Plan Review Details - Permit 05061000
Plan Review Stops For Permit 05061000
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-15 Cont ID  
Sent By alange Date 2005-08-15 Time 07:55 Rev Time 0.66
Received By alange Date 2005-08-15 Time 07:55 Sent To E
Notes
2005-08-15 00:00:00DENIED
  
 2. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.NOTE: ALL PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.CLEARLY SHOW EXISTING SQUARE FOOTAGE
 AND NEW SQUARE FOOTAGE. COVERED PORCH
 TURNED INTO LIVING SPACE?
  
 7.SUBMIT TWO COPIES OF ENERGY CALCS
 COMPLYING WITH FBC CHAPTER 13 TABLE 600
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-25 Cont ID  
Sent By alange Date 2005-07-25 Time 09:28 Rev Time 1.00
Received By alange Date 2005-07-25 Time 09:09 Sent To  
Notes
2005-07-25 00:00:00DENIED
  
 1.SCOPE OF WORK ON APPLICATION DOES
 NOT REFLECT WORK BEING DONE ON PLANS.
 REVISE PROJECT DETAIL ON APPLICATION.
  
 2. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:FLAT ROOF, SHINGLE ROOF,
 OVERHEAD DOOR, IMPACT PROTECTION AND
 STRAPS AND TIE-DOWNS.
 NOTE: ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE APPROVALS
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 5.SUBMIT A ROOF SHEATHING NAILING
 SCHEDULE SHOWING NAILING COMPLYING WITH
 FBC 2306.1 WPB AMMENDMENTS.
  
 6.CLEARLY SHOW EXISTING SQUARE FOOTAGE
 AND NEW SQUARE FOOTAGE.
  
 7.SUBMIT TWO COPIES OF ENERGY CALCS
 COMPLYING WITH FBC CHAPTER 13.
  
 8.SHOW HOW MANY SQUARE FEET OF
 SHINGLES ARE BEING REPLACED.
  
 9.SHOW METHOD OF SLAB TIE IN FROM NEW
 TO EXISTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-15 Cont ID  
Sent By btrobaug Date 2005-08-15 Time 08:53 Rev Time 0.50
Received By btrobaug Date 2005-08-15 Time 08:37 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-28 Cont ID  
Sent By btrobaug Date 2005-06-28 Time 07:28 Rev Time 0.50
Received By btrobaug Date 2005-06-28 Time 06:58 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 18:13 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 18:13 Sent To B
Notes
2005-08-09 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 14:47 Rev Time 0.00
Received By shill Date 2005-06-14 Time 14:47 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-11 Cont ID  
Sent By prafter Date 2005-07-11 Time 11:26 Rev Time 0.50
Received By prafter Date 2005-07-11 Time 11:26 Sent To B
Notes
2005-07-11 00:00:00MECH. PLAN REVIEW.
  
 A/C CONTRACTOR TO SUBMIT PLANS AT
 PERMIT TIME.
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By mmclean Date 2005-08-22 Time 17:36 Rev Time 0.00
Received By mmclean Date 2005-08-22 Time 17:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By mmclean Date 2005-06-21 Time 17:33 Rev Time 0.00
Received By mmclean Date 2005-06-21 Time 17:33 Sent To I
Notes
2005-06-21 00:00:00DENIED,
 1.NEED TO PROVIDE TWO COPY OF SURVEY
 SHOWING THE SETBACKS OF THE EXISTING
 STRUCTURE.
 2. SITEPLAN IS INCOMPLETE, DOES NOT
 PROVIDE INFORMATION NEEDED TO COMPLETE
 REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720