| Plan Review Stops For Permit 05060920 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2007-01-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-11 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-11 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2007-01-11 18:22:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2001 | | | | | | 1.)THE SHUTTERS DO NOT ADDRESS THE ISSUE OF DESIGN | | | PRESSURE FOR THE LOUVER VENTS. | | | | | | 2.)THE OVERHEAD DOOR HAS A LIMITATION OF +-37, | | | OPENINGS HAVE A DESIGN PRESSURE OF -39.PLEASE | | | ADDRESS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-01-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-11 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-11 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2007-01-11 18:09:08 | REVISION; NEW PRODUCT APPROVALS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-09-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-09-11 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-09-15 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2006-09-15 00:00:00 | FIRE SPRINKLER INFORMATION 06081983 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-06-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-06-20 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-06-20 |
Time |
11:14 |
Sent To |
ENG |
|
| Notes |
| 2006-06-20 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | COMMENTS OUTSTANDING FROM PREVIOUS | | | REVIEWS, NUMBERING REMAINING THE SAME | | | FOR CONSITENCY: | | | | | | 4.)PROVIDE A SUREVY OF THIS PROPERTY | | | SO THAT FBC TABLE 600 COMPLIANCE CAN BE | | | DETERMINED. (1ST AND 2ND REVIEWS) | | | | | | 3RD REVIEW - ONE HAS BEEN PROVIDED, BUT | | | CONFLICTS WITH THE ARCHITECTURAL PLAN. | | | EXPLAIN WHY A SIGNED, SEALED SURVEY | | | SHOWS A DISTANCE FROM THE PROPERTY LINE | | | OF 3.4' IN THE REAR, BUT THE SITE PLAN | | | PREPARED BY A.GARGUILIO, PE SHOWS THE | | | BUILDING AS LESS THAN 3' FROM THE | | | PROPERTY LINE, REQUIRING 0 OPENINGS. | | | THIS ISSUE SHOULD HAVE BEEN ADDRESSED | | | PRIOR TO RESUBMITTAL.CODE COMPLIANCE | | | CANNOT BE DETERMINED DUE TO INCONSISTENT | | | INFORMATION. | | | | | | SEE FBC TABLE 600.IF THE BUILDING IS | | | LESS THAN 3', 3 HOUR WALL REQUIRED FOR | | | TYPE V 1 HR PROTECTED, 2 HOUR FOR TYEP V | | | UNPROTECTED. | | | | | | 6.)YOU HAVE DECLARED TYPE IV | | | CONSTRUCTION.SEE FBC606.YOU HAVE | | | COMBUSTIBLE WALLS AND ROOF, SO THIS IS | | | NOT A TYPE IV. (1ST AND 2ND REVIEW). | | | | | | 3RD REVIEW - YOU HAVE NOW DECLARED A | | | TYPE V, 1 HOUR PROTECTED.HOW ARE THE | | | STRUCTURAL ELEMENTS PROTECTED FBC TABLE | | | 600?THE DETAILS PROVIDED ARE NOT | | | COMPLIANT FOR A 1 HOUR PROTECTED | | | BUILLDING. | | | | | | SEE ALSO COMMENT 4 ABOVE.CODE | | | COMPLIANCE CANNOT BE DETERMINED DUE TO | | | INSUFFICIENT/CONFLICTING INFORMATION ON | | | THE PLAN. | | | | | | 7.)C1 ALSO STATES THAT 1 HOUR | | | PROETECTION REQUIRED.SHOW COMPLIANCE, | | | EITHER BY ASSEMBLY OR CALCULATED FIRE | | | RESISTANCE FBC709. (1ST & 2ND REVIEWS) | | | | | | 3RD REVIEW - NOT ADDRESSED. | | | | | | 8.)YOU DECLARE AN OCCUPANT LOAD OF 71. | | | HOW HAVE YOU ARRIVED AT THIS NUMBER? | | | (1ST REVIEW) | | | | | | 2ND REVIEW - NOW THE OCCUPANCY IS SHOWN | | | AS 5; 1500/300.THE BUILDING IS 11,131 | | | SF.SEE FBC1003.1, FBC TABLE 1003.1. | | | | | | 3RD REVIEW - NOT PROPERLY ADDRESSED. | | | OCCUPANCY IS NOW "ONE EMPLOYEE".IT IS | | | UNCLEAR AS TO HOW AN 11K+ BUILDING CAN | | | HAVE AN OCCUPANCY OF ONE. | | | | | | 13.)PRODUCT APPROVALS REQUIRED FOR THE | | | FOLLOWING: | | | ROOF/WALL PANELS | | | METAL DOOR | | | LOUVERS | | | | | | 2ND & 3RD REVIEWS - SUBMIT THE | | | INSTALLATION INSTRUCTIONS FOR THE | | | BENCHMARK DOORS (STATE PRODUCT APPROVAL | | | SUBMITTED). | | | | | | PSUBMIT STATE PRODUCT APPROVALS FOR THE | | | ROLLUP DOOR, SINGLE HUNG WINDOW AND | | | FIXED WINDOW, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | 3RD REVIEW - THE LOCAL PRODUCT APPROVAL | | | APPLICATION IS INCOMPLETE.THERE IS NO | | | QUALITY ASSURANCE ENTITY ON THE | | | APPLICATION.THE LOCAL PRODUCT APPROVAL | | | CANNOT BE ISSUED WITHOUT A QUALITY | | | ASSURANCE PROGRAM, FAC9B72.UNTIL PROOF | | | OF A PROGRAM IS PROVIDED, A REVIEW WILL | | | NOT BE DONE ON THE APPLICATION.SEE THE | | | VALIDATION CHECKLIST AND FAC9B72 AT | | | WWW.FLORIDABUILDING.ORG, PRODUCT | | | APPROVAL.***THE LOCAL PRODUCT APPROVAL | | | APPLICATION MAY BE SUBMITTED PRIOR TO | | | RESUBMITTAL OF THE PLANS*** | | | | | | 14.)SHOW THE ACCESSIBLE ROUTE, | | | FBC11-4.1.3.IT APPEARS THAT THERE IS A | | | STEP UP INTO THE BUILDING.SHOW | | | ELEVATIONS. (1ST REVIEW) | | | | | | 2ND REVIEW - NOT ADDRESSED.THE | | | BUILDING ELEVATIONS STILL SHOW A STEP | | | INTO THE MAIN ENTRANCE.PROVIDE | | | FINISHED FLOOR ELEVATIONS. | | | | | | 3RD REVIEW - NOT ADDRESSED.PLAN STILL | | | SHOWS STEPS AT THE FRONT DOOR.THE | | | ROLLUP DOORS ARE NOT COMPLIANT AS AN | | | ACCESSIBLE ENTRY. | | | | | | 15.)PROVIDE INFORMATION IN REGARDS TO | | | THE DOOR HARDWARE, FBC11-4.13.9.(1ST | | | REVIEW). | | | | | | 2ND & 3RD REVIEWS - NOT ADDRESSED. | | | | | | 16.)ACCESSIBLE PARKING REQUIRED, | | | FBC11-4.1.2(5)(A). (1ST & 2ND REVIEWS) | | | | | | 3RD REVIEW - THIS WAS ADDED TO THE PLAN, | | | BUT DOES NOT HAVE ALL DIMENSIONS, | | | SIGNAGE, ACCESS AISLE.IS THE | | | ACCESSIBLE ROUTE THROUGH THE SIDE DOOR? | | | NO ELEVATION CHANGE INFORMATION PROVIDED | | | AS REQUESTED. | | | | | | | | | 19.)SEE FBC1012.THE TWO OPENINGS IN | | | THE FRONT OF THE BUILDING ARE NOT | | | COMPLIANT WITH THE REQUIREMENTS FOR | | | EGRESS DOORS.ADDRESS. | | | | | | 3RD REVIEW - EXIT LIGHTS SHOWN AT THE | | | ROLLUP DOORS.NOT PROPERLY ADDRESSED. | | | | | | 20.)SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW FEE WILL BE CHARGED IF THE | | | COMMENTS ARE NOT ADDRESSED ON THE NEXT | | | REVIEW AS REQUIRED BY FLORIDA STATUTE. | | | | | | 3RD REVIEW - 4X FEE AGAINST A. GARGUILO, | | | PE APPLIED TO PERMIT. | | | | | | 21.)PROVIDE INFORMATION IN REGARDS TO | | | THE DOOR HARDWARE, INCLUDING ALL OF THE | | | SWING DOORS AND ALSO THE ROLLUP DOORS | | | FOR THE STORAGE UNITS FBC11-4.13.9. | | | | | | 3RD REVIEW - NOT ADDRESSED. | | | | | | NEW COMMENTS: | | | | | | 22.)(PROVIDING MORE DETAIL IN REGARDS | | | WHAT IS REQUIRED TO SHOW COMPLIANCE WITH | | | ITEM 14.) PROVIDE HEIGHT FOR THE FLOOR | | | MOUNTING CHANNEL AT THE DOOR, STORAGE | | | UNITS.THERE IS TO BE AN ACCESSIBLE | | | ROUTE INTO THE STORAGE UNITS, | | | FBC11-4.1.1(1)(A), FBC11-4.1.2(2).THE | | | FLOOR PLAN DOES NOT SHOW A MAN DOOR, | | | ONLY A ROLLUP DOOR, BUT A7 SHOWS A SWING | | | DOOR AND A ROLLUP DOOR.DOORS ARE TO | | | COMPLY WITH FBC11-4.13.AS THE DOORS | | | ARE NOT SHOWN ON THE FLOOR PLAN, AND THE | | | DETAILS ON A7 DO NOT SHOW DOOR SWING | | | INFORMATION, MANEUVERING CLEARANCE | | | CANNOT BE DETERMINED. | | | | | | A SWING DOOR IS REQUIRED FOR EGRESS, | | | FBC1027.2, FBC1012.1.2. | | | | | | 23.)THE PLANS NOW STATE CODE SUMMARY | | | 2004, FORMERLY STATED FBC 2001. | | | GOVERNING CODE AT THE TIME OF | | | APPLICATION WAS FBC2001.TO CHANGE | | | CODE, SUBMIT A NEW PERMIT APPLICATION | | | AND THE PLANS WILL BE REVIEWED UNDER | | | FBC2004. | | | | | | 24.)THE ACCESSIBLE BATHROOM DOOR LACKS | | | THE MANEUVERING CLEARANCE REQUIRED BY | | | FBC11-4.13.6, FBC11 FIGURE 25. | | | | | | 25.)HOW DOES THE GATE OPEN?SHOW | | | REACH RANGE, FBC11-4.2.5, FBC1104.2.6. | | | | | | 26.)CHANGES WERE NOT CLOUDED.THIS | | | REQUIRED A COMPLETE NEW REVIEW.TO | | | EXPEDITE PLAN REVIEW, CLOUD ALL CHANGES. | | | | | | 27.)A SET OF THE PLANS HAS BEEN | | | RETAINED.THEY WILL BE FORWARDED TO | | | FBPE WITH A COMPLAINT. | | | | | | 28.)DOORS ARE SHOWN ENCROACHING THE | | | PROPERTY LINE, SEE FBC3203. | | | | | | 29.)PROVIDE DIMENSIONS FOR THE AWNING, | | | FBC3204.3. | | | | | | 30.)THIS IS A 25-50% IMPROVEMENT AS | | | PER ARCHITECT'S LETTER AND APPRAISAL, | | | FBC3401.2.2. | | | | | | 31.)DECLARE A SUBCLASSIFICATION, | | | FBC312.2. | | | | | | 32.)A2 NOW HAS REFERENCE TO SHUTTERS, | | | ALSO SHOWS IMPACT.REMOVABLE SHUTTERS | | | ON COMMERCIAL BUILDINGS ARE TO BE | | | APPROVED BY THE BUILDING OFFICIAL. | | | SUBMIT A PLAN FOR INSTALLATION, SEE | | | ATTCHED IMPLEMENTATION STANDARD, ITEM | | | 13. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-11-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-10 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-06-01 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | GAVE TO MICHELLE, TO GIVE TO JOHN ROACH | | 2005-11-10 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | COMMENTS FROM PREVIOUS REVIEW, NUMBERING | | | REMAINING THE SAME FOR CONSISTENCY | | | | | | 3.)THIS IS AN OVER 50% IMPROVEMENT AND | | | THE REQUIREMENTS OF FBC3401.7.2.6 APPLY. | | | SOME OF THE COMMENTS RELATE TO THIS CODE | | | SECTION. | | | | | | 4.)PROVIDE A SURVEY OF THIS PROPERTY | | | SO THAT FBC TABLE 600 COMPLIANCE CAN BE | | | DETERMINED. | | | | | | NOT ADDRESSED | | | | | | 6.)YOU HAVE DECLARED TYPE IV | | | CONSTRUCTION.SEE FBC606.YOU HAVE | | | COMBUSTIBLE WALLS AND ROOF, SO THIS IS | | | NOT A TYPE IV. | | | | | | NOT ADDRESSED | | | | | | 7.)C1 ALSO STATES THAT 1 HOUR | | | PROTECTION REQUIRED.SHOW COMPLIANCE, | | | EITHER BY ASSEMBLY OR CALCULATED FIRE | | | RESISTANCE FBC709. | | | | | | NOT ADDRESSED | | | | | | 8.)YOU DECLARE AN OCCUPANT LOAD OF 71. | | | HOW HAVE YOU ARRIVED AT THIS NUMBER? | | | | | | NOW THE OCCUPANCY IS SHOWN AS 5; | | | 1500/300.THE BUILDING IS 11,131 SF. | | | SEE FBC1003.1, FBC TABLE 1003.1. | | | | | | 12.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | SEE ITEM 13 BELOW. | | | | | | 13.)PRODUCT APPROVALS REQUIRED FOR THE | | | FOLLOWING: | | | ROOF/WALL PANELS | | | METAL DOOR | | | LOUVERS | | | | | | SUBMIT THE INSTALLATION INSTRUCTIONS FOR | | | THE BENCHMARK DOORS (STATE PRODUCT | | | APPROVALS SUBMITTED) | | | | | | SUBMIT STATE PRODUCT APPROVALS FOR THE | | | ROLLUP DOOR, SINGLE HUNG WINDOW AND | | | FIXED WINDOW | | | | | | PRODUCT APPROVALS REQUIRED FOR THE ROOF | | | AND WALL PANELS, NONE SUBMITTED | | | | | | 14.)SHOW THE ACCESSIBLE ROUTE, | | | FBC11-4.1.3.IT APPEARS THAT THERE IS A | | | STEP UP INTO THE BUILDING.SHOW | | | ELEVATIONS. | | | | | | NOT ADDRESSED.THE BUILDING ELEVATIONS | | | STILL SHOW A STEP INTO THE MAIN | | | ENTRANCE.PROVIDE FINISHED FLOOR | | | ELEVATIONS. | | | | | | 15.)PROVIDE INFORMATION IN REGARDS TO | | | THE DOOR HARDWARE, FBC11-4.13.9. | | | | | | NOT ADDRESSED. | | | | | | 16.)ACCESSIBLE PARKING REQUIRED, | | | FBC11-4.1.2(5)(A). | | | | | | NOT ADDRESSED. | | | | | | 17.)A NOTE ON THE PLAN STATES THAT | | | FLOOR RAFTERS WILL REMAIN, BUT | | | PARTITIONS ON THE SECOND FLOOR WILL BE | | | REMOVED.C1 STATES THAT THIS IS A TWO | | | STORY BUILDING.WHERE IS THE SECOND | | | FLOOR PLAN AND HOW DO YOU GET TO THE | | | SECOND FLOOR? | | | | | | THE NOTE ON C1 NOW STATES THAT THIS IS A | | | ONE STORY BUILDING, BUT A1 SHOWS A FRAME | | | 2ND STORY. | | | | | | 18.)FBC*1804.1.7, FINISH GRADE SHALL | | | BE SLOPED AWAY FROM THE FOUNDATION FOR | | | DRAINAGE, SEE BB-A5. | | | | | | NOT ADDRESSED. | | | | | | NEW COMMENT: | | | | | | 19.)SEE FBC1012.THE TWO OPENINGS IN | | | THE FRONT OF THE BUILDING ARE NOT | | | COMPLIANT WITH REQUIREMENTS FOR EGRESS | | | DOORS.ADDRESS. | | | | | | 20.)SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW FEE WILL BE CHARGED IF THE | | | COMMENTS ARE NOT ADDRESSED ON THE NEXT | | | REVIEW AS REQUIRED BY FLORIDA STATUTE. | | | | | | 21.)PROVIDE INFORMATION IN REGARDS TO | | | THE DOOR HARDWARE, INCLUDING ALL OF THE | | | SWING DOORS AND ALSO THE ROLLUP DOORS | | | FOR THE STORAGE UNITS FBC11-4.13.9. | | | | | | A SET OF THE PLANS HAS BEEN RETAINED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-08 |
Time |
07:56 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-08-08 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2005-08-08 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.THIS PROJECT INVOLVES A | | | CHANGE OF OCCUPANCY.233-5025 | | | | | | 3.)THIS IS AN OVER 50% IMPROVEMENT AND | | | THE REQUIREMENTS OF FBC3401.7.2.6 APPLY. | | | SOME OF THE COMMENTS RELATE TO THIS CODE | | | SECTION. | | | | | | 4.)PROVIDE A SURVEY OF THIS PROPERTY | | | SO THAT FBC TABLE 600 COMPLIANCE CAN BE | | | DETERMINED. | | | | | | 5.)MERCANTILE OCCUPANCY IS DECLARED ON | | | C1, AS WELL AS SINGLE TENANT.IF THERE | | | IS ONLY ONE TENANT, WHY ARE THERE | | | MULTIPLE UNITS AND BAYS?PLEASE PROVIDE | | | SOME INFORMATION IN REGARDS TO THE | | | INTENDED USE OF THE BUILDING.FBC312, | | | FBC310. | | | | | | 6.)YOU HAVE DECLARED TYPE IV | | | CONSTRUCTION.SEE FBC606.YOU HAVE | | | COMBUSTIBLE WALLS AND ROOF, SO THIS IS | | | NOT A TYPE IV. | | | | | | 7.)C1 ALSO STATES THAT 1 HOUR | | | PROTECTION REQUIRED.SHOW COMPLIANCE, | | | EITHER BY ASSEMBLY OR CALCULATED FIRE | | | RESISTANCE FBC709. | | | | | | 8.)YOU DECLARE AN OCCUPANT LOAD OF 71. | | | HOW HAVE YOU ARRIVED AT THIS NUMBER? | | | | | | 9.)DETAILS A-A2, B-A2, AND C-A2 (SHOWN | | | ON THE NEWFLOOR PLAN, A2) ARE NOT ON | | | A2. | | | | | | 10.)INDICATE WHICH PRODUCTS YOU ARE | | | INSTALLING ON THE PRODUCT APPROVALS. | | | | | | 11.)IMPACT PROTECTION REQUIRED, | | | FBC1606.1.4.USE OF REMOVABLE SHUTTERS | | | ON COMMERCIAL BUILDINGS REQUIRES | | | APPROVAL FROM THE BUILDING OFFICIAL. | | | SEE ATTACHED POLICY, ITEM #13.SUBMIT A | | | PRE-STORM PREPARATION PLAN IF YOU WOULD | | | LIKE TO REQUEST THE USE OF REMOVABLE | | | SHUTTERS. | | | | | | 12.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | 13.)PRODUCT APPROVALS REQUIRED FOR THE | | | FOLLOWING: | | | ROOF/WALL PANELS | | | METAL DOOR | | | LOUVERS | | | | | | 14.)SHOW THE ACCESSIBLE ROUTE, | | | FBC11-4.1.3.IT APPEARS THAT THERE IS A | | | STEP UP INTO THE BUILDING.SHOW | | | ELEVATIONS. | | | | | | 15.)PROVIDE INFORMATION IN REGARDS TO | | | THE DOOR HARDWARE, FBC11-4.13.9. | | | | | | 16.)ACCESSIBLE PARKING REQUIRED, | | | FBC11-4.1.2(5)(A). | | | | | | 17.)A NOTE ON THE PLAN STATES THAT | | | FLOOR RAFTERS WILL REMAIN, BUT | | | PARTITIONS ON THE SECOND FLOOR WILL BE | | | REMOVED.C1 STATES THAT THIS IS A TWO | | | STORY BUILDING.WHERE IS THE SECOND | | | FLOOR PLAN AND HOW DO YOU GET TO THE | | | SECOND FLOOR? | | | | | | 18.)FBC*1804.1.7, FINISH GRADE SHALL | | | BE SLOPED AWAY FROM THE FOUNDATION FOR | | | DRAINAGE, SEE BB-A5. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-04-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-26 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-04-26 |
Time |
08:44 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-28 |
Time |
13:43 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-28 |
Time |
13:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-05-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-05-31 |
Time |
13:06 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-05-31 |
Time |
12:04 |
Sent To |
B |
|
| Notes |
| 2006-05-31 00:00:00 | NONCOMPLIANT | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. THE RATING | | | INDICATED ON THE GEAR (WHICH IS NOT A | | | STANDARD RATING)IS THE SAME AVAILABLE AT | | | THE TRANSFORMER. | | | | | | 2} THE DISCONNECT ON THE RISER IS NOT ON | | | THE PLAN AS NOTED IN THE LAST REVIEW. | | | | | | 3} THE EQUIPMENT GROUND FROM THE METER | | | TO THE DISCONNECT MUST BE REMOVED TO | | | PREVANT OBJECTIONAL CURRENT. SEE 250.6. | | | | | | 4} SEE PREVIOUS NOTE #4. SUBMIT ALL | | | DETAILS AND SPECIFICATIONS FOR THE FIRE | | | PUMP AND CONTROLLER. ALSO SHOW THE FEED | | | TO SAME ON THE RISER. THERE IS NO RECORD | | | OF THE PUMP OR CONTROLLER EVER BEING | | | PERMITTED. | | | | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-11-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-15 |
Time |
08:07 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-11-15 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2005-11-15 00:00:00 | ****** UNSAT ******** | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL | | | ELECTRICAL DEVICES AND CORRELATE WITH | | | THE PANEL SCHEDULE SUBMTTED. PLEASE SEE | | | 700.12E FOR EM/EXT LTS. | | | PLEASE SEE EM/EXT LTS SHALL BE CIRCUITED | | | TO THE LOCAL BRANCH CIRCUIT IN THE AREA | | | WHICH LTS ARE LOCATED. | | | | | | 2)NOTE: PLEASE SEE PLANS STILLINDICATE | | | TWO METERS, HOWEVER ONLY ONE NEW ON | | | RISER. | | | PLEASE ALSO SEE NEW DISCONNECT NOW SHOWN | | | ON RISER IS NOT SHOWN ON PLANS.? | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE MAIN GRONDING | | | ELECTRODE SYSTEM SHALL CONTAIN ALL AS | | | SHOWN AT SUB-PANEL. CWP, GRND ROD AND | | | ANY NEW FOOTER STEEL. | | | 250.50 | | | SUB PANEL IS NOT REQUIRED TO ALSO | | | CONTAIN A GROUNDING ELECTRODE SYSTEM, | | | HOWEVER IT MAY BE DONE. | | | 250.50 | | | | | | 4)NOTE: PLEASE CLARIFY PUMP SHOWN AT | | | FIRE SPRINKLER ENTRANCE LOCATION. PLEASE | | | VERIFY IF "FIRE PUMP", PLEASE SUBMIT ALL | | | INFORMATION FOR FIRE PUMP CONTROLLER | | | ETC. | | | PLEASE CALL TO GO OVER INFORMATION | | | NEEDED IF INDEED THIS IS A FIRE PUMP. | | | NO OTHER PUMP INFORMATION COULD BE | | | LOCATED ON PANEL SCHEDULE OR LOAD CALCS. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE OFFICE DOES NOT SEEM | | | TO SHOW ANY RECEPTS? PLEASE VERIFY. | | | PLEASE SEE OFFICE LT AND RECEPTS ARE | | | INDICATED ON PANEL SCHEDULE? | | | PLEASE ALSO SEE #14 AWG IS SHOWN ON THE | | | 20A BRANCH CIRCUIT. A MAX LOAD OF 1440W | | | IS TO BE ON A 15A CIRCUIT. | | | PLEAS ADJUST.240.4,310.16,215.5 | | | | | | 6)NOTE: PLEASE VERIFY #10 AWG SHOWN FOR | | | SMOKE DETECTORS CIRCUIT? | | | PLEASE ALSO CLARIFY THIS AS A FIRE ALARM | | | PANEL IS BEING INSTALLED, WOULD NOTTHE | | | SMOKE DETECTORS BE WIRED INTOFACP? | | | PLEASE ALSO SEE THESE DEVICES COULD NOT | | | BE LOCATED ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE KNOW THAT SOME OF THE | | | ABOVE COMMENTS MAY AFFECT FIRE REVIEW. | | | | | | | | | ** PLEASE SEE ELECTRICAL SHEET IS | | | LABELED AS SHEET "L", AND "E" SHEET IS | | | FOR FIRE SPRKLR PLANS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-07-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-01 |
Time |
20:14 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-07-01 |
Time |
20:09 |
Sent To |
|
|
| Notes |
| 2005-07-01 00:00:00 | IN ELEC FOR REVIEW. | | | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2)NOTE: PLEASE SHOW MIN CONDUCTORS FROM | | | METER TO MAIN. 310.16/240.4,215.5 | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FROM MAIN TO PANEL. | | | 250.110,250.24,250.122 | | | | | | 4)NOTE: PLEASE SEE NEW RE-LOCATED PANEL | | | MAY NOT BE PLACED IN "STORAGE RM". | | | PLEASE SEE 110.26, 408.16, ETC. | | | | | | 5)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH PANEL SCHEDULE. | | | 215.5 | | | | | | 6)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | PLEASE SEE LOAD CALCULATIONS SUBMITTED | | | ARE RESIDENTIAL LOAD CALCS. | | | | | | 7)NOTE: PLEASE SEE PLANS SHOW TWO | | | METERS?? | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ANY OLD/ VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD/VOIDED SHEETS SHOULD BE | | | SUBMITTED FOR REFERENCE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-06-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-01 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-01 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | ***PROVISO*** | | | | | | PLANS SHOW A 'PUMP' NEAR THE SPRINKLER | | | RISER. DOES THIS BUILDING HAVE A FIRE | | | PUMP, OR IS THIS NOTE REFERENCING THE | | | FIRE SPRINKLER RISER? | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-11-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-11-10 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-11-10 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2005-11-10 00:00:00 | 1. PROVIDE PORTABLE FIRE EXTINGUISHERS. | | | | | | 2. SEPERATE SHOP DRAWINGS REQUIRED FOR | | | FIRE SPRINKLER SYSTEM ADDITIONS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-28 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-28 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2005-07-28 00:00:00 | ******DENIED****** | | | | | | 1) DRAWINGS SHOW AN ADDRESS ON THE | | | BUILDING THAT SHALL BE AT LEAST 6" IN | | | HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. | | | | | | 2) PLEASE INDICATE WHAT CONTENTS WILL BE | | | STORED IN STORAGE AREAS. | | | | | | 3) PLEASE ILLUSTRATE THE TOTAL OCCUPANT | | | LOAD. DOORS SERVING AREAS WITH OCCUPANT | | | LOADS GREATER THAN 50 PERSONS SHALL | | | SWING IN THE DIRECTION OF TRAVEL. PLEASE | | | PROVIDE FURTHER INFORMATION REGARDING | | | SECURITY GATES. | | | | | | 4) PLEASE CLEARLY SHOW THE LOCATIONS OF | | | ALL ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHTING. EMERGENCY LIGHTING IS REQUIRED | | | NFPA 101, SECTION 37.2.9. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 6) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 7) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | WPBFR(561) 804-4756 | | | PLAN REVIEW(561) 805-6722 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-08-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-26 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-26 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2006-08-26 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-06-01 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-06-01 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-06-01 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2006-06-01 00:00:00 | GAVE TO ZONING TO EXPIDITE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-05-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-22 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-22 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2006-05-25 00:00:00 | 5/25/06-SUBMITTAL W/PLANS WAITING FOR | | | "COMM" BD | | 2006-05-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-11 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-11 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2005-10-21 00:00:00 | TO "COMM" BD#47 | | 2005-10-11 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-08-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-08 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-24 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2005-06-24 00:00:00 | WAITING FOR "COMM" BD | | | TO "COMM" BD#55 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-14 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-14 |
Time |
16:09 |
Sent To |
E |
|
| Notes |
| 2005-06-14 00:00:00 | TO ELEC BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-07 |
Time |
08:44 |
Rev Time |
1.00 |
| Received By |
tgordon |
Date |
2006-09-07 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | PLANS GIVEN TO LUIS M. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-30 |
Time |
16:48 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-06-21 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2006-05-30 00:00:00 | *** DENIED *** | | | 1) PLANS NEED TO REFER TO THE 2001 FBC, | | | NOT THE 2004 FBC, AS THE BUILDING PERMIT | | | WAS APPLYED FOR BEFORE 10-1-05. | | | | | | 2) DETAILED MANUFACTURE'S | | | SPECIFICATION'S AND INSTALLATION | | | INSTRUCTIONS FOR THE 4 EXHAUST FANS | | | BEING INSTALLED, MUST BE ON JOB SITE FOR | | | INSPECTIONS. PER 2004 FBC/M 304.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-20 |
Time |
13:21 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2005-07-20 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | NO MECHANICAL CONTRACTOR OR WORK | | | INDICATED WITH PERMIT APPLICATION. | | | PLAN SHEET A3 INDICATES "METAL | | | VENTILATOR" (LOUVERS).PLEASE NOTE | | | MINIMUM VENTILATION REQUIRED PER 2001 | | | FBC(M) TABLE 403.3. BATHROOM SHALL HAVE | | | A WINDOW WITH A MINIMUM OF 3 SQUARE FEET | | | OF OPEN AREA OR HAVE MECHANICAL | | | VENTILATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-07 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-07 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | NO RISER DIAGRAM REQUIRED. EXISTING | | | TOILET ROOM, MOP SINK, AND DRINKING | | | FOUNTAIN. MOVING LAV AROUND THE CORNER | | | ONLY. DEMO ON SEPARATE PERMIT |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-05-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-05-31 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-05-31 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2006-05-31 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | COMMENTS FROM TWO PREVIOUS REVIEWS: | | | | | | COMMENTS FROM PREVIOUS REVIEW: | | | | | | | | | 4. SUBMIT A WATER AND A SANITARY RISER | | | DIAGRAM IN ISOMETRIC FORM. THE WATER | | | RISER DIAGRAM SHALL SHOW ALL PIPE SIZES, | | | VALVES, AND, IF REQUIRED BY SECTION | | | 604.9, WATER HAMMER ARRESTORS. - THE | | | SANT. RISER DIAGRAM SHALL SHOW ALL PIPE | | | SIZES, VENTS, TRAPS AND POINT OF | | | CONNECTION. SECTION 104.3.1.1. - NO | | | WATER RISER ISOMETRIC SUBMITTED. TWO | | | SANITARY RISER ISOMETRICS SUBMITTED, BUT | | | NETHER RISER DIAGRAM MEETS CODE | | | REQUIREMENTS NOR DO THEY REFLECT THE | | | FLOOR PLAN. THE RISER DIAGRAM ON SHEET | | | A8 DOES NOT REFLECT THE FLOOR PLAN | | | BECAUSE THE DRINKING FOUNTAIN IS MISSING | | | AND THE MOP SINK IS SHOWN ON THE SAME | | | SIDE OF THE ROOM AS THE W/C. THE LAV IS | | | NOT VENTED AS SHOWN. THE MOP SINK | | | REQUIRES A TRAP. SHOW ALL PIPE SIZES. | | | SECTIONS 104.2.1, 901.2.1, 1002.1- THE | | | SANT. RISER DIAGRAM SUBMITTED ON AN | | | 8-1/2" X 11" SHEET DOES NOT REFLECT THE | | | FLOOR PLAN, THE MOP SINK, LAV, AND | | | DRINKING FOUNTAIN ARE NOT VENTED. | | | HORIZONTAL DRY VENTS ARE PROHIBITED. THE | | | W/C SHALL NOT BE DOUBLE TRAPPED. THE W/C | | | HAS AN INTEGRAL TRAP. SECTIONS 104.2.1, | | | 1002.1., 901.2.1, 905.3, 905.4. - THE | | | TITLE BLOCK FOR THE ENGINEER CAN NOT BE | | | READ. FAC 61G15-23.002(2) & FS 471.2055 | | | - SUBMIT ONLY ONE SANT. RISER DIAGRAM | | | THAT MEETS CODE REQUIREMENTS AND | | | REFLECTS THE FLOOR PLAN. SECTION | | | 104.3.1.1. | | | ***NO WATER RISER DIAGRAM HAS BEEN | | | SUBMITTED. - SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS | | | SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF | | | THE BATHROOM GROUP. (SEE RED-LINED | | | EXAMPLE OF A SANT. RISER DIAGRAM THAT | | | REFLECTS THE FLOOR PLAN AND MEETS CODE | | | REQUIREMENTS. | | | | | | 6. SHT A8 HC LAV DETAILS 1 & 2 SUBMIT | | | DETAILS FOR THE FOLLOWING: | | | FOR THE W/C: | | | A. 11-4.16.2 CLEAR FLOOR SPACE - NOT | | | SHOWN. | | | FOR THE LAV: | | | F. 11-4.19.5 FAUCETS - NOT SHOWN PER | | | CODE SECTION. | | | FOR THE DRINKING FOUNTAIN. | | | G. 11-4.15.2 SPOUT HEIGHT | | | H. 11-4.15.3 SPOUT LOCATION | | | I. 11-4.15.4 CONTROLS | | | J. 11-4.15.5 CLEARANCES & CLEAR FLOOR | | | SPACE. | | | K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. - NO | | | DETAIL FOR THE DRINKING FOUNTAIN | | | SUBMITTED. | | | ***THE ABOVE ACCESSIBLE REQUIREMENTS ARE | | | NOT SHOWN ON THE PLANS AS REQUESTED. | | | | | | 7. SHT A1 IN THE REMOVAL OF ANY PART OF | | | A DRAINAGE SYSTEM, DEAD ENDS ARE | | | PROHIBITED. (INFORMATIONAL) - ALL | | | CAPPED PIPES FOR DEMO SHALL BE INSPECTED | | | BY THE FIELD INSPECTOR PRIOR TO | | | COVERING. SECTION 704.5 - INDICATE ON | | | THE DEMO SHEET WITH A NOTE. | | | ***THE ABOVE INFORMATION IS NOT SHOWN ON | | | THE PLANS AS REQUESTED. | | | | | | **************NEW COMMENT************** | | | | | | 1B. THE ADDRESS REQUIRED IN THE TITLE | | | BLOCK OF THE ENGINEER DOES NOT REFLECT | | | THE ADDRESS OF RECORD ON THE DBPR WEB | | | SITE. PLEASE CORRELATE THE INFORMATION | | | IN THE TITLE BLOCK TO REFLECT THE DBPR | | | WEB SITE. FAC 61G15-23.002(2) AND FS | | | 471.025. (SEE ATTACHED SHEET FROM DBPR) | | | | | | 2B. SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS 553.80(2)(B). | | | THIS IS GIVEN AS A NOTICE. IF COMMENTS | | | ARE NOT ADDRESSED AFTER THE THIRD | | | REVIEW, 4 TIMES THE PLAN REVIEW PORTION | | | WILL BE ACCESSED TO THE DESIGN | | | PROFESSIONAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-12-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-12-14 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2005-12-14 |
Time |
18:22 |
Sent To |
|
|
| Notes |
| 2005-12-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | COMMENTS FROM PREVIOUS REVIEW: | | | | | | 3. SHT C-1 MINIMUM FACILITIES REQUIRES A | | | DRINKING FOUNTAIN AND A SERVICE SINK PER | | | TABLE 403.1. SHT A2 FLOOR PLAN DOES NOT | | | SHOW THE LOCATION OF THE DRINKING | | | FOUNTAIN, NOR DOES IT SHOW THE LOCATION | | | OF THE SERVICE SINK. PLEASE SHOW THE | | | LOCATION OF THESE REQUIRED FIXTURES. - | | | MINIMUM FACILITIES PROVIDED INDICATE NO | | | SINKS ARE REQUIRED. PER TABLE 403.1 1 | | | SERVICE SINK IS REQUIRED. PLEASE | | | INDICATE ON TABLE SHOWN ON SHT C-1. | | | 4. SUBMIT A WATER AND A SANITARY RISER | | | DIAGRAM IN ISOMETRIC FORM. THE WATER | | | RISER DIAGRAM SHALL SHOW ALL PIPE SIZES, | | | VALVES, AND, IF REQUIRED BY SECTION | | | 604.9, WATER HAMMER ARRESTORS. - THE | | | SANT. RISER DIAGRAM SHALL SHOW ALL PIPE | | | SIZES, VENTS, TRAPS AND POINT OF | | | CONNECTION. SECTION 104.3.1.1. - NO | | | WATER RISER ISOMETRIC SUBMITTED. TWO | | | SANITARY RISER ISOMETRICS SUBMITTED, BUT | | | NETHER RISER DIAGRAM MEETS CODE | | | REQUIREMENTS NOR DO THEY REFLECT THE | | | FLOOR PLAN. THE RISER DIAGRAM ON SHEET | | | A8 DOES NOT REFLECT THE FLOOR PLAN | | | BECAUSE THE DRINKING FOUNTAIN IS MISSING | | | AND THE MOP SINK IS SHOWN ON THE SAME | | | SIDE OF THE ROOM AS THE W/C. THE LAV IS | | | NOT VENTED AS SHOWN. THE MOP SINK | | | REQUIRES A TRAP. SHOW ALL PIPE SIZES. | | | SECTIONS 104.2.1, 901.2.1, 1002.1- THE | | | SANT. RISER DIAGRAM SUBMITTED ON AN | | | 8-1/2" X 11" SHEET DOES NOT REFLECT THE | | | FLOOR PLAN, THE MOP SINK, LAV, AND | | | DRINKING FOUNTAIN ARE NOT VENTED. | | | HORIZONTAL DRY VENTS ARE PROHIBITED. THE | | | W/C SHALL NOT BE DOUBLE TRAPPED. THE W/C | | | HAS AN INTEGRAL TRAP. SECTIONS 104.2.1, | | | 1002.1., 901.2.1, 905.3, 905.4. - THE | | | TITLE BLOCK FOR THE ENGINEER CAN NOT BE | | | READ. FAC 61G15-23.002(2) & FS 471.2055 | | | - SUBMIT ONLY ONE SANT. RISER DIAGRAM | | | THAT MEETS CODE REQUIREMENTS AND | | | REFLECTS THE FLOOR PLAN. SECTION | | | 104.3.1.1. | | | 6. SHT A8 HC LAV DETAILS 1 & 2 SUBMIT | | | DETAILS FOR THE FOLLOWING: | | | FOR THE W/C: | | | A. 11-4.16.2 CLEAR FLOOR SPACE - NOT | | | SHOWN. | | | B. 11-4.16.3 HEIGHT (SHOWN MIN.) - NO | | | SHOWN PER CODE SECTION. | | | D. 11-4.16.5 FLUSH CONTROLS - NOT SHOWN | | | PER CODE SECTION. | | | FOR THE LAV: | | | F. 11-4.19.5 FAUCETS - NOT SHOWN PER | | | CODE SECTION. | | | LAV SHALL BE MINIMUM 15" OFF WALL TO THE | | | CENTERLINE OF THE FIXTURE. - MEASUREMENT | | | NOT SHOWN. | | | FOR THE DRINKING FOUNTAIN. | | | G. 11-4.15.2 SPOUT HEIGHT | | | H. 11-4.15.3 SPOUT LOCATION | | | I. 11-4.15.4 CONTROLS | | | J. 11-4.15.5 CLEARANCES & CLEAR FLOOR | | | SPACE. | | | K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. - NO | | | DETAIL FOR THE DRINKING FOUNTAIN | | | SUBMITTED. | | | 7. SHT A1 IN THE REMOVAL OF ANY PART OF | | | A DRAINAGE SYSTEM, DEAD ENDS ARE | | | PROHIBITED. (INFORMATIONAL) - ALL | | | CAPPED PIPES FOR DEMO SHALL BE INSPECTED | | | BY THE FIELD INSPECTOR PRIOR TO | | | COVERING. SECTION 704.5 - INDICATE ON | | | THE DEMO SHEET WITH A NOTE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-04 |
Time |
17:27 |
Rev Time |
3.42 |
| Received By |
kstevens |
Date |
2005-08-04 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2005-08-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1. SHT C-1 INDICATES OCCUPANCY AS | | | MERCANTILE, BUT FLOOR PLAN AND "STORAGE" | | | ON THE FRONT OF THE BUILDING INDICATE | | | THAT THE OCCUPANCY WILL BE STORAGE. - | | | MINIMUM FACILITIES FOR PLUMBING FIXTURES | | | WILL BE CALCULATED FOR STORAGE. TABLES | | | 1003.1 & 403.1. | | | 2. SHT C-1 UNDER MINIMUM NUMBER OF | | | PLUMBING FIXTURES, SECTION 403.2 | | | EXCEPTION 2 IS REFERENCED. PLEASE | | | INDICATE ON THE PLANS THE NUMBER OF | | | EMPLOYEES EMPLOYED FOR RECORD. | | | 3. SHT C-1 MINIMUM FACILITIES REQUIRES A | | | DRINKING FOUNTAIN AND A SERVICE SINK PER | | | TABLE 403.1. SHT A2 FLOOR PLAN DOES NOT | | | SHOW THE LOCATION OF THE DRINKING | | | FOUNTAIN, NOR DOES IT SHOW THE LOCATION | | | OF THE SERVICE SINK. PLEASE SHOW THE | | | LOCATION OF THESE REQUIRED FIXTURES. | | | 4. SUBMIT A WATER AND A SANITARY RISER | | | DIAGRAM IN ISOMETRIC FORM. THE WATER | | | RISER DIAGRAM SHALL SHOW ALL PIPE SIZES, | | | VALVES, AND, IF REQUIRED BY SECTION | | | 604.9, WATER HAMMER ARRESTORS. - THE | | | SANT. RISER DIAGRAM SHALL SHOW ALL PIPE | | | SIZES, VENTS, TRAPS AND POINT OF | | | CONNECTION. SECTION 104.3.1.1. | | | 5. SHT A-2 NEW FLOOR PLAN STATES "SEE | | | BATHROOM DETAIL ON SH A-4". NO BATHROOM | | | DETAIL ON SHT A4. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | 6. SHT A8 HC LAV DETAILS 1 & 2 | | | MEASUREMENTS CAN NOT BE READ. SUBMIT | | | DETAILS FOR THE FOLLOWING: | | | FOR THE W/C: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.3 HEIGHT (SHOWN MIN.) | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | WATER CLOSET TO BE 18" OFF WALL TO THE | | | CENERLINE OF THE FIXTURE. | | | FOR THE LAV: | | | F. 11-4.19.5 FAUCETS | | | LAV SHALL BE MINIMUM 15" OFF WALL TO THE | | | CENTERLINE OF THE FIXTURE. | | | FOR THE DRINKING FOUNTAIN. | | | G. 11-4.15.2 SPOUT HEIGHT | | | H. 11-4.15.3 SPOUT LOCATION | | | I. 11-4.15.4 CONTROLS | | | J. 11-4.15.5 CLEARANCES & CLEAR FLOOR | | | SPACE. | | | K. 11-4.1.3(10)(A) FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. | | | 7. SHT A1 IN THE REMOVAL OF ANY PART OF | | | A DRAINAGE SYSTEM, DEAD ENDS ARE | | | PROHIBITEDL. (INFORMATIONAL) - ALL | | | CAPPED PIPES FOR DEMO SHALL BE INSPECTED | | | BY THE FIELD INSPECTOR PRIOR TO | | | COVERING. SECTION 704.5 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-06-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-06-15 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-06-15 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2006-06-15 00:00:00 | 6/15/06 ***PASSED*** | | | | | | REPLACEMENT OF HURRICANE | | | DAMAGE...ADDITIONAL IMPROVEMENTS DO NOT | | | EXCEED 50% OF THE VALUE OF THE | | | STRUCTURE. | | | | | | JOHN ROACH, SENIOR PLANNER | | | (561) 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2006-02-02 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-02-02 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-02-02 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2006-02-02 00:00:00 | 2/2/2006 ***FAILED*** | | | | | | AS INDICATED IN PREVIOUS REVIEWS, THE | | | SUBJECT COMMERCIAL PROPERTY IS LOCATED | | | WITHIN A RESIDENTIAL ZONING DISTRICT AND | | | IS CONSIDERED A NONCONFORMING STRUCTURE | | | AND MAJOR USE NONCONFORMITY...SUBJECT TO | | | ARTICLE XVI OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS. | | | | | | ALTERATIONS AND REPAIRS ARE LIMITED TO | | | THE FOLLOWING: | | | | | | A) REPAIRS RELATED TO DAMAGE THAT WAS A | | | RESULT OF A NATURAL DISASTER (I.E. | | | HURRICANE) WITHIN THE LAST 12 MONTHS. | | | THIS REQUIRES PROVIDING PROOF TO THE | | | CITY THAT THE REPAIRS ARE REQUIRED AS A | | | RESULT OF THE NATURAL DISASTER | | | (INSURANCE CLAIMS, ETC.). | | | | | | B) ALTERATIONS AND/OR REPAIRS ARE | | | PERMITTED SO LONG AS THEY DO NOT CREATE | | | A NEW NONCONFORMITY OR INCREASE AN | | | EXISTING NONCONFORMITY AND ARE LIMITED | | | TO 50% OF THE VALUE OF THE STRUCTURE. | | | THE VALUE MAY BE DETERMINED BY MEANS OF | | | THE COUNTY PROPERTY APPRAISER OR BY A | | | PRIVATE APPRAISAL.THIS LIMITATION | | | APPLIES TO ALL ALTERATIONS/REPAIRS | | | OUTSIDE OF THAT RESULTING FROM A NATURAL | | | DISASTER. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | PLANNER AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2005-07-18 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2005-07-18 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2005-07-18 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2005-07-18 00:00:00 | 7/18/2005 ***FAILED*** | | | | | | 1) LOCATED IN SF14 ZONING DISTRICT AND | | | CONSIDERED A NONCONFORMING STRUCTURE AND | | | MAJOR USE NONCONFORMITY. | | | | | | 1A) NONCONFORMING STRUCTURE SHALL NOT BE | | | IMPROVED, CONSTRUCTED, ENLARGED OR | | | ALTERED IN ANY MANNER TO CREATE A NEW | | | NONCONFORMITY OR TO INCREASE AN EXISTING | | | NONCONFORMITY [SECTION 94-513(A)(2)]. | | | THIS APPLIES TO THE CONSTRUCTION OF THE | | | PARKING LOT. | | | | | | 2) ON-STREET PARKING SHALL BE APPROVED | | | BY THE CITY TRANSPORTATION ENGINEER | | | (BRIAN COLLINS - 494-1040). | | | | | | 3) IN RESIDENTIAL DISTRICT, NO FENCE OR | | | WALL SHALL EXCEED 48 INCHES IN HEIGHT | | | WITHIN THE REQUIRED FRONT SETBACK | | | [SECTION 94-302(B)(1)].THIS APPLIES TO | | | THE NEW ROLLING GATE. | | | | | | 4) ADJUST PLANS TO SHOW THAT THE | | | CHAIN-LINK FENCE ALONG KANUGA IS | | | EXISTING AND NOT PROPOSED. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | PLANNER AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-14 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2005-07-14 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2005-07-14 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2005-07-14 00:00:00 | 7/14/2005 ***FAILED*** | | | | | | 1) LOCATED IN SF14 ZONING DISTRICT AND | | | CONSIDERED A NONCONFORMING STRUCTURE AND | | | MAJOR USE NONCONFORMITY. | | | | | | 1A) NONCONFORMING STRUCTURE SHALL NOT BE | | | IMPROVED, CONSTRUCTED, ENLARGED OR | | | ALTERED IN ANY MANNER TO CREATE A NEW | | | NONCONFORMITY OR TO INCREASE AN EXISTING | | | NONCONFORMITY [SECTION 94-513(A)(2)]. | | | THIS INCLUDES THE EXPANSION OF THE | | | BUILDING AND THE CONSTRUCTION OF THE | | | PARKING LOT. | | | | | | 2) ATTACHED OR DETACHED ADDITIONS IN | | | EXCESS OF 1,000 SQUARE FEET TO AN | | | EXISTING RESIDENTIAL OR NON RESIDENTIAL | | | STRUCTURE REQUIRES INFORMAL SITE PLAN | | | REVIEW [SECTION 94-35(D)(5)]. | | | | | | 3) ON-STREET PARKING SHALL BE APPROVED | | | BY THE CITY TRANSPORTATION ENGINEER | | | (BRIAN COLLINS - 494-1040). | | | | | | 4) IN RESIDENTIAL DISTRICT, NO FENCE OR | | | WALL SHALL EXCEED 48 INCHES IN HEIGHT | | | WITHIN THE REQUIRED FRONT SETBACK | | | [SECTION 94-302(B)(1)]. | | | | | | 5) EXPANSION NOT APPROVED BY THE | | | HISTORIC PRESERVATION DIVISION. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | PLANNER AT (561) 822-1435. |
|
|