| Plan Review Stops For Permit 05060829 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-09-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-13 |
Time |
15:50 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-09-13 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-12 |
Time |
16:45 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-12 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2005-07-12 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)THE PLANS STATE THAT THE DESIGN | | | WILL COMPLY WITH 140MPH WINDS, AND ALSO | | | THAT THE GENERATOR WILL BE INSTALLED | | | ACCORDING TO MANUFACTURER'S | | | SPECIFICATIONS.PLEASE EITHER PROVIDE | | | MFGR SPEC AND HAVE ENGINEER REVIEW OR | | | INCORPORATE ANCHORING INTO THE PLAN. | | | FBC1606.1.3. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-09-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-03 |
Time |
15:06 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-09-03 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2005-09-03 00:00:00 | STAMPED SPECS BOOKS. | | | | | | SIGNAGE REQUIRED FOR LOCATION OF MDP | | | INSIDE MAIN ELECTRICAL RM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-29 |
Time |
17:39 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-06-29 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT MANUFACTURES | | | SPECS/CUT SHEETS FOR GENERATOR, ATS, AND | | | FUEL TANK. | | | PLEASE BE SURE ALL EQUIPMENT INDICATES A | | | LISTING FROM A NRTL. PLEASE SEE ATS TO | | | BE SERVICE ENTRANCE RATED.THIS IS NOTED | | | ON PLANS, HOWEVER SPECS MUST INDICATE | | | THIS. | | | 215.5,225.36 | | | | | | 2)NOTE: PLEASE SEE DUE TO SPECS FOR ATS, | | | NOT BEING SUBMITTED AT THIS TIME,THE MCB | | | INDICATED FOR ATS CAN NOT BE VERIFIED IF | | | LOCATED ON THE OUTSIDE OF THE ATS WITH A | | | MANUAL MEANS OF DISC? | | | 110.27, 225.31-36 | | | | | | 3)NOTE: PLEASE SEE 445.13 FOR MIN SIZING | | | OF CONDUCTORS. | | | | | | 4)NOTE: PLEASE SEE NO LOAD CALCULATIONS | | | FOR LOADS TO BE SERVED BY GENERATOR WERE | | | SUBMITTED. PLEASE SEE 702.5 | | | 220 | | | | | | 5)NOTE: PLEASE SEE ZONING COMMENTS FOR | | | SITE/SURVEY. THIS SHALL INDICATE FLOOD | | | ZONE AND BFE. UNIT SHALL BE MOUNTED | | | ABOVE BFE. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-09-12 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-09-12 |
Time |
13:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-07-11 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-07-11 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2005-07-11 00:00:00 | 1. PLEASE PROVIDE DETAILS ON GENERATOR | | | AND SUB-BASE FUEL TANK. | | | | | | 2. WHAT LISTINGS ARE PRESENT FOR | | | THE FUEL TANK. | | | | | | 3. THE VICINITY MAP HAS NO SCALE | | | PROVIDED. PLEASE PROVIDE MINIMUM | | | DISTANCES TO ADJACENT PROPERTY LINES | | | IMPORTANT BUILDINGS, EXIT DOORS, ETC. | | | | | | 4. SINCE THE PROPOSED FUEL TANK IS | | | ABOVE GROUND, PLEASE PROVIDE ALL DETAILS | | | REGARDING LISTINGS, SPECIFICATIONS, | | | LABELING, ETC.OF THE FUEL TANK. | | | | | | 5. FUEL INSTALLATION TO COMPLY WITH | | | NFPA 30. | | | | | | 6. WHAT EQUIPMENT IS THE GENERATOR | | | EXPECTED TO SUPPLY EMERGENCY POWER FOR. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 835-2910 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-01 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-01 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | TO "COMM" BD#27 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-13 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-06-10 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2005-06-17 00:00:00 | COMM BOARD #20 | | | | | 2005-06-10 00:00:00 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-30 |
Time |
14:12 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-09-30 |
Time |
13:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-13 |
Time |
09:40 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2005-07-13 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2005-07-13 00:00:00 | DENIED: | | | 1.PROVIDE MANUFACTURER'S SUBMITTAL | | | DATA FOR THE GENERATOR & SUB-BASE FUEL | | | TANK. | | | | | | 2.PROVIDE DISTANCE BETWEEN THE | | | GENERATOR & THE EXISTING BUILDING.PLAN | | | SHEET E-1 INDICATES 4 FT.PLEASE SHOW | | | DISTANCES TO OPENINGS, SHOW COMPLIANCE | | | WITH 2001 FBC(M)501.3. | | | | | | 3.PROVIDE DETAIL OF HOW THE | | | GENERATOR/FUEL SUB-BASE WILL BE ANCHORED | | | TO THE SLAB. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-09-30 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-09-30 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2005-09-30 00:00:00 | DIESEL FUEL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-09-13 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2005-09-13 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2005-09-13 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-07-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-07-08 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-07-08 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2005-07-08 00:00:00 | DENIED, | | | 1. MUST APPLY FOR A MINOR AMENDMENT, BY | | | CALL PLANNING & ZONING DEPT AT 822-1435 |
|
|