Plan Review Details - Permit 05060752
Plan Review Stops For Permit 05060752
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-02 Cont ID  
Sent By rmcdouga Date 2005-12-02 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2005-12-02 Time 10:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-21 Cont ID  
Sent By rmcdouga Date 2005-10-21 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2005-10-21 Time 09:13 Sent To  
Notes
2005-10-21 00:00:00DENIED
  
 1) SUBMIT COPY OF RERECORDED NOC WITH
 ACCURATE DESCRIPTION OF WORK.
  
 2) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. PLEASE
 SUBMIT PRODUCT APPROVAL WITH COVERSHEET
 LISTING FL# AND THE CORRESPONDING
 EVALUATION REPORT/INSTALLATION
 INSTRUCTIONS FOR THE EXTERIOR IMPACT
 RESISTANT WINDOWS AND DOORS AS SPECIFIED
 ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By rmcdouga Date 2005-07-12 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2005-07-12 Time 11:18 Sent To  
Notes
2005-07-12 00:00:00DENIED
  
 1) DESIGN CRITERIA ON SHEET 1 IS
 INCORRECT. THE BASIC WIND SPEED FOR THE
 CITY OF WPB IS 140 MPH (3 SECOND GUST).
 SEE FBC FIGURE 1606.
  
 2) SSTD-10 CAN NOT BE USED FOR DESIGN IN
 AREAS WITH BASIC WIND SPEEDS GREATER
 THAN 130 MPH. FBC 1606.1.1.
  
 3) THE BUILDING CATEGORY IS II NOT B.
 THE EXPOSURE CATEGORY IS B.
 SEE ASCE 7-98.
  
 4) THE INTERNAL PRESSURE COEFFICENT IS
 PLUS OR MINUS 0.18 PER ASCE 7-98.
  
 5) REVISE GENERAL NOTE 1 FROM STANDARD
 TO FLORIDA BUILDING CODE.
  
 6) SPECIFY THE OCCUPANCY TYPE AS
 R1,R2,R3 OR R4 AS APPLICABLE.
 SEE FBC 311.2.
  
 7) SPECIFY THE NUMBER OF UNITS IN THIS
 BUILDING.
  
 8) SUBMIT ENGINEERING FOR THE NEW
 TRUSSES.
  
 9) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE NEW EXTERIOR WINDOWS AND DOORS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 10) SPECIFY HOW EXTERIOR GLAZING WILL BE
 PROTECTED FROM WINDBOURNE DEBRIS. SEE
 FBC 1606.1.4 AND 3401.7.2.4. IF NOT
 INSTALLING IMPACT RATED WINDOWS, SUBMIT
 A STORM PANEL INSTALLATION PLAN FOR THE
 BUILDING OFFICIAL TO REVIEW. IF THERE IS
 AN EXISTING APPROVED PLAN, SUBMIT A
 COPY.
  
 11) THE SCOPE OF WORK ON THE PLANS IS
 MORE THAN LISTED ON THE APPLICATION.
 GIVE ADEQUATE DESCRIPTION OF WORK.
  
 12) THE GENERAL DISCRIPTION OF
 IMPROVEMENTS WAS LEFT BLANK ON THE NOC.
 RE-RECORD NOC WITH THIS REQUIRED
 INFORMATION. SEE FS 713.13.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-06 Cont ID  
Sent By dpalmer Date 2005-12-06 Time 11:20 Rev Time 0.00
Received By dpalmer Date 2005-12-06 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-20 Cont ID  
Sent By dpalmer Date 2005-10-20 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2005-10-20 Time 09:40 Sent To  
Notes
2005-10-20 00:00:00********* UNSAT *************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE
 INFORMATION NOW SHOWN.
  
  
 1)NOTE: PLEASE SEE LETTER FROM ARCHITECT
 PERTAINING TO SIGNATURE VERIFICATION.
 PLEASE SEE TITLE BLOCKS ON LTRS ARE
 STILL INDICATING "ENGINEER'S".
 PLEASE ALSO SEE THAT LETTER MUST BE
 CORRECTLY NOTORIZED UNDER FS 117.05.
  
 2)NOTE: PLEASE SEE SERVICE SHOWN
 INDICATES AN EXISTING 60A SERVICE WITH
 110A'S LOAD?
 PLEASE SEE PANEL SCHEDULE ALSO MENTIONS
 MIN SERVICE TO BE 125A'S , HOWEVER
 PANELS/RISER WAS NOT INCREASED TO SHOW
 AN UPGRADE IN THE ELECTRICAL SERVICE.
 PLEASE SUBMIT A NEW REVISED ELECTRICAL
 RISER DIAGRAM, PANEL, CONDUCTORS, ETC.
 PLEASE SEE 310.16,240.4, ETC.
  
 3)NOTE: PLEASE SEE MISSING GFI RECEPT
 REQUIRED ON PENINSULAR. 210.52C3
  
 4)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT PER
 210.52D,210.11C3, MUST BE 20A AND #12.
  
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIOAL AND REPEAT COMMENTS ON PLAN
 REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By dpalmer Date 2005-06-20 Time 15:58 Rev Time 0.30
Received By dpalmer Date 2005-06-20 Time 15:58 Sent To  
Notes
2005-06-20 00:00:00*********UNSAT *********
  
 1)NOTE: PLEASE INCLUDE ALL CIRCUTING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE VERIFY IF PANEL IS NEW OR
 EXSITNG.
 PLEASE INCLUDE LOAD/FEEDER SIZE TO UNTI.
 PLEASE INCLUDE ALL MIN CIRCUITING PER
 2002 NEC, 210.52D, 210.11C1-3, 210.12
 210.52A,B,C , 210.52CC-5 ETC
  
 2)NOTE: PLEASE CORRELATE TITLE BLOCK AS
 SHOWN WITH FIRM # AND NAME LISTED WITH
 STATE DBPR. STATE DOES NOT INCLUDE
 ENGINEERS AS ARCH FIRM AND A SEPARATE
 CA#MAY BE REQUIRED PER FS 471.023, FAC
 61G15-23.002
  
 3)NOTE: PLEASE SEE PLANS APPEAR TO BE
 "SIGNED" WITH INITIALS? PLEASE SEE FS
 481.221, FAC 61G1-16PLEASE SEE IF THIS
 IS INDEED "LEGAL SIGNATURE" , PLEASE
 PROVIDE A SIGNED, SEALED NOTORIZED
 LETTER FOR VERIFICATION. THIS WILL BE
 PLACED IN SIGNATURE FILE FOR FUTURE
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-11-28 Cont ID  
Sent By nmccray Date 2005-11-28 Time 10:16 Rev Time 0.00
Received By nmccray Date 2005-11-28 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By mcarsill Date 2005-06-20 Time 11:10 Rev Time 0.00
Received By mcarsill Date 2005-06-20 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-28 Cont ID  
Sent By adarroug Date 2005-11-28 Time 09:45 Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 09:45 Sent To  
Notes
2005-11-28 00:00:00TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-14 Time 11:51 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 11:51 Sent To  
Notes
2005-10-19 00:00:00TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-07-13 Time 13:51 Rev Time 0.00
Received By shill Date 2005-06-09 Time 13:51 Sent To  
Notes
2005-07-12 00:00:00MOVED TO "BOB" BD#4
2005-06-17 00:00:00COMM BOARD #13
2005-06-09 00:00:00TO ELEC BOX
 AWAITING SPACE ON COMMERCIAL BOARD
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-01-30 Cont ID  
Sent By pkrauss Date 2006-01-30 Time 06:09 Rev Time 0.00
Received By pkrauss Date 2006-01-30 Time 06:09 Sent To  
Notes
2006-01-30 00:00:00EQUIPMENT CHANGE / SAME TONNAGE & SEER /
 MANUFACTURER CHANGE ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-11-30 Cont ID  
Sent By rregueir Date 2005-11-30 Time 17:25 Rev Time 0.00
Received By rregueir Date 2005-11-30 Time 17:24 Sent To  
Notes
2005-11-30 00:00:00----------------PROVISO-----------------
 1) SLEEPING ROOM SHALL HAVE BALANCED
 RETURN AIR PER FBC,M 601.4
  
 2) PLAN DOES NOT INDICATE A FIRE DAMPER
 LOCATED IN A/C CLOSET AT SUPPLY PLENUM
 CEILING PENETRACTION AS REQUIRED BY NOTE
 3 ON PLAN.PROVIDE FIRE DAMPER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS
 ON-SITE FOR INSPECTION.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-15 Cont ID  
Sent By prafter Date 2005-11-15 Time 08:57 Rev Time 0.50
Received By prafter Date 2005-11-15 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-07-13 Cont ID  
Sent By hmoser Date 2005-07-13 Time 15:18 Rev Time 0.00
Received By hmoser Date 2005-07-13 Time 15:18 Sent To  
Notes
2005-07-13 00:00:00NO PLANS HM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-11-30 Cont ID  
Sent By jleech Date 2005-11-30 Time 13:10 Rev Time 0.50
Received By jleech Date 2005-11-30 Time 13:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-22 Cont ID  
Sent By pschmitz Date 2005-10-22 Time 07:08 Rev Time 0.00
Received By pschmitz Date 2005-10-22 Time 07:08 Sent To  
Notes
2005-10-22 00:00:00REPLACE ALL DAMAGED PLUMBING

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-09 Cont ID  
Sent By kstevens Date 2005-07-09 Time 09:43 Rev Time 0.25
Received By kstevens Date 2005-07-09 Time 09:43 Sent To  
Notes
2005-07-09 00:00:00 
  
 PLUMBING PERMIT REQUIRED
 PLUMBING WORK SHALL BE CONFINED TO
 FIXTURE CHANGE OUT IN SAME LOCATION. IF
 ANY PIPING ALTERATION WORK IS PERFORMED,
 PLANS SHALL BE REQUIRED IN THE FORM OF A
 PLUMBING FLOOR PLAN, WITH SANITARY AND
 WATER ISOMETRIC RISER DIAGRAMS
 SUBMITTED. SECTION 104.3.1.1.
  
  
  
  
  
 .