Plan Review Details - Permit 05060893
Plan Review Stops For Permit 05060893
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-27 Cont ID  
Sent By jwitmer Date 2005-07-27 Time 07:27 Rev Time 0.33
Received By jwitmer Date 2005-07-27 Time 07:26 Sent To PC
Notes
2005-07-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060893
 ADD: 3410 EMBASSY DR
 CONT:FIORENTINO ELEC
 TEL: (561)436-4945
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE INFORMATION ON THE SLAB AND
 ATACHMENT OF UNIT TO SLAB.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By btrobaug Date 2005-06-27 Time 09:37 Rev Time 0.33
Received By btrobaug Date 2005-06-27 Time 09:21 Sent To M
Notes
2005-06-27 00:00:00 
 INDICATE THE TRANSFER AWITCH BEING USED
 AND SUBMIT A LOAD CALCULATION INDICATING
 THE SWITCH IS ADEQUATE FOR THE LOAD TO
 BE SERVED.
  
 SHOW THE PHYSICAL LOCATION OF ALL
 SERVICE AND EMERGENCY ON A SITE PLAN SO
 THAT SIGNAGE AND DISCONNECTING MEANS CAN
 BE REVIEWED FOR COMPLIANCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-22 Cont ID  
Sent By adarroug Date 2005-06-22 Time 13:58 Rev Time 0.00
Received By adarroug Date 2005-06-22 Time 13:58 Sent To E
Notes
2005-06-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 16:08 Rev Time 0.00
Received By shill Date 2005-06-10 Time 16:08 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By hmoser Date 2005-07-06 Time 17:06 Rev Time 0.00
Received By hmoser Date 2005-07-06 Time 16:55 Sent To P
Notes
2005-07-06 00:00:00APPLICATION IS FOR TRANSFER SWITCH AND
 SUBPANEL ONLEY.HM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 07:53 Rev Time 0.33
Received By jleech Date 2005-07-09 Time 07:53 Sent To B
Notes
2005-07-09 00:00:00PERMIT APPLICATION FOR GAS MUST BE WITH
 RES GEN APPLICATION. GAS APPLICATION
 MUST BE PULLED BY A LIC. PLUMBING
 CONTRACTOR. PLANS REQUIRED WITH
 APPLICATION.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By mmclean Date 2005-06-21 Time 11:45 Rev Time 0.00
Received By mmclean Date 2005-06-21 Time 11:45 Sent To I
Notes
2005-06-21 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF SURVEY
 SHOWING THE LOCATION OF GENERATOR WITH
 SETBACK(DIMENSION) FROM PROPERTY LINE
 AND STRUCTURE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720