Plan Review Details - Permit 05061017
Plan Review Stops For Permit 05061017
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-08 Cont ID  
Sent By jwitmer Date 2006-05-08 Time 08:19 Rev Time 0.44
Received By jwitmer Date 2006-05-08 Time 08:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By jwitmer Date 2005-09-14 Time 06:22 Rev Time 2.22
Received By jwitmer Date 2005-09-13 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 12:55 Rev Time 2.22
Received By jwitmer Date 2005-07-24 Time 12:55 Sent To PC
Notes
2005-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061017
 ADD: 2813 EXCHANGE CT
 CONT: SOUTHHAMPTON RESTORATION
 TEL: (561)687-0505
  
 2001 FL BLDGFLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLION
  
 3) PLANS DO NOT PROVIDE CLASSIFICATION
 BY TYPE OF BUILDING 601.2.1. PLANS ALSO
 DO NOT PROVIDE IF FIRE SPRINKLERED? A-3
 INDICATES A FIRE SPRINKLER RISER ON THE
 EXTERIOR OF BUILDING, IS ACTIVE?
  
 4) PROVIDE INFORMATION ON CHAIRLIFT?
 TO COMPLY WITH ASME A 17.1.
  
 5) IF BUILDING IS NOT FIRE SPRINKLERED,
 THEN ARTICLES DEALING WITH AREA OF
 RESCUE ASSISTANCE ARE REQUIRED.
 SEE 11-4.3.11.1.(1-7).
  
 6)SEE A.1 LUNCHROOM INDICATES SECTION 3
 BUT NO SECTION APPEARS FOR LUNCH COUNTER
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN
 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
  
 7)M1 INDICATES A A/C GRILL IN THE
 STAIRWELL, SEE 1006.1.3.1.
  
 8) DOOR# 9 REQUIES 18" CLEAR ON THE
 LATCH SIDE. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARENCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-22 Cont ID  
Sent By dpalmer Date 2006-06-22 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2006-06-22 Time 19:12 Sent To  
Notes
2006-06-22 00:00:00** PLANS REDLINED **
  
 TO VERIFY OF PC/ MPDEM RM IS INDEED AN
 "IT" ROOM WHICH WILL REQUIRE RATING S
 FOR CONSTRUCTION, DISCONNECTS ETC.
 PLEASE SEE 645 OF NFPA-70, AND NFPA-75
 FOR REQUIREMENTS ALSO IN "IT" ROOMS.
 ENGINEER OR RECORD HAS SEALED PLANS NOT
 AS AN IT ROOM.
  
  
 ** PLEASE KNOW, AS NOTED ON PREVIOUS
 REVIEW, THIS ROOM WAS NOT ON ORIGINAL
 PLANS AND WAS ADDED DURING CONSTRUCTION.
 IF AN "IT", REVISED PLANS WILL BE
 REQUIRED TO BE SUBMITTED FOR B,M,F, E.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-25 Cont ID  
Sent By dpalmer Date 2006-04-25 Time 07:43 Rev Time 0.00
Received By dpalmer Date 2006-04-25 Time 07:12 Sent To  
Notes
2006-04-25 00:00:00************UNSAT ***************
  
 1) NOTE: PLEASE SEE PLANS WHICH WERE
 REDLINED TWICE BEFORE THIS REVIEW WHICH
 REQUESTED KITCHENS IN OTHER THAN
 DWELLING UNITS TO MEET 210.8B3
 PLEASE ADJUST.
  
 2) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 PLEASE SEE AN "IT" ROOM WAS NOT
 IDENTIFIED ON ORIG ELECTRICAL PLANS.
 PLEASE SEE ALL OF NEC 645, NFPA-75 FOR
 MIN REQUIRMENTS.
 PLEASE SEE 645.10,645.5,645.2.
 PLEASE ADJUST ACCORDINGLY.
  
 3) NOTE: PLEASE SEE RISER WHICH INDICATE
 ONE RISER OF 3-3/0'S OR 500MCM'S, WHICH
 IS ALSO NOTED AS BEING DONE BY FPL, OR
 MAYBE BY FPL.
 PLEASE KNOW, THE WH, RISER, ETC UP TO
 THE SERVICE ENTRANCE DRIP LOOP BELONGS
 TO THE OWNER OF THE BUILDING, NOT FPL.
 FPL WILL NOT BE INSTALLING THIS RISER.
 PLEASE SPECIFY WHICH OPTION FOR RISER
 WAS OR IS BEING INSTALLED.
 THIS WAS REDLINED ON PREVIOUS PLANS.
 215.5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 20:19 Rev Time 0.25
Received By dpalmer Date 2005-09-03 Time 20:10 Sent To  
Notes
2005-09-03 00:00:00********* NOTES REDLINED *********
  
 1)NOTE: PLEASE SEE PREVIOUS REVIEW,
 PLANS WERE REDLINED FOR 2002 NEC 210.8B3
 WHICH REQUIRES ALL 15A& 20A RECEPTS IN
 KITCHEN/LUNCH RM AREA TO BE GFI OR GFI
 PROTECTED CIRCUITS.
  
 THIS WAS RED LINED PLANS ONCE AGAIN.
 PLEASE KNOW, IF PLANS COME BACK DURING
 CONTRUCTION FOR ANY OTHER REVISIONS,
 PLEASE MAKE CORRECTIONS.
  
 NEW SHEETS E-1 AND E-2 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 15:35 Rev Time 0.75
Received By dpalmer Date 2005-07-01 Time 10:34 Sent To  
Notes
2005-07-01 00:00:00**** REDLINED PLANS **********
  
  
  
 PLEASE SEE 2002 NEC 210.8B3 WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-02 Cont ID  
Sent By mwennerg Date 2006-06-02 Time 10:33 Rev Time 0.00
Received By mwennerg Date 2006-06-02 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 14:22 Rev Time 0.00
Received By mcarsill Date 2005-09-12 Time 14:22 Sent To  
Notes
2005-09-12 00:00:001. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2005-07-11 Time   Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 11:27 Sent To  
Notes
2005-07-11 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3. ON PAGE M1 THERE APPEARS TO BE A/C
 DUCTWORK WITHIN THE EXIT STAIR. IF SO,
 NOT ALLOWED BY CODE. PLEASE EXPLAIN.
  
 4. PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS.
  
 5. TEN (10) INCH TREADS SHOWN ON PAGE
 A-4. TEN INCH TREADS ARE NOT ALLOWED
 FOR NEW STAIRS.
  
 6. FIRE ALARM SYSTEM SHALL BE CLASS A OR
 FULLY ADDRESSABLE.
  
 7. ELEVATION DRAWINGS DO NOT DISPLAY
 BUILDING ADDRESS. BUILDING ADDRESS SHALL
 BE A MINIMUM OF AT LEAST 6" HIGH
 NUMBERS.
  
 8. WHAT FIRE RATING IS PRESENT FOR THE
 STAIRWELL DOOR LOCATED ON THE SECOND
 LEVEL NEAR FAX PRINTER AREA.
  
 9. PLEASE ILLUSTRATE FIRE EXTINGUISHER
 LOCATIONS.
  
 10. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER.
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 15:01 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 15:01 Sent To  
Notes
2006-06-22 00:00:00TO "COMM" BD#4-REV
2006-06-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 09:29 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 09:29 Sent To  
Notes
2006-06-02 00:00:006/2/06-FROM "COMM" BD#26-ROUTED TO "F"
2006-04-18 00:00:00TO "COMM" BD#26
2006-03-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-18 Time 10:09 Rev Time 0.00
Received By adarroug Date 2005-10-18 Time 10:09 Sent To P
Notes
2005-10-18 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-25 Cont ID  
Sent By adarroug Date 2005-08-25 Time 09:37 Rev Time 0.00
Received By adarroug Date 2005-08-25 Time 09:36 Sent To  
Notes
2005-08-29 00:00:00TO "COMM" BD#53
2005-08-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-07-24 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2005-06-14 Time 17:34 Sent To  
Notes
2005-06-20 00:00:00COMM BOARD #48
  
2005-06-14 00:00:00WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-08-08 Cont ID  
Sent By pkrauss Date 2006-08-08 Time 10:09 Rev Time 0.00
Received By pkrauss Date 2006-08-08 Time 10:09 Sent To  
Notes
2006-08-08 00:00:00EQUIPMENT SCHEDULE / EQUIPMENT CHANGE
 FROM CARRIER TO TRANE / 13 SEER

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-07-05 Cont ID  
Sent By tgordon Date 2006-07-05 Time 12:12 Rev Time 0.30
Received By tgordon Date 2006-07-05 Time 12:12 Sent To  
Notes
2006-07-05 00:00:00REVISION TO MECH. PLANS PAGE M1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-10 Cont ID  
Sent By tgordon Date 2006-05-10 Time 10:21 Rev Time 0.45
Received By tgordon Date 2006-05-10 Time 10:21 Sent To  
Notes
2006-05-10 00:00:00*** PROVISO ***
 1) BATHROOM EXHAUST APPEARS TO TERMINATE
 BELOW THE FRESH AIR INTAKE TO AHU#1,
 PLEASE COMPLY WITH 2001 FBC/M 501.3 .
 2) BATHROOM EXHAUST FANS REQUIRE 100
 CFM'S EACH. NEED 50 CFM,S PER WATER
 CLOSET OR URINAL, PER 2001 FBC/M 403.3 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-21 Cont ID  
Sent By pkrauss Date 2005-11-21 Time 14:10 Rev Time 0.40
Received By pkrauss Date 2005-11-21 Time 14:05 Sent To  
Notes
2005-11-21 00:00:00PROVISO:
 1. PLAN SHEET M-1 PER 2001 FBC(M)501.3,
 EXHAUST SHALL TERMINATE AT A LOCATION AS
 NOT TO BE READILY DRAWN IN BY THE
 VENTILATING SYSTEM.EXHAUST TERMINATION
 APPEAR TO TERMINATE UNDERNEATH THE FRESH
 AIR INTAKE TO AHU-1.PLEASE REVISE
 PLANS PRIOR TO INSPECTION.
  
 2. FAN SHUTDOWN REQUIRED FOR AHU-1 PER
 2001 FBC(M)606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-20 Cont ID  
Sent By pkrauss Date 2005-07-20 Time 06:48 Rev Time 0.45
Received By pkrauss Date 2005-07-20 Time 06:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-07-26 Cont ID  
Sent By pschmitz Date 2006-07-26 Time 14:58 Rev Time 0.00
Received By pschmitz Date 2006-07-26 Time 14:58 Sent To  
Notes
2006-07-26 00:00:00AS BUILT FOR PLUMBING

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-01 Cont ID  
Sent By kstevens Date 2006-06-01 Time 18:22 Rev Time 0.00
Received By kstevens Date 2006-05-31 Time 19:27 Sent To  
Notes
2006-06-01 00:00:00REVISION OK - SHTS P-1 & P-3. - SHTS P-2
 & P-4 NO REVISIONS NOTED.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-11-21 Cont ID  
Sent By jleech Date 2005-11-21 Time 13:41 Rev Time 1.00
Received By jleech Date 2005-11-21 Time 13:41 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-10-18 Cont ID  
Sent By jleech Date 2005-10-18 Time 13:22 Rev Time 1.00
Received By jleech Date 2005-10-18 Time 13:21 Sent To  
Notes
2005-10-18 00:00:00DENIED;
 1. PLEASE SHOW TURNING RADIUS IN LADIES
 TOILET ROOM. (THIRD REQUEST)
 2.WOMAN'S ROOM TOILET STALL IS TO SMALL.
 REQUIRED TO BE 30" X 60" SEE FBC-2001
 PLUMBING SEC. 405.3.1 AND FIG. 405.3.1.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-01 Cont ID  
Sent By jleech Date 2005-10-01 Time 14:01 Rev Time 1.00
Received By jleech Date 2005-10-01 Time 14:01 Sent To  
Notes
2005-10-01 00:00:00DENIED;
 1. SHEET D-1 ADD TO NOTES DEAD ENDS TO
 BE 2' OR LESS, FIELD INSPECTION
 REQUIRED.
 2.WOMEN'S ROOM; SHOW THE CLEAR FLOOR
 SPACE FOR THE TOILET ROOM IN THE TOILET
 ROOM NOT IN THE STALL.
 3.BREAK SINK DOES NOT COMPLY WITH FBC
 CHAPTER 11 SEC. 11-4.24.3 KNEE CLEARANCE
 SHALL BE 19" UNDERNEATH SINK. LOWER
 FRONT PANEL CAN NOT BE INSTALLED AS
 DRAWN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-12 Cont ID  
Sent By kstevens Date 2005-07-12 Time 08:21 Rev Time 1.12
Received By kstevens Date 2005-07-12 Time 08:21 Sent To  
Notes
2005-07-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT D-1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5 - ALL CAPPED
 OFF PIPING SHALL BE FIELD INSPECTED
 PRIOR TO COVERING.
 2. SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE SINK IN THE LUNCHROOM. SECTION
 11-4.24.5. SINK SHALL BE CENTERED ON THE
 30" WIDTH.
 3. SHT A-1 SHOW THE CLEAR FLOOR SPACE
 FOR THE TOILET ROOMS IN THE TOILET ROOM,
 NOT THE STALL. SECTION 11-4.22.3
 4. SHT A-5 BREAKROOM SINK SHALL BE
 ACCESSIBLE. PROVIDE THE FOLLOWING
 INFORMATION ON DETAIL 3/A5 TO SHOW
 COMPLIANCE:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE SHALL BE
 PROVIDED TO ALLOW FORWARD APPROACH AND
 SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. - CABINET DOORS SHALL NOT BE
 IN THE CLEAR FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 5. SHT P2 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED, DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  
  
  