Plan Review Details - Permit 05060829
Plan Review Stops For Permit 05060829
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By shill Date 2005-09-13 Time 15:50 Rev Time 0.50
Received By shill Date 2005-09-13 Time 15:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By shill Date 2005-07-12 Time 16:45 Rev Time 0.50
Received By shill Date 2005-07-12 Time 16:45 Sent To  
Notes
2005-07-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE PLANS STATE THAT THE DESIGN
 WILL COMPLY WITH 140MPH WINDS, AND ALSO
 THAT THE GENERATOR WILL BE INSTALLED
 ACCORDING TO MANUFACTURER'S
 SPECIFICATIONS.PLEASE EITHER PROVIDE
 MFGR SPEC AND HAVE ENGINEER REVIEW OR
 INCORPORATE ANCHORING INTO THE PLAN.
 FBC1606.1.3.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 15:06 Rev Time 1.00
Received By dpalmer Date 2005-09-03 Time 13:35 Sent To  
Notes
2005-09-03 00:00:00STAMPED SPECS BOOKS.
  
 SIGNAGE REQUIRED FOR LOCATION OF MDP
 INSIDE MAIN ELECTRICAL RM.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-29 Cont ID  
Sent By dpalmer Date 2005-06-29 Time 17:39 Rev Time 0.75
Received By dpalmer Date 2005-06-29 Time 17:31 Sent To  
Notes
2005-06-29 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/CUT SHEETS FOR GENERATOR, ATS, AND
 FUEL TANK.
 PLEASE BE SURE ALL EQUIPMENT INDICATES A
 LISTING FROM A NRTL. PLEASE SEE ATS TO
 BE SERVICE ENTRANCE RATED.THIS IS NOTED
 ON PLANS, HOWEVER SPECS MUST INDICATE
 THIS.
 215.5,225.36
  
 2)NOTE: PLEASE SEE DUE TO SPECS FOR ATS,
 NOT BEING SUBMITTED AT THIS TIME,THE MCB
 INDICATED FOR ATS CAN NOT BE VERIFIED IF
 LOCATED ON THE OUTSIDE OF THE ATS WITH A
 MANUAL MEANS OF DISC?
 110.27, 225.31-36
  
 3)NOTE: PLEASE SEE 445.13 FOR MIN SIZING
 OF CONDUCTORS.
  
 4)NOTE: PLEASE SEE NO LOAD CALCULATIONS
 FOR LOADS TO BE SERVED BY GENERATOR WERE
 SUBMITTED. PLEASE SEE 702.5
 220
  
 5)NOTE: PLEASE SEE ZONING COMMENTS FOR
 SITE/SURVEY. THIS SHALL INDICATE FLOOD
 ZONE AND BFE. UNIT SHALL BE MOUNTED
 ABOVE BFE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 13:55 Rev Time 0.00
Received By mcarsill Date 2005-09-12 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 10:06 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 10:06 Sent To  
Notes
2005-07-11 00:00:001. PLEASE PROVIDE DETAILS ON GENERATOR
 AND SUB-BASE FUEL TANK.
  
 2. WHAT LISTINGS ARE PRESENT FOR
 THE FUEL TANK.
  
 3. THE VICINITY MAP HAS NO SCALE
 PROVIDED. PLEASE PROVIDE MINIMUM
 DISTANCES TO ADJACENT PROPERTY LINES
 IMPORTANT BUILDINGS, EXIT DOORS, ETC.
  
 4. SINCE THE PROPOSED FUEL TANK IS
 ABOVE GROUND, PLEASE PROVIDE ALL DETAILS
 REGARDING LISTINGS, SPECIFICATIONS,
 LABELING, ETC.OF THE FUEL TANK.
  
 5. FUEL INSTALLATION TO COMPLY WITH
 NFPA 30.
  
 6. WHAT EQUIPMENT IS THE GENERATOR
 EXPECTED TO SUPPLY EMERGENCY POWER FOR.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 13:10 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 13:10 Sent To  
Notes
2005-09-01 00:00:00TO "COMM" BD#27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-13 Cont ID  
Sent By shill Date 2005-07-13 Time 11:49 Rev Time 0.00
Received By pkrauss Date 2005-06-10 Time 11:33 Sent To  
Notes
2005-06-17 00:00:00COMM BOARD #20
  
2005-06-10 00:00:00WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By pkrauss Date 2005-09-30 Time 14:12 Rev Time 0.40
Received By pkrauss Date 2005-09-30 Time 13:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-13 Cont ID  
Sent By pkrauss Date 2005-07-13 Time 09:40 Rev Time 0.45
Received By pkrauss Date 2005-07-13 Time 09:40 Sent To  
Notes
2005-07-13 00:00:00DENIED:
 1.PROVIDE MANUFACTURER'S SUBMITTAL
 DATA FOR THE GENERATOR & SUB-BASE FUEL
 TANK.
  
 2.PROVIDE DISTANCE BETWEEN THE
 GENERATOR & THE EXISTING BUILDING.PLAN
 SHEET E-1 INDICATES 4 FT.PLEASE SHOW
 DISTANCES TO OPENINGS, SHOW COMPLIANCE
 WITH 2001 FBC(M)501.3.
  
 3.PROVIDE DETAIL OF HOW THE
 GENERATOR/FUEL SUB-BASE WILL BE ANCHORED
 TO THE SLAB.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-30 Cont ID  
Sent By pschmitz Date 2005-09-30 Time 07:51 Rev Time 0.00
Received By pschmitz Date 2005-09-30 Time 07:51 Sent To  
Notes
2005-09-30 00:00:00DIESEL FUEL

Review Stop Z ZONING
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By jroach Date 2005-09-13 Time 14:11 Rev Time 0.00
Received By jroach Date 2005-09-13 Time 14:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-08 Cont ID  
Sent By mmclean Date 2005-07-08 Time 12:42 Rev Time 0.00
Received By mmclean Date 2005-07-08 Time 12:42 Sent To  
Notes
2005-07-08 00:00:00DENIED,
 1. MUST APPLY FOR A MINOR AMENDMENT, BY
 CALL PLANNING & ZONING DEPT AT 822-1435