Plan Review Details - Permit 05060920
Plan Review Stops For Permit 05060920
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-01-11 Cont ID  
Sent By shill Date 2007-01-11 Time 18:20 Rev Time 0.00
Received By shill Date 2007-01-11 Time 18:20 Sent To  
Notes
2007-01-11 18:22:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2001
  
 1.)THE SHUTTERS DO NOT ADDRESS THE ISSUE OF DESIGN
 PRESSURE FOR THE LOUVER VENTS.
  
 2.)THE OVERHEAD DOOR HAS A LIMITATION OF +-37,
 OPENINGS HAVE A DESIGN PRESSURE OF -39.PLEASE
 ADDRESS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-01-11 Cont ID  
Sent By shill Date 2007-01-11 Time 18:08 Rev Time 0.00
Received By shill Date 2007-01-11 Time 18:08 Sent To  
Notes
2007-01-11 18:09:08REVISION; NEW PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-15 Cont ID  
Sent By shill Date 2006-09-11 Time 08:11 Rev Time 0.00
Received By shill Date 2006-09-15 Time 09:08 Sent To  
Notes
2006-09-15 00:00:00FIRE SPRINKLER INFORMATION 06081983

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-20 Cont ID  
Sent By shill Date 2006-06-20 Time 11:14 Rev Time 0.00
Received By shill Date 2006-06-20 Time 11:14 Sent To ENG
Notes
2006-06-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS OUTSTANDING FROM PREVIOUS
 REVIEWS, NUMBERING REMAINING THE SAME
 FOR CONSITENCY:
  
 4.)PROVIDE A SUREVY OF THIS PROPERTY
 SO THAT FBC TABLE 600 COMPLIANCE CAN BE
 DETERMINED. (1ST AND 2ND REVIEWS)
  
 3RD REVIEW - ONE HAS BEEN PROVIDED, BUT
 CONFLICTS WITH THE ARCHITECTURAL PLAN.
 EXPLAIN WHY A SIGNED, SEALED SURVEY
 SHOWS A DISTANCE FROM THE PROPERTY LINE
 OF 3.4' IN THE REAR, BUT THE SITE PLAN
 PREPARED BY A.GARGUILIO, PE SHOWS THE
 BUILDING AS LESS THAN 3' FROM THE
 PROPERTY LINE, REQUIRING 0 OPENINGS.
 THIS ISSUE SHOULD HAVE BEEN ADDRESSED
 PRIOR TO RESUBMITTAL.CODE COMPLIANCE
 CANNOT BE DETERMINED DUE TO INCONSISTENT
 INFORMATION.
  
 SEE FBC TABLE 600.IF THE BUILDING IS
 LESS THAN 3', 3 HOUR WALL REQUIRED FOR
 TYPE V 1 HR PROTECTED, 2 HOUR FOR TYEP V
 UNPROTECTED.
  
 6.)YOU HAVE DECLARED TYPE IV
 CONSTRUCTION.SEE FBC606.YOU HAVE
 COMBUSTIBLE WALLS AND ROOF, SO THIS IS
 NOT A TYPE IV. (1ST AND 2ND REVIEW).
  
 3RD REVIEW - YOU HAVE NOW DECLARED A
 TYPE V, 1 HOUR PROTECTED.HOW ARE THE
 STRUCTURAL ELEMENTS PROTECTED FBC TABLE
 600?THE DETAILS PROVIDED ARE NOT
 COMPLIANT FOR A 1 HOUR PROTECTED
 BUILLDING.
  
 SEE ALSO COMMENT 4 ABOVE.CODE
 COMPLIANCE CANNOT BE DETERMINED DUE TO
 INSUFFICIENT/CONFLICTING INFORMATION ON
 THE PLAN.
  
 7.)C1 ALSO STATES THAT 1 HOUR
 PROETECTION REQUIRED.SHOW COMPLIANCE,
 EITHER BY ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709. (1ST & 2ND REVIEWS)
  
 3RD REVIEW - NOT ADDRESSED.
  
 8.)YOU DECLARE AN OCCUPANT LOAD OF 71.
 HOW HAVE YOU ARRIVED AT THIS NUMBER?
 (1ST REVIEW)
  
 2ND REVIEW - NOW THE OCCUPANCY IS SHOWN
 AS 5; 1500/300.THE BUILDING IS 11,131
 SF.SEE FBC1003.1, FBC TABLE 1003.1.
  
 3RD REVIEW - NOT PROPERLY ADDRESSED.
 OCCUPANCY IS NOW "ONE EMPLOYEE".IT IS
 UNCLEAR AS TO HOW AN 11K+ BUILDING CAN
 HAVE AN OCCUPANCY OF ONE.
  
 13.)PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 ROOF/WALL PANELS
 METAL DOOR
 LOUVERS
  
 2ND & 3RD REVIEWS - SUBMIT THE
 INSTALLATION INSTRUCTIONS FOR THE
 BENCHMARK DOORS (STATE PRODUCT APPROVAL
 SUBMITTED).
  
 PSUBMIT STATE PRODUCT APPROVALS FOR THE
 ROLLUP DOOR, SINGLE HUNG WINDOW AND
 FIXED WINDOW, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 3RD REVIEW - THE LOCAL PRODUCT APPROVAL
 APPLICATION IS INCOMPLETE.THERE IS NO
 QUALITY ASSURANCE ENTITY ON THE
 APPLICATION.THE LOCAL PRODUCT APPROVAL
 CANNOT BE ISSUED WITHOUT A QUALITY
 ASSURANCE PROGRAM, FAC9B72.UNTIL PROOF
 OF A PROGRAM IS PROVIDED, A REVIEW WILL
 NOT BE DONE ON THE APPLICATION.SEE THE
 VALIDATION CHECKLIST AND FAC9B72 AT
 WWW.FLORIDABUILDING.ORG, PRODUCT
 APPROVAL.***THE LOCAL PRODUCT APPROVAL
 APPLICATION MAY BE SUBMITTED PRIOR TO
 RESUBMITTAL OF THE PLANS***
  
 14.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-4.1.3.IT APPEARS THAT THERE IS A
 STEP UP INTO THE BUILDING.SHOW
 ELEVATIONS. (1ST REVIEW)
  
 2ND REVIEW - NOT ADDRESSED.THE
 BUILDING ELEVATIONS STILL SHOW A STEP
 INTO THE MAIN ENTRANCE.PROVIDE
 FINISHED FLOOR ELEVATIONS.
  
 3RD REVIEW - NOT ADDRESSED.PLAN STILL
 SHOWS STEPS AT THE FRONT DOOR.THE
 ROLLUP DOORS ARE NOT COMPLIANT AS AN
 ACCESSIBLE ENTRY.
  
 15.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, FBC11-4.13.9.(1ST
 REVIEW).
  
 2ND & 3RD REVIEWS - NOT ADDRESSED.
  
 16.)ACCESSIBLE PARKING REQUIRED,
 FBC11-4.1.2(5)(A). (1ST & 2ND REVIEWS)
  
 3RD REVIEW - THIS WAS ADDED TO THE PLAN,
 BUT DOES NOT HAVE ALL DIMENSIONS,
 SIGNAGE, ACCESS AISLE.IS THE
 ACCESSIBLE ROUTE THROUGH THE SIDE DOOR?
 NO ELEVATION CHANGE INFORMATION PROVIDED
 AS REQUESTED.
  
  
 19.)SEE FBC1012.THE TWO OPENINGS IN
 THE FRONT OF THE BUILDING ARE NOT
 COMPLIANT WITH THE REQUIREMENTS FOR
 EGRESS DOORS.ADDRESS.
  
 3RD REVIEW - EXIT LIGHTS SHOWN AT THE
 ROLLUP DOORS.NOT PROPERLY ADDRESSED.
  
 20.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED ON THE NEXT
 REVIEW AS REQUIRED BY FLORIDA STATUTE.
  
 3RD REVIEW - 4X FEE AGAINST A. GARGUILO,
 PE APPLIED TO PERMIT.
  
 21.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, INCLUDING ALL OF THE
 SWING DOORS AND ALSO THE ROLLUP DOORS
 FOR THE STORAGE UNITS FBC11-4.13.9.
  
 3RD REVIEW - NOT ADDRESSED.
  
 NEW COMMENTS:
  
 22.)(PROVIDING MORE DETAIL IN REGARDS
 WHAT IS REQUIRED TO SHOW COMPLIANCE WITH
 ITEM 14.) PROVIDE HEIGHT FOR THE FLOOR
 MOUNTING CHANNEL AT THE DOOR, STORAGE
 UNITS.THERE IS TO BE AN ACCESSIBLE
 ROUTE INTO THE STORAGE UNITS,
 FBC11-4.1.1(1)(A), FBC11-4.1.2(2).THE
 FLOOR PLAN DOES NOT SHOW A MAN DOOR,
 ONLY A ROLLUP DOOR, BUT A7 SHOWS A SWING
 DOOR AND A ROLLUP DOOR.DOORS ARE TO
 COMPLY WITH FBC11-4.13.AS THE DOORS
 ARE NOT SHOWN ON THE FLOOR PLAN, AND THE
 DETAILS ON A7 DO NOT SHOW DOOR SWING
 INFORMATION, MANEUVERING CLEARANCE
 CANNOT BE DETERMINED.
  
 A SWING DOOR IS REQUIRED FOR EGRESS,
 FBC1027.2, FBC1012.1.2.
  
 23.)THE PLANS NOW STATE CODE SUMMARY
 2004, FORMERLY STATED FBC 2001.
 GOVERNING CODE AT THE TIME OF
 APPLICATION WAS FBC2001.TO CHANGE
 CODE, SUBMIT A NEW PERMIT APPLICATION
 AND THE PLANS WILL BE REVIEWED UNDER
 FBC2004.
  
 24.)THE ACCESSIBLE BATHROOM DOOR LACKS
 THE MANEUVERING CLEARANCE REQUIRED BY
 FBC11-4.13.6, FBC11 FIGURE 25.
  
 25.)HOW DOES THE GATE OPEN?SHOW
 REACH RANGE, FBC11-4.2.5, FBC1104.2.6.
  
 26.)CHANGES WERE NOT CLOUDED.THIS
 REQUIRED A COMPLETE NEW REVIEW.TO
 EXPEDITE PLAN REVIEW, CLOUD ALL CHANGES.
  
 27.)A SET OF THE PLANS HAS BEEN
 RETAINED.THEY WILL BE FORWARDED TO
 FBPE WITH A COMPLAINT.
  
 28.)DOORS ARE SHOWN ENCROACHING THE
 PROPERTY LINE, SEE FBC3203.
  
 29.)PROVIDE DIMENSIONS FOR THE AWNING,
 FBC3204.3.
  
 30.)THIS IS A 25-50% IMPROVEMENT AS
 PER ARCHITECT'S LETTER AND APPRAISAL,
 FBC3401.2.2.
  
 31.)DECLARE A SUBCLASSIFICATION,
 FBC312.2.
  
 32.)A2 NOW HAS REFERENCE TO SHUTTERS,
 ALSO SHOWS IMPACT.REMOVABLE SHUTTERS
 ON COMMERCIAL BUILDINGS ARE TO BE
 APPROVED BY THE BUILDING OFFICIAL.
 SUBMIT A PLAN FOR INSTALLATION, SEE
 ATTCHED IMPLEMENTATION STANDARD, ITEM
 13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-10 Cont ID  
Sent By shill Date 2005-11-10 Time 09:43 Rev Time 0.00
Received By lmartine Date 2006-06-01 Time 10:55 Sent To  
Notes
2006-06-01 00:00:00GAVE TO MICHELLE, TO GIVE TO JOHN ROACH
2005-11-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS REVIEW, NUMBERING
 REMAINING THE SAME FOR CONSISTENCY
  
 3.)THIS IS AN OVER 50% IMPROVEMENT AND
 THE REQUIREMENTS OF FBC3401.7.2.6 APPLY.
 SOME OF THE COMMENTS RELATE TO THIS CODE
 SECTION.
  
 4.)PROVIDE A SURVEY OF THIS PROPERTY
 SO THAT FBC TABLE 600 COMPLIANCE CAN BE
 DETERMINED.
  
 NOT ADDRESSED
  
 6.)YOU HAVE DECLARED TYPE IV
 CONSTRUCTION.SEE FBC606.YOU HAVE
 COMBUSTIBLE WALLS AND ROOF, SO THIS IS
 NOT A TYPE IV.
  
 NOT ADDRESSED
  
 7.)C1 ALSO STATES THAT 1 HOUR
 PROTECTION REQUIRED.SHOW COMPLIANCE,
 EITHER BY ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709.
  
 NOT ADDRESSED
  
 8.)YOU DECLARE AN OCCUPANT LOAD OF 71.
 HOW HAVE YOU ARRIVED AT THIS NUMBER?
  
 NOW THE OCCUPANCY IS SHOWN AS 5;
 1500/300.THE BUILDING IS 11,131 SF.
 SEE FBC1003.1, FBC TABLE 1003.1.
  
 12.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 SEE ITEM 13 BELOW.
  
 13.)PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 ROOF/WALL PANELS
 METAL DOOR
 LOUVERS
  
 SUBMIT THE INSTALLATION INSTRUCTIONS FOR
 THE BENCHMARK DOORS (STATE PRODUCT
 APPROVALS SUBMITTED)
  
 SUBMIT STATE PRODUCT APPROVALS FOR THE
 ROLLUP DOOR, SINGLE HUNG WINDOW AND
 FIXED WINDOW
  
 PRODUCT APPROVALS REQUIRED FOR THE ROOF
 AND WALL PANELS, NONE SUBMITTED
  
 14.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-4.1.3.IT APPEARS THAT THERE IS A
 STEP UP INTO THE BUILDING.SHOW
 ELEVATIONS.
  
 NOT ADDRESSED.THE BUILDING ELEVATIONS
 STILL SHOW A STEP INTO THE MAIN
 ENTRANCE.PROVIDE FINISHED FLOOR
 ELEVATIONS.
  
 15.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, FBC11-4.13.9.
  
 NOT ADDRESSED.
  
 16.)ACCESSIBLE PARKING REQUIRED,
 FBC11-4.1.2(5)(A).
  
 NOT ADDRESSED.
  
 17.)A NOTE ON THE PLAN STATES THAT
 FLOOR RAFTERS WILL REMAIN, BUT
 PARTITIONS ON THE SECOND FLOOR WILL BE
 REMOVED.C1 STATES THAT THIS IS A TWO
 STORY BUILDING.WHERE IS THE SECOND
 FLOOR PLAN AND HOW DO YOU GET TO THE
 SECOND FLOOR?
  
 THE NOTE ON C1 NOW STATES THAT THIS IS A
 ONE STORY BUILDING, BUT A1 SHOWS A FRAME
 2ND STORY.
  
 18.)FBC*1804.1.7, FINISH GRADE SHALL
 BE SLOPED AWAY FROM THE FOUNDATION FOR
 DRAINAGE, SEE BB-A5.
  
 NOT ADDRESSED.
  
 NEW COMMENT:
  
 19.)SEE FBC1012.THE TWO OPENINGS IN
 THE FRONT OF THE BUILDING ARE NOT
 COMPLIANT WITH REQUIREMENTS FOR EGRESS
 DOORS.ADDRESS.
  
 20.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED ON THE NEXT
 REVIEW AS REQUIRED BY FLORIDA STATUTE.
  
 21.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, INCLUDING ALL OF THE
 SWING DOORS AND ALSO THE ROLLUP DOORS
 FOR THE STORAGE UNITS FBC11-4.13.9.
  
 A SET OF THE PLANS HAS BEEN RETAINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By shill Date 2005-08-08 Time 07:56 Rev Time 3.00
Received By shill Date 2005-08-08 Time 07:56 Sent To  
Notes
2005-08-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.THIS PROJECT INVOLVES A
 CHANGE OF OCCUPANCY.233-5025
  
 3.)THIS IS AN OVER 50% IMPROVEMENT AND
 THE REQUIREMENTS OF FBC3401.7.2.6 APPLY.
 SOME OF THE COMMENTS RELATE TO THIS CODE
 SECTION.
  
 4.)PROVIDE A SURVEY OF THIS PROPERTY
 SO THAT FBC TABLE 600 COMPLIANCE CAN BE
 DETERMINED.
  
 5.)MERCANTILE OCCUPANCY IS DECLARED ON
 C1, AS WELL AS SINGLE TENANT.IF THERE
 IS ONLY ONE TENANT, WHY ARE THERE
 MULTIPLE UNITS AND BAYS?PLEASE PROVIDE
 SOME INFORMATION IN REGARDS TO THE
 INTENDED USE OF THE BUILDING.FBC312,
 FBC310.
  
 6.)YOU HAVE DECLARED TYPE IV
 CONSTRUCTION.SEE FBC606.YOU HAVE
 COMBUSTIBLE WALLS AND ROOF, SO THIS IS
 NOT A TYPE IV.
  
 7.)C1 ALSO STATES THAT 1 HOUR
 PROTECTION REQUIRED.SHOW COMPLIANCE,
 EITHER BY ASSEMBLY OR CALCULATED FIRE
 RESISTANCE FBC709.
  
 8.)YOU DECLARE AN OCCUPANT LOAD OF 71.
 HOW HAVE YOU ARRIVED AT THIS NUMBER?
  
 9.)DETAILS A-A2, B-A2, AND C-A2 (SHOWN
 ON THE NEWFLOOR PLAN, A2) ARE NOT ON
 A2.
  
 10.)INDICATE WHICH PRODUCTS YOU ARE
 INSTALLING ON THE PRODUCT APPROVALS.
  
 11.)IMPACT PROTECTION REQUIRED,
 FBC1606.1.4.USE OF REMOVABLE SHUTTERS
 ON COMMERCIAL BUILDINGS REQUIRES
 APPROVAL FROM THE BUILDING OFFICIAL.
 SEE ATTACHED POLICY, ITEM #13.SUBMIT A
 PRE-STORM PREPARATION PLAN IF YOU WOULD
 LIKE TO REQUEST THE USE OF REMOVABLE
 SHUTTERS.
  
 12.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 13.)PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 ROOF/WALL PANELS
 METAL DOOR
 LOUVERS
  
 14.)SHOW THE ACCESSIBLE ROUTE,
 FBC11-4.1.3.IT APPEARS THAT THERE IS A
 STEP UP INTO THE BUILDING.SHOW
 ELEVATIONS.
  
 15.)PROVIDE INFORMATION IN REGARDS TO
 THE DOOR HARDWARE, FBC11-4.13.9.
  
 16.)ACCESSIBLE PARKING REQUIRED,
 FBC11-4.1.2(5)(A).
  
 17.)A NOTE ON THE PLAN STATES THAT
 FLOOR RAFTERS WILL REMAIN, BUT
 PARTITIONS ON THE SECOND FLOOR WILL BE
 REMOVED.C1 STATES THAT THIS IS A TWO
 STORY BUILDING.WHERE IS THE SECOND
 FLOOR PLAN AND HOW DO YOU GET TO THE
 SECOND FLOOR?
  
 18.)FBC*1804.1.7, FINISH GRADE SHALL
 BE SLOPED AWAY FROM THE FOUNDATION FOR
 DRAINAGE, SEE BB-A5.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-04-26 Cont ID  
Sent By btrobaug Date 2007-04-26 Time 09:11 Rev Time 0.00
Received By btrobaug Date 2007-04-26 Time 08:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-08-28 Cont ID  
Sent By btrobaug Date 2006-08-28 Time 13:43 Rev Time 0.50
Received By btrobaug Date 2006-08-28 Time 13:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-05-31 Cont ID  
Sent By btrobaug Date 2006-05-31 Time 13:06 Rev Time 1.00
Received By btrobaug Date 2006-05-31 Time 12:04 Sent To B
Notes
2006-05-31 00:00:00NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. THE RATING
 INDICATED ON THE GEAR (WHICH IS NOT A
 STANDARD RATING)IS THE SAME AVAILABLE AT
 THE TRANSFORMER.
  
 2} THE DISCONNECT ON THE RISER IS NOT ON
 THE PLAN AS NOTED IN THE LAST REVIEW.
  
 3} THE EQUIPMENT GROUND FROM THE METER
 TO THE DISCONNECT MUST BE REMOVED TO
 PREVANT OBJECTIONAL CURRENT. SEE 250.6.
  
 4} SEE PREVIOUS NOTE #4. SUBMIT ALL
 DETAILS AND SPECIFICATIONS FOR THE FIRE
 PUMP AND CONTROLLER. ALSO SHOW THE FEED
 TO SAME ON THE RISER. THERE IS NO RECORD
 OF THE PUMP OR CONTROLLER EVER BEING
 PERMITTED.
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-15 Cont ID  
Sent By dpalmer Date 2005-11-15 Time 08:07 Rev Time 1.00
Received By dpalmer Date 2005-11-15 Time 07:40 Sent To  
Notes
2005-11-15 00:00:00****** UNSAT ********
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 ELECTRICAL DEVICES AND CORRELATE WITH
 THE PANEL SCHEDULE SUBMTTED. PLEASE SEE
 700.12E FOR EM/EXT LTS.
 PLEASE SEE EM/EXT LTS SHALL BE CIRCUITED
 TO THE LOCAL BRANCH CIRCUIT IN THE AREA
 WHICH LTS ARE LOCATED.
  
 2)NOTE: PLEASE SEE PLANS STILLINDICATE
 TWO METERS, HOWEVER ONLY ONE NEW ON
 RISER.
 PLEASE ALSO SEE NEW DISCONNECT NOW SHOWN
 ON RISER IS NOT SHOWN ON PLANS.?
 215.5
  
 3)NOTE: PLEASE SEE MAIN GRONDING
 ELECTRODE SYSTEM SHALL CONTAIN ALL AS
 SHOWN AT SUB-PANEL. CWP, GRND ROD AND
 ANY NEW FOOTER STEEL.
 250.50
 SUB PANEL IS NOT REQUIRED TO ALSO
 CONTAIN A GROUNDING ELECTRODE SYSTEM,
 HOWEVER IT MAY BE DONE.
 250.50
  
 4)NOTE: PLEASE CLARIFY PUMP SHOWN AT
 FIRE SPRINKLER ENTRANCE LOCATION. PLEASE
 VERIFY IF "FIRE PUMP", PLEASE SUBMIT ALL
 INFORMATION FOR FIRE PUMP CONTROLLER
 ETC.
 PLEASE CALL TO GO OVER INFORMATION
 NEEDED IF INDEED THIS IS A FIRE PUMP.
 NO OTHER PUMP INFORMATION COULD BE
 LOCATED ON PANEL SCHEDULE OR LOAD CALCS.
 215.5
  
 5)NOTE: PLEASE SEE OFFICE DOES NOT SEEM
 TO SHOW ANY RECEPTS? PLEASE VERIFY.
 PLEASE SEE OFFICE LT AND RECEPTS ARE
 INDICATED ON PANEL SCHEDULE?
 PLEASE ALSO SEE #14 AWG IS SHOWN ON THE
 20A BRANCH CIRCUIT. A MAX LOAD OF 1440W
 IS TO BE ON A 15A CIRCUIT.
 PLEAS ADJUST.240.4,310.16,215.5
  
 6)NOTE: PLEASE VERIFY #10 AWG SHOWN FOR
 SMOKE DETECTORS CIRCUIT?
 PLEASE ALSO CLARIFY THIS AS A FIRE ALARM
 PANEL IS BEING INSTALLED, WOULD NOTTHE
 SMOKE DETECTORS BE WIRED INTOFACP?
 PLEASE ALSO SEE THESE DEVICES COULD NOT
 BE LOCATED ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE KNOW THAT SOME OF THE
 ABOVE COMMENTS MAY AFFECT FIRE REVIEW.
  
  
 ** PLEASE SEE ELECTRICAL SHEET IS
 LABELED AS SHEET "L", AND "E" SHEET IS
 FOR FIRE SPRKLR PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 20:14 Rev Time 0.50
Received By dpalmer Date 2005-07-01 Time 20:09 Sent To  
Notes
2005-07-01 00:00:00IN ELEC FOR REVIEW.
 ************ UNSAT ************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SHOW MIN CONDUCTORS FROM
 METER TO MAIN. 310.16/240.4,215.5
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN TO PANEL.
 250.110,250.24,250.122
  
 4)NOTE: PLEASE SEE NEW RE-LOCATED PANEL
 MAY NOT BE PLACED IN "STORAGE RM".
 PLEASE SEE 110.26, 408.16, ETC.
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE.
 215.5
  
 6)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOAD CALCULATIONS SUBMITTED
 ARE RESIDENTIAL LOAD CALCS.
  
 7)NOTE: PLEASE SEE PLANS SHOW TWO
 METERS??
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ANY OLD/ VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-01 Cont ID  
Sent By mwennerg Date 2006-06-01 Time 10:11 Rev Time 0.00
Received By mwennerg Date 2006-06-01 Time 10:11 Sent To  
Notes
2006-06-01 00:00:00***PROVISO***
  
 PLANS SHOW A 'PUMP' NEAR THE SPRINKLER
 RISER. DOES THIS BUILDING HAVE A FIRE
 PUMP, OR IS THIS NOTE REFERENCING THE
 FIRE SPRINKLER RISER?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-11-18 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 12:49 Rev Time 0.00
Received By mcarsill Date 2005-11-10 Time 12:49 Sent To  
Notes
2005-11-10 00:00:001. PROVIDE PORTABLE FIRE EXTINGUISHERS.
  
 2. SEPERATE SHOP DRAWINGS REQUIRED FOR
 FIRE SPRINKLER SYSTEM ADDITIONS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-28 Cont ID  
Sent By mwennerg Date 2005-07-28 Time 11:04 Rev Time 0.00
Received By mwennerg Date 2005-07-28 Time 11:04 Sent To  
Notes
2005-07-28 00:00:00******DENIED******
  
 1) DRAWINGS SHOW AN ADDRESS ON THE
 BUILDING THAT SHALL BE AT LEAST 6" IN
 HEIGHT AND CONTRASTING TO THE
 BACKGROUND.
  
 2) PLEASE INDICATE WHAT CONTENTS WILL BE
 STORED IN STORAGE AREAS.
  
 3) PLEASE ILLUSTRATE THE TOTAL OCCUPANT
 LOAD. DOORS SERVING AREAS WITH OCCUPANT
 LOADS GREATER THAN 50 PERSONS SHALL
 SWING IN THE DIRECTION OF TRAVEL. PLEASE
 PROVIDE FURTHER INFORMATION REGARDING
 SECURITY GATES.
  
 4) PLEASE CLEARLY SHOW THE LOCATIONS OF
 ALL ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHTING. EMERGENCY LIGHTING IS REQUIRED
 NFPA 101, SECTION 37.2.9.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 6) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 7) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 14:35 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 14:35 Sent To  
Notes
2006-08-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-01 Cont ID  
Sent By lmartine Date 2006-06-01 Time 10:57 Rev Time 0.00
Received By lmartine Date 2006-06-01 Time 10:56 Sent To  
Notes
2006-06-01 00:00:00GAVE TO ZONING TO EXPIDITE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 09:04 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 09:04 Sent To  
Notes
2006-05-25 00:00:005/25/06-SUBMITTAL W/PLANS WAITING FOR
 "COMM" BD
2006-05-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 15:01 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 15:01 Sent To  
Notes
2005-10-21 00:00:00TO "COMM" BD#47
2005-10-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-08 Cont ID  
Sent By shill Date 2005-08-08 Time 08:00 Rev Time 0.00
Received By shill Date 2005-06-24 Time 08:39 Sent To  
Notes
2005-06-24 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#55

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 16:09 Rev Time 0.00
Received By shill Date 2005-06-14 Time 16:09 Sent To E
Notes
2005-06-14 00:00:00TO ELEC BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-07 Cont ID  
Sent By tgordon Date 2006-09-07 Time 08:44 Rev Time 1.00
Received By tgordon Date 2006-09-07 Time 10:36 Sent To  
Notes
2006-09-07 00:00:00PLANS GIVEN TO LUIS M.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-21 Cont ID  
Sent By tgordon Date 2006-05-30 Time 16:48 Rev Time 0.30
Received By tgordon Date 2006-06-21 Time 09:06 Sent To  
Notes
2006-05-30 00:00:00*** DENIED ***
 1) PLANS NEED TO REFER TO THE 2001 FBC,
 NOT THE 2004 FBC, AS THE BUILDING PERMIT
 WAS APPLYED FOR BEFORE 10-1-05.
  
 2) DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR THE 4 EXHAUST FANS
 BEING INSTALLED, MUST BE ON JOB SITE FOR
 INSPECTIONS. PER 2004 FBC/M 304.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-20 Cont ID  
Sent By pkrauss Date 2005-07-20 Time 13:21 Rev Time 0.25
Received By pkrauss Date 2005-07-20 Time 13:21 Sent To  
Notes
2005-07-20 00:00:00NO MECHANICAL CONTRACTOR OR WORK
 INDICATED WITH PERMIT APPLICATION.
 PLAN SHEET A3 INDICATES "METAL
 VENTILATOR" (LOUVERS).PLEASE NOTE
 MINIMUM VENTILATION REQUIRED PER 2001
 FBC(M) TABLE 403.3. BATHROOM SHALL HAVE
 A WINDOW WITH A MINIMUM OF 3 SQUARE FEET
 OF OPEN AREA OR HAVE MECHANICAL
 VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status N Date 2006-09-07 Cont ID  
Sent By kstevens Date 2006-09-07 Time 16:02 Rev Time 0.00
Received By kstevens Date 2006-09-07 Time 16:02 Sent To  
Notes
2006-09-07 00:00:00NO RISER DIAGRAM REQUIRED. EXISTING
 TOILET ROOM, MOP SINK, AND DRINKING
 FOUNTAIN. MOVING LAV AROUND THE CORNER
 ONLY. DEMO ON SEPARATE PERMIT

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-05-31 Cont ID  
Sent By kstevens Date 2006-05-31 Time 18:46 Rev Time 0.00
Received By kstevens Date 2006-05-31 Time 18:46 Sent To  
Notes
2006-05-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 COMMENTS FROM TWO PREVIOUS REVIEWS:
  
 COMMENTS FROM PREVIOUS REVIEW:
  
  
 4. SUBMIT A WATER AND A SANITARY RISER
 DIAGRAM IN ISOMETRIC FORM. THE WATER
 RISER DIAGRAM SHALL SHOW ALL PIPE SIZES,
 VALVES, AND, IF REQUIRED BY SECTION
 604.9, WATER HAMMER ARRESTORS. - THE
 SANT. RISER DIAGRAM SHALL SHOW ALL PIPE
 SIZES, VENTS, TRAPS AND POINT OF
 CONNECTION. SECTION 104.3.1.1. - NO
 WATER RISER ISOMETRIC SUBMITTED. TWO
 SANITARY RISER ISOMETRICS SUBMITTED, BUT
 NETHER RISER DIAGRAM MEETS CODE
 REQUIREMENTS NOR DO THEY REFLECT THE
 FLOOR PLAN. THE RISER DIAGRAM ON SHEET
 A8 DOES NOT REFLECT THE FLOOR PLAN
 BECAUSE THE DRINKING FOUNTAIN IS MISSING
 AND THE MOP SINK IS SHOWN ON THE SAME
 SIDE OF THE ROOM AS THE W/C. THE LAV IS
 NOT VENTED AS SHOWN. THE MOP SINK
 REQUIRES A TRAP. SHOW ALL PIPE SIZES.
 SECTIONS 104.2.1, 901.2.1, 1002.1- THE
 SANT. RISER DIAGRAM SUBMITTED ON AN
 8-1/2" X 11" SHEET DOES NOT REFLECT THE
 FLOOR PLAN, THE MOP SINK, LAV, AND
 DRINKING FOUNTAIN ARE NOT VENTED.
 HORIZONTAL DRY VENTS ARE PROHIBITED. THE
 W/C SHALL NOT BE DOUBLE TRAPPED. THE W/C
 HAS AN INTEGRAL TRAP. SECTIONS 104.2.1,
 1002.1., 901.2.1, 905.3, 905.4. - THE
 TITLE BLOCK FOR THE ENGINEER CAN NOT BE
 READ. FAC 61G15-23.002(2) & FS 471.2055
 - SUBMIT ONLY ONE SANT. RISER DIAGRAM
 THAT MEETS CODE REQUIREMENTS AND
 REFLECTS THE FLOOR PLAN. SECTION
 104.3.1.1.
 ***NO WATER RISER DIAGRAM HAS BEEN
 SUBMITTED. - SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS
 SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE BATHROOM GROUP. (SEE RED-LINED
 EXAMPLE OF A SANT. RISER DIAGRAM THAT
 REFLECTS THE FLOOR PLAN AND MEETS CODE
 REQUIREMENTS.
  
 6. SHT A8 HC LAV DETAILS 1 & 2 SUBMIT
 DETAILS FOR THE FOLLOWING:
 FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE - NOT
 SHOWN.
 FOR THE LAV:
 F. 11-4.19.5 FAUCETS - NOT SHOWN PER
 CODE SECTION.
 FOR THE DRINKING FOUNTAIN.
 G. 11-4.15.2 SPOUT HEIGHT
 H. 11-4.15.3 SPOUT LOCATION
 I. 11-4.15.4 CONTROLS
 J. 11-4.15.5 CLEARANCES & CLEAR FLOOR
 SPACE.
 K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. - NO
 DETAIL FOR THE DRINKING FOUNTAIN
 SUBMITTED.
 ***THE ABOVE ACCESSIBLE REQUIREMENTS ARE
 NOT SHOWN ON THE PLANS AS REQUESTED.
  
 7. SHT A1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITED. (INFORMATIONAL) - ALL
 CAPPED PIPES FOR DEMO SHALL BE INSPECTED
 BY THE FIELD INSPECTOR PRIOR TO
 COVERING. SECTION 704.5 - INDICATE ON
 THE DEMO SHEET WITH A NOTE.
 ***THE ABOVE INFORMATION IS NOT SHOWN ON
 THE PLANS AS REQUESTED.
  
 **************NEW COMMENT**************
  
 1B. THE ADDRESS REQUIRED IN THE TITLE
 BLOCK OF THE ENGINEER DOES NOT REFLECT
 THE ADDRESS OF RECORD ON THE DBPR WEB
 SITE. PLEASE CORRELATE THE INFORMATION
 IN THE TITLE BLOCK TO REFLECT THE DBPR
 WEB SITE. FAC 61G15-23.002(2) AND FS
 471.025. (SEE ATTACHED SHEET FROM DBPR)
  
 2B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
 THIS IS GIVEN AS A NOTICE. IF COMMENTS
 ARE NOT ADDRESSED AFTER THE THIRD
 REVIEW, 4 TIMES THE PLAN REVIEW PORTION
 WILL BE ACCESSED TO THE DESIGN
 PROFESSIONAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-14 Cont ID  
Sent By kstevens Date 2005-12-14 Time 18:22 Rev Time 0.00
Received By kstevens Date 2005-12-14 Time 18:22 Sent To  
Notes
2005-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 COMMENTS FROM PREVIOUS REVIEW:
  
 3. SHT C-1 MINIMUM FACILITIES REQUIRES A
 DRINKING FOUNTAIN AND A SERVICE SINK PER
 TABLE 403.1. SHT A2 FLOOR PLAN DOES NOT
 SHOW THE LOCATION OF THE DRINKING
 FOUNTAIN, NOR DOES IT SHOW THE LOCATION
 OF THE SERVICE SINK. PLEASE SHOW THE
 LOCATION OF THESE REQUIRED FIXTURES. -
 MINIMUM FACILITIES PROVIDED INDICATE NO
 SINKS ARE REQUIRED. PER TABLE 403.1 1
 SERVICE SINK IS REQUIRED. PLEASE
 INDICATE ON TABLE SHOWN ON SHT C-1.
 4. SUBMIT A WATER AND A SANITARY RISER
 DIAGRAM IN ISOMETRIC FORM. THE WATER
 RISER DIAGRAM SHALL SHOW ALL PIPE SIZES,
 VALVES, AND, IF REQUIRED BY SECTION
 604.9, WATER HAMMER ARRESTORS. - THE
 SANT. RISER DIAGRAM SHALL SHOW ALL PIPE
 SIZES, VENTS, TRAPS AND POINT OF
 CONNECTION. SECTION 104.3.1.1. - NO
 WATER RISER ISOMETRIC SUBMITTED. TWO
 SANITARY RISER ISOMETRICS SUBMITTED, BUT
 NETHER RISER DIAGRAM MEETS CODE
 REQUIREMENTS NOR DO THEY REFLECT THE
 FLOOR PLAN. THE RISER DIAGRAM ON SHEET
 A8 DOES NOT REFLECT THE FLOOR PLAN
 BECAUSE THE DRINKING FOUNTAIN IS MISSING
 AND THE MOP SINK IS SHOWN ON THE SAME
 SIDE OF THE ROOM AS THE W/C. THE LAV IS
 NOT VENTED AS SHOWN. THE MOP SINK
 REQUIRES A TRAP. SHOW ALL PIPE SIZES.
 SECTIONS 104.2.1, 901.2.1, 1002.1- THE
 SANT. RISER DIAGRAM SUBMITTED ON AN
 8-1/2" X 11" SHEET DOES NOT REFLECT THE
 FLOOR PLAN, THE MOP SINK, LAV, AND
 DRINKING FOUNTAIN ARE NOT VENTED.
 HORIZONTAL DRY VENTS ARE PROHIBITED. THE
 W/C SHALL NOT BE DOUBLE TRAPPED. THE W/C
 HAS AN INTEGRAL TRAP. SECTIONS 104.2.1,
 1002.1., 901.2.1, 905.3, 905.4. - THE
 TITLE BLOCK FOR THE ENGINEER CAN NOT BE
 READ. FAC 61G15-23.002(2) & FS 471.2055
 - SUBMIT ONLY ONE SANT. RISER DIAGRAM
 THAT MEETS CODE REQUIREMENTS AND
 REFLECTS THE FLOOR PLAN. SECTION
 104.3.1.1.
 6. SHT A8 HC LAV DETAILS 1 & 2 SUBMIT
 DETAILS FOR THE FOLLOWING:
 FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE - NOT
 SHOWN.
 B. 11-4.16.3 HEIGHT (SHOWN MIN.) - NO
 SHOWN PER CODE SECTION.
 D. 11-4.16.5 FLUSH CONTROLS - NOT SHOWN
 PER CODE SECTION.
 FOR THE LAV:
 F. 11-4.19.5 FAUCETS - NOT SHOWN PER
 CODE SECTION.
 LAV SHALL BE MINIMUM 15" OFF WALL TO THE
 CENTERLINE OF THE FIXTURE. - MEASUREMENT
 NOT SHOWN.
 FOR THE DRINKING FOUNTAIN.
 G. 11-4.15.2 SPOUT HEIGHT
 H. 11-4.15.3 SPOUT LOCATION
 I. 11-4.15.4 CONTROLS
 J. 11-4.15.5 CLEARANCES & CLEAR FLOOR
 SPACE.
 K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. - NO
 DETAIL FOR THE DRINKING FOUNTAIN
 SUBMITTED.
 7. SHT A1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITED. (INFORMATIONAL) - ALL
 CAPPED PIPES FOR DEMO SHALL BE INSPECTED
 BY THE FIELD INSPECTOR PRIOR TO
 COVERING. SECTION 704.5 - INDICATE ON
 THE DEMO SHEET WITH A NOTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By kstevens Date 2005-08-04 Time 17:27 Rev Time 3.42
Received By kstevens Date 2005-08-04 Time 12:09 Sent To  
Notes
2005-08-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT C-1 INDICATES OCCUPANCY AS
 MERCANTILE, BUT FLOOR PLAN AND "STORAGE"
 ON THE FRONT OF THE BUILDING INDICATE
 THAT THE OCCUPANCY WILL BE STORAGE. -
 MINIMUM FACILITIES FOR PLUMBING FIXTURES
 WILL BE CALCULATED FOR STORAGE. TABLES
 1003.1 & 403.1.
 2. SHT C-1 UNDER MINIMUM NUMBER OF
 PLUMBING FIXTURES, SECTION 403.2
 EXCEPTION 2 IS REFERENCED. PLEASE
 INDICATE ON THE PLANS THE NUMBER OF
 EMPLOYEES EMPLOYED FOR RECORD.
 3. SHT C-1 MINIMUM FACILITIES REQUIRES A
 DRINKING FOUNTAIN AND A SERVICE SINK PER
 TABLE 403.1. SHT A2 FLOOR PLAN DOES NOT
 SHOW THE LOCATION OF THE DRINKING
 FOUNTAIN, NOR DOES IT SHOW THE LOCATION
 OF THE SERVICE SINK. PLEASE SHOW THE
 LOCATION OF THESE REQUIRED FIXTURES.
 4. SUBMIT A WATER AND A SANITARY RISER
 DIAGRAM IN ISOMETRIC FORM. THE WATER
 RISER DIAGRAM SHALL SHOW ALL PIPE SIZES,
 VALVES, AND, IF REQUIRED BY SECTION
 604.9, WATER HAMMER ARRESTORS. - THE
 SANT. RISER DIAGRAM SHALL SHOW ALL PIPE
 SIZES, VENTS, TRAPS AND POINT OF
 CONNECTION. SECTION 104.3.1.1.
 5. SHT A-2 NEW FLOOR PLAN STATES "SEE
 BATHROOM DETAIL ON SH A-4". NO BATHROOM
 DETAIL ON SHT A4. PLEASE CLARIFY.
 SECTION 104.2.1.
 6. SHT A8 HC LAV DETAILS 1 & 2
 MEASUREMENTS CAN NOT BE READ. SUBMIT
 DETAILS FOR THE FOLLOWING:
 FOR THE W/C:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT (SHOWN MIN.)
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 WATER CLOSET TO BE 18" OFF WALL TO THE
 CENERLINE OF THE FIXTURE.
 FOR THE LAV:
 F. 11-4.19.5 FAUCETS
 LAV SHALL BE MINIMUM 15" OFF WALL TO THE
 CENTERLINE OF THE FIXTURE.
 FOR THE DRINKING FOUNTAIN.
 G. 11-4.15.2 SPOUT HEIGHT
 H. 11-4.15.3 SPOUT LOCATION
 I. 11-4.15.4 CONTROLS
 J. 11-4.15.5 CLEARANCES & CLEAR FLOOR
 SPACE.
 K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 7. SHT A1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITEDL. (INFORMATIONAL) - ALL
 CAPPED PIPES FOR DEMO SHALL BE INSPECTED
 BY THE FIELD INSPECTOR PRIOR TO
 COVERING. SECTION 704.5
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-06-15 Cont ID  
Sent By jroach Date 2006-06-15 Time 10:53 Rev Time 0.00
Received By jroach Date 2006-06-15 Time 10:53 Sent To  
Notes
2006-06-15 00:00:006/15/06 ***PASSED***
  
 REPLACEMENT OF HURRICANE
 DAMAGE...ADDITIONAL IMPROVEMENTS DO NOT
 EXCEED 50% OF THE VALUE OF THE
 STRUCTURE.
  
 JOHN ROACH, SENIOR PLANNER
 (561) 822-1435

Review Stop Z ZONING
Rev No 3 Status F Date 2006-02-02 Cont ID  
Sent By jroach Date 2006-02-02 Time 15:07 Rev Time 0.00
Received By jroach Date 2006-02-02 Time 15:07 Sent To  
Notes
2006-02-02 00:00:002/2/2006 ***FAILED***
  
 AS INDICATED IN PREVIOUS REVIEWS, THE
 SUBJECT COMMERCIAL PROPERTY IS LOCATED
 WITHIN A RESIDENTIAL ZONING DISTRICT AND
 IS CONSIDERED A NONCONFORMING STRUCTURE
 AND MAJOR USE NONCONFORMITY...SUBJECT TO
 ARTICLE XVI OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 ALTERATIONS AND REPAIRS ARE LIMITED TO
 THE FOLLOWING:
  
 A) REPAIRS RELATED TO DAMAGE THAT WAS A
 RESULT OF A NATURAL DISASTER (I.E.
 HURRICANE) WITHIN THE LAST 12 MONTHS.
 THIS REQUIRES PROVIDING PROOF TO THE
 CITY THAT THE REPAIRS ARE REQUIRED AS A
 RESULT OF THE NATURAL DISASTER
 (INSURANCE CLAIMS, ETC.).
  
 B) ALTERATIONS AND/OR REPAIRS ARE
 PERMITTED SO LONG AS THEY DO NOT CREATE
 A NEW NONCONFORMITY OR INCREASE AN
 EXISTING NONCONFORMITY AND ARE LIMITED
 TO 50% OF THE VALUE OF THE STRUCTURE.
 THE VALUE MAY BE DETERMINED BY MEANS OF
 THE COUNTY PROPERTY APPRAISER OR BY A
 PRIVATE APPRAISAL.THIS LIMITATION
 APPLIES TO ALL ALTERATIONS/REPAIRS
 OUTSIDE OF THAT RESULTING FROM A NATURAL
 DISASTER.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-07-18 Cont ID  
Sent By jroach Date 2005-07-18 Time 08:24 Rev Time 0.00
Received By jroach Date 2005-07-18 Time 08:24 Sent To  
Notes
2005-07-18 00:00:007/18/2005 ***FAILED***
  
 1) LOCATED IN SF14 ZONING DISTRICT AND
 CONSIDERED A NONCONFORMING STRUCTURE AND
 MAJOR USE NONCONFORMITY.
  
 1A) NONCONFORMING STRUCTURE SHALL NOT BE
 IMPROVED, CONSTRUCTED, ENLARGED OR
 ALTERED IN ANY MANNER TO CREATE A NEW
 NONCONFORMITY OR TO INCREASE AN EXISTING
 NONCONFORMITY [SECTION 94-513(A)(2)].
 THIS APPLIES TO THE CONSTRUCTION OF THE
 PARKING LOT.
  
 2) ON-STREET PARKING SHALL BE APPROVED
 BY THE CITY TRANSPORTATION ENGINEER
 (BRIAN COLLINS - 494-1040).
  
 3) IN RESIDENTIAL DISTRICT, NO FENCE OR
 WALL SHALL EXCEED 48 INCHES IN HEIGHT
 WITHIN THE REQUIRED FRONT SETBACK
 [SECTION 94-302(B)(1)].THIS APPLIES TO
 THE NEW ROLLING GATE.
  
 4) ADJUST PLANS TO SHOW THAT THE
 CHAIN-LINK FENCE ALONG KANUGA IS
 EXISTING AND NOT PROPOSED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By jroach Date 2005-07-14 Time 14:35 Rev Time 0.00
Received By jroach Date 2005-07-14 Time 14:35 Sent To  
Notes
2005-07-14 00:00:007/14/2005 ***FAILED***
  
 1) LOCATED IN SF14 ZONING DISTRICT AND
 CONSIDERED A NONCONFORMING STRUCTURE AND
 MAJOR USE NONCONFORMITY.
  
 1A) NONCONFORMING STRUCTURE SHALL NOT BE
 IMPROVED, CONSTRUCTED, ENLARGED OR
 ALTERED IN ANY MANNER TO CREATE A NEW
 NONCONFORMITY OR TO INCREASE AN EXISTING
 NONCONFORMITY [SECTION 94-513(A)(2)].
 THIS INCLUDES THE EXPANSION OF THE
 BUILDING AND THE CONSTRUCTION OF THE
 PARKING LOT.
  
 2) ATTACHED OR DETACHED ADDITIONS IN
 EXCESS OF 1,000 SQUARE FEET TO AN
 EXISTING RESIDENTIAL OR NON RESIDENTIAL
 STRUCTURE REQUIRES INFORMAL SITE PLAN
 REVIEW [SECTION 94-35(D)(5)].
  
 3) ON-STREET PARKING SHALL BE APPROVED
 BY THE CITY TRANSPORTATION ENGINEER
 (BRIAN COLLINS - 494-1040).
  
 4) IN RESIDENTIAL DISTRICT, NO FENCE OR
 WALL SHALL EXCEED 48 INCHES IN HEIGHT
 WITHIN THE REQUIRED FRONT SETBACK
 [SECTION 94-302(B)(1)].
  
 5) EXPANSION NOT APPROVED BY THE
 HISTORIC PRESERVATION DIVISION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.