Plan Review Details - Permit 05060766
Plan Review Stops For Permit 05060766
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-12-05 Cont ID  
Sent By alange Date 2005-12-05 Time 09:53 Rev Time 0.66
Received By alange Date 2005-12-05 Time 09:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-10-06 Cont ID  
Sent By alange Date 2005-10-06 Time 08:23 Rev Time 0.66
Received By alange Date 2005-10-06 Time 08:11 Sent To  
Notes
2005-10-06 00:00:00DENIED
  
 3.**ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT:
 A.TRI-PLY BITUMEN ROOF PRODUCT
 APPROVAL.SELECT THE ASSEMBLY THAT WILL
 BE INSTALLED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-22 Cont ID  
Sent By alange Date 2005-08-22 Time 08:01 Rev Time 0.75
Received By alange Date 2005-08-22 Time 07:33 Sent To M
Notes
2005-08-22 00:00:00DENIED
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING:STRAPS AND
 TIEDOWNS AND LINTELS.
 **ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 8.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By alange Date 2005-07-14 Time 15:57 Rev Time 1.66
Received By alange Date 2005-07-14 Time 15:42 Sent To  
Notes
2005-07-14 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING:
 ROOFING, EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION, STRAPS AND TIEDOWNS AND
 LINTELS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION HAS BEEN
 REVISED TO $41,789.00. ADDITION PERMIT
 FEES OF $445.58 ARE DUE PRIOR TO
 RESUBMITTING PLANS.
  
 5.THE MINIMUM FOOTING DEPTH BELOW
 GRADE SHALL BE 12"FBC1804.2.3
  
 6.SHOW SIZE AND TYPE OF EXISTING
 BEDROOM WINDOW ADJACENT TO ROOM
 ADDITION.FBC 1005.4
  
 7.SHOW TIE-IN DETAIL FOR NEW ADDITION
 TO EXISTING STRUCTURE.INCLUDE METHOD
 OF SLAB TIE-IN AND ROOF TIE-IN.SO ALSO
 HOW EXISTING ROOF WILL BE VENTILATED
 SINCE IT APPEARS TO LOOSING VENTILATION
 ACROSS THE BACK OF THE HOUSE.
  
 8.SUBMIT TWO COPIES OF TABLE 600
 ENERGY CALCS.
  
 9.ROOF SHEATHING SHALL COMPLY WITH FBC
 2306.1 WPB AMMENDMENTS.PLANS SHOW
 DIFFERENT NAILING PATTERNS THROUGHOUT
 PLANS.
  
 10.SUBMIT AN APPROVED HOMESTEAD
 EXEMPTION FOR THIS PROPERTY OR A
 CONTRACTOR WILL BE REQUIRED TO OBTAIN A
 PERMIT. FS 489
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-29 Cont ID  
Sent By jleahy Date 2005-09-29 Time 19:53 Rev Time 0.45
Received By jleahy Date 2005-09-29 Time 19:53 Sent To P
Notes
2005-09-29 00:00:00PLAN SHOWS A 1.5 KW WATER HEATER
  
 MAY NEED MAIN AT METER
  
 OUTLET SPACING ???

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-17 Cont ID  
Sent By jleahy Date 2005-08-17 Time 13:24 Rev Time 0.30
Received By jleahy Date 2005-08-17 Time 13:24 Sent To P
Notes
2005-08-17 00:00:00PLANS SHOW DRYER AND WATER HEATER THESE
 ITEMS ARE NOT SHOWN ON PANEL SHEDULE.
  
 ALSO SHOW LOCATION OF PANEL.
  
 COMMENTS CALL JAKE 644-7291

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By jleahy Date 2005-06-22 Time 21:41 Rev Time 0.30
Received By jleahy Date 2005-06-22 Time 21:37 Sent To M
Notes
2005-06-22 00:00:00NEED TO SHOW THE PANEL SCHEDULE SHOWING
 BRANCH CIRCUITS SIZES FOR NEW LOADS.
 WASHER, DRYER, WATER HEATER, ECT
  
 JAKE LEAHY644-7291

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 17:20 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 17:20 Sent To E
Notes
2006-06-07 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-29 Cont ID  
Sent By adarroug Date 2005-11-29 Time 13:29 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 13:29 Sent To B
Notes
2005-11-29 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 15:08 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 15:08 Sent To E
Notes
2005-09-29 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 15:35 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 15:35 Sent To E
Notes
2005-08-16 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-08-05 Time 15:30 Rev Time 0.00
Received By adarroug Date 2005-08-05 Time 15:30 Sent To I
Notes
2005-08-05 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 10:34 Rev Time 0.00
Received By shill Date 2005-06-20 Time 10:34 Sent To E
Notes
2005-06-20 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 16:02 Rev Time 0.00
Received By shill Date 2005-06-09 Time 16:02 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-10-06 Cont ID  
Sent By tgordon Date 2005-10-06 Time 08:32 Rev Time 0.20
Received By tgordon Date 2005-10-06 Time 08:31 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-08-23 Cont ID  
Sent By pkrauss Date 2005-08-23 Time 08:55 Rev Time 0.40
Received By pkrauss Date 2005-08-23 Time 08:54 Sent To P
Notes
2005-08-23 00:00:00DENIED:
 1.PLAN SHEET A-1 INDICATES THE
 ADDITION WILL BE 543 SQUARE FEET.THIS
 WILL INCREASE THE LOAD OF THE A/C SYSTEM
 BY 1 TON.PROVIDE THE EXISTING
 EQUIPMENT INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By hmoser Date 2005-07-06 Time 09:52 Rev Time 0.00
Received By hmoser Date 2005-07-06 Time 09:54 Sent To P
Notes
2005-07-06 00:00:00PLEASE HAVE AIRCONDITIONING CONTRACTOR
 SUBMIT PLANS WITH THERE APPLICATION
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-10-03 Cont ID  
Sent By jleech Date 2005-10-03 Time 08:21 Rev Time 0.25
Received By jleech Date 2005-10-03 Time 08:21 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-20 Cont ID  
Sent By jleech Date 2005-08-20 Time 13:03 Rev Time 0.50
Received By jleech Date 2005-08-20 Time 13:03 Sent To B
Notes
2005-08-20 00:00:00KITCHEN SINK SANITARY WASTE IS NOT
 SHOWN. SHOW DISPOSABLE ROUGHT AND SIZE
 OF PIPE.
 IS INLINE WATER HEATER ELLECTRIC? IF ITS
 GAS IT MUST BE INSTALLED OUT SIDE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-09 Cont ID  
Sent By jleech Date 2005-07-09 Time 07:36 Rev Time 0.33
Received By jleech Date 2005-07-09 Time 07:36 Sent To B
Notes
2005-07-09 00:00:00DENIED;
 WASHING MACHINE TO DISCHARGE DOWN STREAM
 OF THE BATHROOM GROUP. 909.1.
 VENT W/M.
 SEE RED LINES ON ONE SET OF PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By mmclean Date 2005-08-11 Time 17:12 Rev Time 0.00
Received By mmclean Date 2005-08-11 Time 17:12 Sent To I
Notes
2005-08-11 00:00:00APPROVING REVISION FOR THE ADDITION AND
 NEW DRIVEWAY ON LAKE AVE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-17 Cont ID  
Sent By mmclean Date 2005-06-17 Time 17:07 Rev Time 0.00
Received By mmclean Date 2005-06-17 Time 17:06 Sent To I
Notes
2005-06-17 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF UPDATED
 SURVEY SHOWING THE SETBACKS OF THE
 EXISTING STRUCTURE AND LOCATION WITH
 SETBACK OF NEW STRUCTURE.
 2. SITEPLAN DOES NOT PROVIDE INFORMATION
 FOR ZONING REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720