE BUREAU OF FIRE PREVENTION.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4724 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By mwennerg Date 2005-07-27 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2005-07-27 Time 15:17 Sent To  
Notes
2005-07-27 00:00:00******DENIED******
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 3) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC TITLE BLOCK
 REQUIREMENTS FOR ALL SHEETS.
  
 4) PLEASE ILLUSTRATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS,
 IE. CLASS A,B OR C.
  
 5) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS WHERE
 PROVIDED SHALL BE WIRED TO THE FIRE
 ALARM SYSTEM TO CAUSE A GENERAL FIRE
 ALARM CONDITION WHEN ACTIVATED.
  
 6) AN ADDRESS SUITE NUMBER IS REQUIRED
 ON THE BUILDING.
  
  
 MIKE WENNERGREN, CAPTAIN
 PLAN REVIEW(561) 805-6722
 WPBFR(561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-24 Time 10:04 Rev Time 0.00
Received By adarroug Date 2005-08-24 Time 10:04 Sent To  
Notes
2005-08-24 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-07-28 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-06-14 Time 17:40 Sent To  
Notes
2005-06-20 00:00:00COMM BOARD #17
  
2005-06-14 00:00:00WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By pkrauss Date 2005-09-30 Time 13:23 Rev Time 0.00
Received By pkrauss Date 2005-09-30 Time 12:54 Sent To  
Notes
2005-09-30 00:00:00PROVISO:
 GREASE DUCT SHALL TERMINATE A MINIMUM OF
 10 FT FROM ADJACENT PROPERTY LINES
 CONTIGUOUS BUILDINGS AND AIR INTAKE
 OPENINGS.2001 FBC(M)506.3.14.3.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION AND WALK-IN COOLERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-16 Cont ID  
Sent By hmoser Date 2005-07-16 Time 07:01 Rev Time 0.00
Received By hmoser Date 2005-07-16 Time 06:36 Sent To  
Notes
2005-07-16 00:00:00PLAN DENIED
 1) PLEASE REFER TO SECTION 104.2.1 FBC.
 DRAWINGS AND SPECIFICATIONS
 REQUIREMENTS.
 2) PLEASE REFER TO SECTION 601.4 FBC(M)
 BALANCED RETURN AIR.
 3) PLEASE PROVIDE FRESH AIR CALCULATIONS
 PER TABLE 403.3 FBC(M).
 (4 ADDITINOAL PERMITS ARE REQUIRED FOR
 HOOD,HOOD SUPRESSION AND WALK IN
 COOLERS.
 5) PLEASE REFER TO SECTION 506.3.14.2
 AND NFPA 96 SECTION 7.8.3 COMMERCIAL
 HOODS WALL TERMINATIONS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-01 Cont ID  
Sent By pschmitz Date 2005-10-01 Time 14:35 Rev Time 0.00
Received By pschmitz Date 2005-10-01 Time 14:35 Sent To  
Notes
2005-10-01 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLANREVIEW
 DENIED
 1) PREVIOUS COMMENTS DATED 7-9-05
 6 THRU 22, DIFFICULT TO FIND YOUR
 COMMENTS.
 WHEN RE- SUBMITTING PLANS, PLEASE
 INCLUDE A TRANSMITTAL LETTER FOR ALL
 DISIPLINES, LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE. IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By kstevens Date 2005-07-12 Time 07:24 Rev Time 10.64
Received By kstevens Date 2005-07-09 Time 13:23 Sent To  
Notes
2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE PERSONAL SIGNATURE IS REQUIRED ON
 ALL ARCHITECTURAL SHEETS. IT APPEARS
 THAT THE SHEETS ARE INITIALED AND NOT A
 SIGNATURE. PLEASE PROVIDE A SIGNED,
 SEALED, DATED AND NOTORIZED LETTER
 INDICATING THE LEGAL SIGNATURE OF THE
 ARCHITECT OF RECORD FOR OUR FILES. FAC
 61G1-16.003 AND FS 481.2055.
 2. THE FOLLOWING INFORMATION IS REQUIRED
 IN THE TITLE BLOCK OF THE ARCHITECT PER
 FAC 61G1-16.004(1) THRU (6): FIRM NAME,
 ADDRESS, & TELEPHONE NUMBER(1), FIRM
 LICENSE NUMBER(2), & SPACE FOR PRINTED
 NAME OF THE PERSON SEALING THE
 DOCUMENT(6). FS 481.2055.
 3. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AS HE/SHE AFFIXES THE DATED
 SEAL. PER FBPE RULING INITIALS ARE NOT
 APPROVED. SUBMIT A SIGNED, SEALED, DATED
 AND NOTORIZED LETTER INDICATING THE
 LEGAL SIGNATURE OF THE ENGINEER OF
 RECORD FOR OUR RECORDS. FAC
 61G15-23.002(1) AND FS 471.025
 4. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THROUGH A
 DULY AUTHROIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF
 AUTHROIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) AND FS 471.025.
 5. PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND RESTURANT DIVISION FOR REVIEW. PLANS
 SHALL BE STAMPED AND THE 2 PAGE
 "WORKSHEET" ATTACHED TO EACH SET OF
 PLANS RESUBMITTED FOR BY CITY OF WPB.
 SECTION 101.4.7.
 6. INDICATE IF THE RESTURANT WILL HAVE
 FIXED SEATING OR BE WITHOUT FIXED
 SEATING. SEE TABLE 1003.1.
 7. SHT A1.1 TOILET ROOMS, IN NEW
 CONSTRUCTION A LAVATORY SHALL BE
 PROVIDED WITHIN THE ACCESSIBLE TOILET
 STALL. SEE FIG 30E.
 8. SHT T1 INDICATES MAXIMUM SEATING TO
 BE 76, BUT SHT A1.1 INDICATES SEAT COUNT
 TO BE UP TO 104 ON THE SEATING SUMMARY.
 ALSO THE COUNT OF THE SEATS ON SHT A1.1
 ADD UP TO 96. PLEASE CLARIFY AS THIS
 WILL AFFECT THE NUMBER OF FACILITITES
 REQUIRED IN TABLES 1003.1 & 403.1.
 SECTION 104.2.1.
 9. SHT A1.1 PLEASE SUBMIT AN EQUIPMENT
 SCHEDULE IDENTIFYING ALL EQUIPMENT,
 INDICATING ALL SUPPLY AND DRAINAGE PIPE
 SIZES ECT.
 10. SHT A1.4 RESPONSIBLIITY SCHEDULE IS
 INCOMPLETE. SECTION 104.2.1.
 11. SHT A4.0 WHERE DOES IT INDICATE THE
 WALL DESIGINATION, (A-B-C-D), SO THE
 FINISH CAN BE MATCHED UP TO THE WALL?
 ALSO PLEASE SHOW HOW THE WOOD BASE AND
 THE WALL FINISH COMPLIES WITH SECTION
 1204.2 FOR PUBLIC TOILETS.
 12. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE RESTURANT. SECTION
 608.13.2.
 13. SHT P1.0 PLUMBING NOTES #22 FILTER
 TO ICE MACHINE FILTER SHALL COMPLY WITH
 NSF 42. SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 611.1
 14. SHT P1.0 DEMOLITION GENERAL NOTES #4
 IN THE REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5.
 15. SHT P1.1 OVERWALL SANITARY PLAN, THE
 GREASE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. WASTE
 ORDINANCE#2938-96. CONTACT LYNN MASSON
 (561) 822-2271 - FAX (561) 822-2279 -
 E-MAIL [email protected]. PLEASE SUBMIT A
 COPY OF THE DETERMINATION SHEET WITH
 PLANS WHEN RESUBMITTING.
 16. SHT P2.1 SANT. RISER DIAGRAM AND
 SANT. FLOOR PLAN. EVERY DRY VENT
 CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE
 HORIZONTAL DRAIN PIPI. SECTION 905.3.
 VENT SHALL RISE VERTICALLY TO A MINIMUM
 OF 6" ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE SERVED.
 SECTION 905.4.
 17. SHT P2.1 GREASE WASTE RISER AND
 GREASE FLOOR PLAN. DISHWASHERS SHALL
 CONNECT TO THE SANITARY SYSTEM NOT THE
 GREASE SYSTEM PER UTILITY DEPT.
 18. SHT P2.1 GREASE WASTE RISER AND
 GREASE FLOOR PLAN. KEY NOTES #3 STATES
 "3 INCH GW TO VENTED 3" FS SEE P1.1-01
 FOR CONTINUATION". THE CONTINUATION HAS
 NOT BEEN FOUND ON SHT P1.1-01. PLEASE
 CLARIFY.SECTION 104.2.1.
 19. SHT P3.1 WATER RISER DIAGRAM WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE ICE
 MAKER, AND THE DISH WASHERS PER SECTION
 604.9. ALL WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201.
 20. SHT P3.1 WATER RISER ISOMETRIC DOES
 NOT REFLECT THE FLOOR PLAN AT EQUIPMENT
 NUMBER 9. A CW LINE ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 21. SHT P3.1 DETAIL P3.1-03 IS
 MISLABELED AS SANITARY AND VENT
 ISOMETRIC PLAN. THIS IS A WATER
 ISOMETRIC. SECTION 104.2.1.
 22. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. WELDED PIPE REQUIRES A PICTURE
 IDENTIFICATION, WELDING CERTIFICATION,
 AND WELDING PROCEDURE AT TIME OF
 APPLICATION FOR GAS PERMIT.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]