Plan Review Details - Permit 05060925
Plan Review Stops For Permit 05060925
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-13 Cont ID  
Sent By rmcdouga Date 2005-09-13 Time 08:49 Rev Time 0.00
Received By jleahy Date 2006-02-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-06 Cont ID  
Sent By rmcdouga Date 2005-09-06 Time 12:39 Rev Time 0.00
Received By rmcdouga Date 2005-09-06 Time 12:39 Sent To  
Notes
2005-09-06 00:00:00NEEDS TO PAY IMPACT FEES AND HAVE PLANS
 STAMPED BY THE COUNTY BEFORE THE PERMIT
 IS ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-23 Cont ID  
Sent By rmcdouga Date 2005-08-23 Time 09:08 Rev Time 0.00
Received By rmcdouga Date 2005-08-23 Time 09:08 Sent To  
Notes
2005-08-23 00:00:00DENIED
  
 1) PLEASE REVISE THE ANCHOR SCHEDULE ON
 A5. THE MAXIMUM UPLIFT FOR A USP HTA 16
 CONNECTOR IS 1500#. THE DOUBLE HTA 16
 HAS A MAXIMUM UPLIFT OF 3000#. THESE ARE
 THE VALUES LISTED IN THE 2005 USP
 CATALOG AND DO NOT INCLUDE THE ONE THIRD
 STRESS INCREASE ON THE STEEL
 CALCULATIONS WHICH IS NOT ALLOWED BY THE
 2001 FBC. SEE FBC 1609.4.3. SEE ITEM #6
 ON PREVIOUS REVIEW.
  
 2) THE DESIGN PRESSURES REQUIRED BY THE
 PLANS FOR THE SMALL GARAGE DOOR EXCEED
 THE DESIGN PRESSURES GIVEN IN THE
 PRODUCT APPROVAL THAT WAS SUBMITTED.
 SUBMIT PRODUCT WITH ADEQUATE DESIGN
 PRESSURES. SEE COMMENT # 8 FROM PREVIOUS
 REVIEW.
  
 3) THE PRODUCT APPROVALS SUBMITTED FOR
 THE FIXED GLASS WINDOWS ARE FOR
 NON-IMPACT RESISTANT GLAZING. THE PLANS
 SPECIFY IMPACT GLAZING FOR ALL WINDOWS.
 SUBMIT PRODUCT APPROVALS FOR IMPACT
 WINDOWS OR REVISE PLANS AND SUBMIT STORM
 PANEL PRODUCT APPROVALS, KEY PLANS AND
 INSTALLATION SCHEDULES.
  
 4)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-15 Cont ID  
Sent By rmcdouga Date 2005-07-15 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2005-07-15 Time 07:16 Sent To  
Notes
2005-07-15 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) ITEM #4 IN THE DOOR SCHEDULE ON A2 IS
 LISTED AS A SLIDING GLASS DOOR AND ON
 THE PLAN IT IS DRAWN AS A DOUBLE
 OUTSWING FRENCH DOOR AT THE FAMILY ROOM.
  
 3) ITEM #16 IN THE SCHEDULE IS ANOTHER
 SLIDING GLASS DOOR AND THERE AREN'T ANY
 SG DOORS ON THE PLANS. PLEASE CORRECT.
 ALSO REMOVE THE PRODUCT APPROVALS FOR
 SLIDING GLASS DOORS FROM THE SUBMITTALS
 AS IT DOES NOT APPLY TO THIS PROJECT.
  
 4) PLEASE UPDATE DESIGN CRITERIA ON A5.
 THE REFERENCED STANDARDS IN THE 2OO1 FBC
 ARE ACI 318-02 AND ACI530.1-02. SEE FBC
 CHAPTER 35.
  
 5) ON A5 THERE IS A CONNECTOR AT THE
 COVERED PATIO WITH A #12 TAG. THERE IS
 NO #12 SPECIFIED IN THE ANCHOR LEGEND.
 PLEASE CLARIFY.
  
 6) PLEASE REVISE THE ANCHOR SCHEDULE ON
 A5, AS SEVERAL CONNECTOR UPLIFTS
 SPECIFIED ARE IN ERROR. THE MAXIMUM
 UPLIFT FOR HTA 16 IS 1500#. THE DOUBLE
 HTA 16S HAVE A MAXIMUM UPLIFT OF 3000#.
 THE MAX. UPLIFTS FOR THE 'USP' RT22T AND
 RT20T ARE 1225#. SEE 2005 USP CATALOG.
  
 7) PROVIDE STRUCTURAL DETAILS OF THE
 CUPOLA ABOVE THE MASTER BEDROOM. SPECIFY
 ALL CONNECTORS, EXTERIOR AND INTERIOR
 FINISHES, STUD SIZE AND SPACING,
 INSULATION, ETC.
  
 8) THE DESIGN PRESSURES REQUIRED BY THE
 PLANS FOR THE SMALL GARAGE DOOR EXCEED
 THE DESIGN PRESSURES GIVEN IN THE
 PRODUCT APPROVAL THAT WAS SUBMITTED.
  
 9) SUBMIT PRODUCT APPROVALS FOR THE
 HOLLOW METAL DOOR AT THE MECHANICAL
 ROOM, # 17 IN THE SCHEDULE.
  
 10) SUBMIT PRODUCT APPROVALS FOR THE
 STORE FRONT WINDOWS (H,I,AND D IN THE
 SCHEDULE).
  
 11) ITEM #5 IN THE DOOR SCHEDULE IS
 SPECIFIED AS A STORE DOOR. PLEASE
 CLARIFY AND SUBMIT THE APPROPRIATE
 PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-05 Cont ID  
Sent By jleahy Date 2006-02-05 Time 11:14 Rev Time 0.45
Received By jleahy Date 2006-02-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-18 Cont ID  
Sent By btrobaug Date 2005-08-18 Time 08:01 Rev Time 0.50
Received By btrobaug Date 2005-08-18 Time 07:37 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By btrobaug Date 2005-06-22 Time 18:17 Rev Time 0.50
Received By btrobaug Date 2005-06-22 Time 18:00 Sent To M
Notes
2005-06-22 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER SHOWS PANELS WITH MAIN
 BREAKERS, PLAN SHOWS MAIN DISCONNECTS
 OUTSIDE AND PANELS INSIDE. PLEASE
 CLARIFY.
  
 2} PANEL "C" IS FED FROM PANEL "B" ON
 THE RISER, BUT OUT OF PANEL "A"ON THE
 SCHEDULE.
  
 3} INDICATE THE AIC RATING OF THE
 SERVICE EQUIPMENT PER 110.9 & 10.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status   Date   Cont ID  
Sent By adarroug Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 16:26 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 16:26 Sent To B
Notes
2005-08-29 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 09:15 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 09:15 Sent To E
Notes
2005-08-16 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 14:38 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 14:38 Sent To Z
Notes
2005-08-09 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-22 Cont ID  
Sent By adarroug Date 2005-06-22 Time 13:28 Rev Time 0.00
Received By adarroug Date 2005-06-22 Time 13:28 Sent To E
Notes
2005-06-22 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-14 Cont ID  
Sent By mjacobs Date 2005-06-14 Time 06:45 Rev Time 0.00
Received By mjacobs Date 2005-06-14 Time 06:45 Sent To Z
Notes
2005-06-14 00:00:00TO 'Z' BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By pkrauss Date 2005-08-22 Time 06:32 Rev Time 0.35
Received By pkrauss Date 2005-08-22 Time 06:32 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-05 Cont ID  
Sent By pkrauss Date 2005-07-05 Time 12:12 Rev Time 0.40
Received By pkrauss Date 2005-07-05 Time 11:50 Sent To B
Notes
2005-07-05 00:00:00DENIED:
 1.PROVIDE COMBUSTION AIR CALCULATIONS
 ON THE LAUNDRY ROOM WITH THE GAS DRYER
 IN ACCORDANCE WITH 2001 FBC(M) CHAPTER
 7.
  
 2.PER 2001 FBC CHAPTER 13 SUB-SECTION
 609.1.ABC.1 #2, NO VENTILATION OR A/C
 MAKE-UP AIR SHALL BE PROVIDED TO
 CONDITIONED SPACE FROM ATTICS OR
 ROOFTOPS.LAUNDRY ROOM INDICATES VTR
 BUT DOES NOT INDICATE IF THIS IS FOR THE
 COMBUSTION AIR MAKE-UP, PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-25 Cont ID  
Sent By adarroug Date 2006-01-27 Time 14:04 Rev Time 0.33
Received By jleech Date 2005-06-25 Time 06:23 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By mmclean Date 2005-08-11 Time 18:38 Rev Time 0.00
Received By mmclean Date 2005-08-11 Time 18:38 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By mmclean Date 2005-06-21 Time 14:33 Rev Time 0.00
Received By mmclean Date 2005-06-21 Time 14:33 Sent To I
Notes
2005-06-21 00:00:00DENIED,
 1. MUST REMOVE THE GAS COOKTOP FROM
 PLANS - OUTSIDE BALLARD ROOM.(ONLY ONE
 COOKING FACILITY IS ALLOWED IN SF7).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720